Figure 32: System Config Web Page – Part Two
System Configuration
HVAC 1 Interface
HVAC 2 Interface
Communications interface to HVAC unit 2:
•
CoolLinks™ DX
•
Hardwired DX (default)
Note that changing the interface type requires a controller restart and
the technician is prompted to confirm or cancel the request. After the
restart the Wi-fi has to be re-enabled to connect to the controller.
Supplemental Blower
Use the blower on the DX unit to supplement air flow:
•
Off (default)
•
On
If enabled, the evaporator blower on the DX unit will run together with
the DAC/WAC blower when the temperature rises above the DAC
blower high speed enable set point (see section 5.6). The purpose is
to increase the rate of exchange of air inside the shelter.
System FA Code
Text entry field
Enter the six-digit FA code for the site.
Table 16: System Config Web Page Components