5.6 DX Menu
For system configurations with dual DX HVAC units shows status of both DX units.
Figure 25: DX Unit Menu Web Page
DX1/DX2
DX 1/DX 2 unit status:
•
: Power on.
•
: Communications alarm or power failure alarm.
•
: Mechanical cooling active.
•
: Blower running.
•
: Mechanical heating active.
Touching the symbol opens the DX unit control screen for selected unit.
Indicates that this unit is the lead DX unit. The system automatically
swaps the lead and lag unit every 24 hours.
Lead swap push button. Touch to swap the lead and lag unit. If the
lag unit has a communications alarm or power failure alarm or is in
lockout, the system will not swap. If the lead unit experiences a
communications alarm or power failure alarm or lockout while cooling,
the system will automatically swap to the lag unit.
Table 12: DX Menu Web Page Components