5.7 DX Unit Control
Provides functions to control the operation of the equipment associated with the DX unit.
Figure 26: DX Unit Control Web Page
Auto
Auto mode push button (default auto). Touch to disable auto (grey)
and touch again to enable auto (green). Note that re-selecting auto
will automatically de-energize any equipment that was energized while
auto mode was disabled.
Compressor
When not in auto, touch push button to turn on compressor (green)
and touch again to turn off compressor (grey). If the indoor blower is
not currently running, activating the compressor will automatically
cause the indoor blower to run. Note that the anti-short cycle timer
may prevent the compressor from running until the timer has expired
(typically three minutes).
Heater
When not in auto, touch push button to turn on heater (green) and
touch again to turn off heater (grey). If the indoor blower is not
currently running, activating the heater will automatically cause the
indoor blower to run. Note that there may be up to a ten second delay
after the blower starts running before the heater will turn on.
Indoor Blower
When not in auto, touch push button to turn on indoor blower (green)
and touch again to turn off indoor blower (grey). Note that if the
compressor or heater is energized it is not possible to turn the indoor
blower off.
Table 13: DX Unit Web Page Components