It can be used with Marvair’s ComPac
®
I or II unique vertical packaged wall mount air conditioners
or Marvair’s environmental control units. See CommStat 3 Product Data Sheet for installation and
programming instructions.
LL357D4 Lead/Lag Controller
(See Figure 8b)
The Marvair
®
LL357D4 is a complete control package designed to operate a fully or partially redundant
air conditioning system. It consists of a two-stage heat and two-stage cool electronic thermostat and
a solid state timer. It can be used with either the Marvair ComPac
®
I vertical packaged wall mount air
conditioner or our unique ComPac
®
II air conditioner with built-in economizer. The LL357D4 provides
environmental control and the security demanded by the communication shelter industry for a backup
unit. The lead/lag controller insures equal wear on both air conditioners while allowing the lag unit
to assist upon demand. The LL357D4 is factory wired, tested, and mounted in an enclosure for quick
installation. Refer to the LL357D4 Product Data Sheet for complete installation instructions.
Operational Specifications
• Thermostat Range: 45ºF to 90ºF (7ºC to 32ºC)
• Accuracy: ±1ºF (± ½ºC)
• Changeover Temperature Differential (separation between the heat set point and the cool set point):
2ºF to 9ºF (1.0ºC to 4.5ºC)
• First Stage Temperature Differential (number of degrees between the set point temperature and the
“turn on” temperature): 1ºF to 3ºF (.5ºC to 1.5ºC)
• Second Stage Temperature Differential (number of degrees between when stage 1 turns on and
when stage 2 turns on): 1ºF to 6ºF (.5ºC to 3.0ºC).
• Minimum Cool Temperature Set Point: Adjustable from 45ºF to 75ºF (7ºC to 24.0ºC).
• Maximum Heat Temperature Set Point: Adjustable from 55ºF to 90ºF (13ºC to 32.0ºC)
• Staged OFF Outputs: Air conditioners will turn off independently.
Timing Device
• Solid state timer with both 3.5 and 7 day changeover capability.
NOTE: Cut timer circuit wire to provide 3.5 day changeover. Timing accuracy ±5%.
• Momentary push button for accelerated manual timer advance. (9 seconds = 7 days)
• Light emitting diode indicates power on and identifies the lead unit.
Unit Shutdown/Fire Alarm Systems
Immediate shutdown of the air conditioning system can be accomplished by wiring the normally closed
set of contacts in the fire extinguishing or alarm system across terminals 8 and 10 on the low voltage
terminal board inside the air conditioner. Note: The factory jumper between these terminals must be
removed.
This function cannot be accomplished at the wall thermostat because the fan purge on the electronic
control board inside the unit allows the indoor blower to operate from 10 to 90 seconds following each
cool "on" cycle.
NOTE:
The fan purge on the electronic control board allows the indoor fan to run for approximately
10 to 90 seconds after the compressor is off. This operation provides a small improvement in system
efficiency.