55908059-01
19
C
Low superheat alarm timeout (LowSH)
(0= alarm DISABLED)
300
0
18000
s
I
43
170
C
Low evap temp alarm timeout (LOP)
(0= alarm DISABLED)
300
0
18000
s
I
41
168
C
High evap temp alarm timeout (MOP)
(0= alarm DISABLED)
600
0
18000
s
I
42
169
C
High cond temp alarm timeout (High Tcond)
(0= alarm DISABLED)
600
0
18000
s
I
44
171
C
Low suction temperature alarm threshold
-50
-85 (-121)
200 (392)
°C(°F)
A
26
25
C
Low suct temp alarm timeout
(0= alarm DISABLED)
300
0
18000
s
I
9
136
C
Alarm delay S1
0
0
240
s
I
131 258
C
Alarm delay S2
0
0
240
s
I
132 259
C
Alarm delay S3
0
0
240
s
I
133 260
C
Alarm delay S4
0
0
240
s
I
134 261
VALVE
C
EEV minimum steps
50
0
9999
step
I
30
157
C
EEV maximum steps
480
0
9999
step
I
31
158
C
EEV closing steps
500
0
9999
step
I
36
163
C
EEV nominal step rate
50
1
2000
step/s
I
32
159
C
EEV nominal current
450
0
800
mA
I
33
160
C
EEV holding current
100
0
250
mA
I
35
162
C
EEV duty cycle
30
1
100
%
I
34
161
C
EEV opening synchroniz.
1
0
1
-
D
20
19
C
EEV closing synchroniz.
1
0
1
-
D
21
20
* User: A= Service (installer), C= Manufacturer.
**Type of variable: A= analogue, D= digital, I= integer
Содержание A2LCELLARMATCH
Страница 1: ...55908059 01 A2LCELLARMATCH TECHNICAL MANUAL ...
Страница 12: ...55908059 01 12 2G CONDENSING UNIT WIRING DIAGRAMS ...
Страница 14: ...55908059 01 14 ...
Страница 22: ...55908059 01 22 2K COMPONENT IDENTIFICATION SMC ...
Страница 31: ...55908059 01 31 3H EVAPORATOR WIRING DIAGRAM 3I REFRIGERANT SYSTEM SCHEMATIC DIAGRAM ...