55908059-01
27
3D EVAPORATOR INSTALLATION
When installing a cellar cooling system utilising an A2L refrigerant it is important to ensure that sufficient free
space is allowed around the evaporator. The correct amount of space will ensure that, in the unlikely event of a
leak occurring, a flammable mixture is not created.
I
NSTALLATION
CONTENTS
PARTS DESCRIPTION
QTY
ACTION
Envelope containing operating instructions and
Declaration of Conformity
1
Pass to the end user.
Mounting brackets
2
Use to hang unit.
Drain Stub/Nut/Gasket
1
Fitted by installer.
Drain stub adaptor
1
Convert to ¾
"
drain if required.
Screw M5
6
To fix brackets to unit.
Washer nylon
6
To fix brackets to unit.
Washer M5 shakeproof
6
To fix brackets to unit.
The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the appropriately sized
outdoor unit; this instruction should be used in conjunction with the outdoor unit installation instructions.
UNIT COMBINATIONS
1. Fit all kits prior to installing the unit.
2. Ensure that the mounting surface will support the operating weight of the unit.
3. Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength fasteners
(ensure that the unit is positioned to give sufficient access (min 0.5m) to the removable side panel).
4. Fix the mounting brackets to the unit in the correct position for wall or ceiling mounting.
5. Raise the unit into position and secure the fixings,
ensuring that it is square and level.
6. Remove the drain tray then fit the drain stub, nut &
gasket. Refit the drain tray
NITROGEN CHARGE
The unit contains a small charge of dry nitrogen, which should be discharged into the atmosphere. This is a non-
toxic, non-ozone depleting gas with no global warming potent
Minimum Set Temperature 8°C
INDOOR UNIT
OUTDOOR UNIT
CXE 30
SMC 20
CXE 40
SMC 30
CXE 50
SMC 45
CXE 70
SMC 50
CXE 70
SMC 80
DRAIN TRAY
GASKET
NUT
DRAIN STUB
Содержание A2LCELLARMATCH
Страница 1: ...55908059 01 A2LCELLARMATCH TECHNICAL MANUAL ...
Страница 12: ...55908059 01 12 2G CONDENSING UNIT WIRING DIAGRAMS ...
Страница 14: ...55908059 01 14 ...
Страница 22: ...55908059 01 22 2K COMPONENT IDENTIFICATION SMC ...
Страница 31: ...55908059 01 31 3H EVAPORATOR WIRING DIAGRAM 3I REFRIGERANT SYSTEM SCHEMATIC DIAGRAM ...