background image

 

 

 

PROBLEM 

CAUSE 

SOLUTION 

NO AIR BLOWING 
OUT OF DISCHARGE 
NOZZLE 

- No power being supplied to the unit 

from the electrical power source 

 - Confirm power source / check if in on position 

  

 - Circuit breaker is tripped 

 - Reset circuit breaker 

  

 - Blown fuses on power supply  

 - Replace fuses 

  

 - Motor overload is open or tripped 

 - Allow the motor to cool down; motor has auto reset 

internal overload; if unit is panel equipped, press 
reset button on overload inside panel, or replace 
motor overload if overload remains tripped 

  

 - Motor contactor / relay defective  

(if applicable) 

 - Check voltage to coil; check contacts to see if they 

are pulling in 

  

 - Failed switch 

 - Replace or repair limit switch 

MOTOR IS RUNNING 
BUT FANS ARE NOT 
SPINNING 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

ELECTRICAL 
CONTROLS NOT 
WORKING WHEN 
DOOR IS OPEN 

 - Switch is in off position 

 - Turn unit's switch to the on position 

  

 - Door limit switch is not operating 

 - Repair or replace door limit switch 

UNIT WILL NOT TURN 
OFF 

 - Door limit switch is permanently 

closed or energized 

 - Position the door switch in a manner that turns off the 

unit when the door closes and turns on the unit when 
the door opens.  Only light pressure required. 

LOW AIR FLOW 

 - Discharge air vanes out of 

adjustment 

 - Adjust vanes to proper position                           

(Refer to Start-Up Section in this manual) 

  

 - Obstruction on intake or discharge 

 - Remove obstruction or move air curtain  

  

 - Power leads out of polarity                                       

 - Switch power leads to correct polarity                                            

(3 phase models only) 

  

 - Blower motor rotating below normal 

speed 

 - Apply proper voltage per unit requirement             

(see unit label) / Adjust adjustable motor speed knob 
(if applicable) 

  

 - Fan rubbing against housing 

 - Free fan from housing 

  

 - Blower wheels clogged with dirt 

 - Clean and remove dirt from blower wheels 

EXCESSIVE AIR 
VELOCITY AT DOOR 
OPENING 

 - Nozzle out of adjustment and not 

angled far out enough (BD only) 

 - Adjust nozzle angle to outside 

  

 - Air temperature too cold 

 - Add auxiliary heat to overcome wind chill 

  

 - Air stream pushing air outside of the 

building 

 - Adjust discharge angle back into building 

  

 

  

AIR NOT HITTING 
THE FLOOR 

 -  Low air velocity  

 - Adjust vanes to proper position or check installation 

height (Refer to Start-Up Section in this manual) 

  

 -  Obstruction in the direction of air flow 

 - Remove obstruction or move air curtain              

(Move out 3/8" for every 1" up from the door) 

  

 -  Negative building pressure 

 - Provide a make-up air system to relieve negative 

building pressure 

UNEVEN AIR 

 - Shaft rotating inside fan 

 - Replace fan or tighten fan on shaft 

  

 - One motor not functioning 

 - Replace or repair motor 

EXCESSIVE NOISE 
AND OR VIBRATION 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

  

 - Bearing end caps worn 

 - Replace Bearing end caps 

  

 - Damaged blower wheel 

 - Replace Blower Wheel 

  

 - Bearing end caps worn 

 - Replace Bearing end caps 

  

 - Balancing clips missing 

 - Replace Blower Wheel 

TROUBLESHOOTING 

 

Содержание Wind Stopping 16 Series

Страница 1: ...out notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA WMH Electric H...

Страница 2: ...entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Page Content 3 4 WMH Electric...

Страница 3: ......

Страница 4: ...ly Made in the USA Electric Heater Coil and Wiring Electric Heaters are U L listed for Zero Clearance Coils are an open type for rapid temperature rise to be located in the air curtain s intake direct...

Страница 5: ......

Страница 6: ...odels Low voltage 24V control Fan and Heat Control Switch Remote Wall Mounted by others Do not mount low voltage thermostat greater than 30ft from the air curtain Mounting the low voltage thermostat t...

Страница 7: ...nged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical...

Страница 8: ...6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installa...

Страница 9: ...s The WMI WMH Series can be configured with Flat Bank or V Bank Filter Sections as options GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any q...

Страница 10: ...s of the housing Note Bracket Support mounting is not generally recommended for Air Curtains equipped with steam or hot water coils Overhead installation using threaded rods with independent suspensio...

Страница 11: ...blower wheels note direction arrows on the blower wheel housing Correct if needed by changing polarity of three phase power L VERY IMPORTANT Using a clamp meter measure the amperage to each motor and...

Страница 12: ...all the product reverse the procedures above 8 Reconnect the power source to the product 9 If you have any questions regarding the maintenance of the product contact the manufacturer SPECIAL APPLICATI...

Страница 13: ...bstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed...

Страница 14: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black...

Страница 15: ...ninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 Third party claims against you for damages or 2 Special incidental or indirect dama...

Страница 16: ...switch with terminals provided The thermostat should be mounted as close to the product s discharge air flow as possible in order to best sense the discharged air temperature around the door opening C...

Страница 17: ...assembled transitions are provided FIG 5 Indirect Fired Gas Heated HV Unit Note 1 Assemble the transition section s 2 Measure the width of the transition section s to determine the installation locat...

Страница 18: ...CLUDES A Air curtains for pedestrian entrances B Air curtains for vehicular entrances C Air curtains for large loading dock doors 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed s...

Страница 19: ...for Forced Circulation Air cooling and Air Heating Coils F CRN Canadian Registration Number Coil G ANSI Z223 NFPA 54 National Fuel Gas Code H NEC National Electric Code 1 4 SUBMITTALS A Submit under...

Страница 20: ...on B Installer Qualifications Minimum five years documented experience installing products specified in this Section 1 6 DELIVERY STORAGE AND HANDLING A Store products in manufacturer s unopened packa...

Страница 21: ...s indicated d Electrical Characteristics 208 230V AC three phase 19 0 15 8 Amp full load per motor fan e Electrical Characteristics 460V AC three phase 7 9 Amp full load per motor fan f Electrical Cha...

Страница 22: ...vanes with a plus minus 40 degree sweep front to back 2 Air Velocity at Nozzle a WMH 96 2 99 Inch 2516 mm Wide Units 3732 feet min 18 9 m s two 5HP motor fan assemblies b WMH 120 2 123 Inch 3126 mm W...

Страница 23: ...coils for field mounting on air intake side of the air curtain cabinet with opposite end connections 1 Output Air curtain manufacturer s standard one row coils 2 Output Air curtain manufacturer s stan...

Страница 24: ...ch is used to automatically start and stop the air curtain Thermostat is included with optional motor control panel for field installation Provide motor control panel as follows 1 Thermostat Wall moun...

Страница 25: ...3 1 EXAMINATION A Verify that required utilities are in correct location and are of correct capacities for specified products B Verify openings to receive air curtains are plumb level square accurate...

Страница 26: ...asuring air temperature 6 inches off the floor Optimal reading is halfway between the temperature inside and outside the building 3 4 CLEANING A Clean air curtains promptly after installation in accor...

Страница 27: ...ions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description ht...

Отзывы: