background image

PH12 (Phantom 12) Series 

Electric Heated 

 

Model Lengths 36” – 144”  

 
 

14716 S. BROADWAY, GARDENA, CA 90248 

● Ph: (310)532

-1555 Fax: (310)532-

3030 ● 

www.marsair.com

 

© Copyright Mars Air Systems, LLC 2014 

NOTE: MARS AIR SYSTEMS, LLC reserves the right to change specifications and product design without notice. Such revisions do not entitle the buyer to corresponding changes, improvements, additions, or replacements 
for previously purchased equipment. 

 

MARS AIR SYSTEMS, LLC 

● 

GARDENA, CA 

● 

USA

 

VM, 10/02/20

 

MARS Air Systems, LLC certifies that the Air Curtains shown on  this data 
sheet are licensed to bear the AMCA seal. The ratings shown are based on 
tests and procedures performed in accordance with AMCA Publication 211 
and comply with the requirements of the AMCA Certified Ratings Program. 

The AMCA Certified Ratings Seal applies to airflow rate, average outlet 
velocity, outlet velocity uniformity, velocity projection and power rating at 
free delivery only. 

NOTE: Models PH1260-1 & PH12120-2 are not AMCA Certified. 
 

Electric Heated Data Sheet 

 Applications: Environmental Separation: Max Height 16’ 

/

 

Insect Control: Max Height 14’ 

 

 

Features:  

Air Curtain 

 

1 HP Continuous Duty TEAO Motors 

 

Recessed mounted in ceiling for invisible coverage  

 

ETL Certified to conform to UL 2021 (US) and CSA 22.2 (Canada) Standards 

 

(4) 3/8” top mounting holes provided  

 

Utilized in premium design concepts 

 

Durable aluminum construction 

 

Cabinet has sufficient strength for fastening to wall on both ends without 

intermediate support. (Tandem mounted units longer than 72” require center 

support) 

 

Cleanable polyester filters included as standard 

 

Adjustable air directional vanes with 40° sweep front to back 

 

Standard color is Pearl White  

 

Rust preventative electrostatic polyurethane powder coating 

 

18-month parts warranty 

 

Freight Included (FOB Continental USA)  

 

Proudly Made in the USA  

Electric Heater Coil and Wiring 

 

Coils are an open type for rapid temperature rise to be located in the air curtain's intake directly in 

the air stream 

 

Manual reset thermal overload protection provided 

 

Controls internally mounted, prewired ready for power connection and accessible through the 

bottom intake or top access panels 

 

A heat/off/fan switch is unit mounted at the bottom and the control voltage is 24 volts 

 

A wall mounted 24-volt thermostat is included (field wired and installed by others) 

Mars Recommended Accessories (See Submittals for additional details):  

 

Door Limit Switches 

o

 

99-018, Commercial surface mounted magnetic switch, 24v 

 

Controllers  

o

 

SK-EU, SimpleLink, 208V-575V, (460-575V, 3PH needs additional 115-230V, 1PH power), Integral 

Control, Nema1 

 

Factory Mounted Options 

o

 

INS-TD, Adjustable time delay (1 sec to 17 min) 

o

 

INS-HD, Heat on demand 

o

 

INS-2S, Unit mounted 2 speed switch (460-575V, 3PH needs additional 115-230V, 1PH power) 

o

 

BMS-300, BMS for monitor and control 

Note: Dry contact provided in panel for monitoring motor and heater. 24Vac signal provided from panel for 

controlling motor and heater.  

 

Disconnects 

o

 

99-122 & 99-123, Non-Fused Disconnect, remote mounted, 

600V, 32A & 80A respectively, 3 Pole, IP65 

o

 

99-***-**, Fused Disconnect, remote mounted, 240V-600V, 

30A-100A, 3 Pole, Nema3R (See disconnect submittals for 

complete part numbers) 

 

Sound Levels: (measured at 10’ in an open field) 

 

1 Motor Unit = 70 dBA; 2 Motor Unit = 73 dBA; 3 & 4 Motor Unit 

= 75 dBA 

PH12

(Phantom 12)

Model Number

Nozzle Length

(in)

Length

(in)

Depth

(in)

Height

(in)

Motor

(hp)

Weight

(lbs)

Max Core 

Velocity at 

Nozzle (fpm)

Avg Velocity

(fpm)

Volume

(cfm)

Uniformity

(%)

Power Rating

(watts)

PH1248-1E**-PW

48

48

26

17

1

100

5203

3164

2373

91

1190

PH1260-1E**-PW

60

60

26

17

1

105

5055

3539

2654

90

1290

PH1272-2E**-PW

72

72

26

17

Two 1

170

5500

2789

4184

80

2180

PH1284-2E**-PW

84

84

26

17

Two 1

190

5250

3089

4634

89

2190

PH1296-2E**-PW

96

96

26

17

Two 1

195

5203

3164

4746

91

2380

PH12120-2E**-PW

120

120

26

17

Two 1

210

5055

3539

5308

90

2580

PH12144-4E**-PW

144

144

26

17

Four 1

340

5500

2789

8368

91

4360

Mechanical Data

AMCA Certified Lab Data

Note: Data above for 1725 RPM at 60 Hz. 50 Hz is 1425 RPM with a 17% reduction in 

the performance data.

* - Use corresponding letters in "Electrical Data" & "Heater Wattage Data" columns to complete the model 

numbers.

1. The AMCA Certified Ratings Seal applies to airflow rate, average outlet velocity, outlet velocity uniformity, velocity projection and power rating at free delivery only. 

2. Rated data shown are only for electric heated units, as shown. 

 

Temp 

Rise

208v/3Ø

(E)

230v/3Ø

(F)

460v/3Ø

(H)

575v/3Ø

(I)

(H)

(N)

(T)

°F

PH1248-1E**-PW

37

34

17

14

12

-

-

15

PH1260-1E**-PW

37

34

17

14

12

-

-

14

PH1272-2E**-PW

74

67

34

27

-

24

-

16

PH1284-2E**-PW

74

67

34

27

-

24

-

15

PH1296-2E**-PW

74

67

34

27

-

24

-

15

PH12120-2E**-PW

74

67

34

27

-

24

-

14

PH12144-4E**-PW

147

134

67

54

-

-

48

16

* - Use corresponding letters in "Voltage Code" and "Wattage

     Code" to complete the model numbers.

Three Phase

Electrical Data

(FLA)

For ampacity, multiply FLA X 1.25       

Motor amps per motor: 9A @ 115v; 5A @ 208v/230v/1Ø; 3.3A @ 208v/3Ø; 3.2A @ 230v/3Ø; 1.6A @ 460v; 1.3A @ 575v/3Ø

Unit Voltage

(Voltage Code)

Amperage

Heater Kilowatts

(Wattage Code)

kW

Temp 

Rise

208v/1Ø

(B)

230v/1Ø

(C)

(B)

(H)

(N)

°F

PH1248-1E**-PW

34

32

6

-

-

7

PH1260-1E**-PW

34

32

6

-

-

7

PH1272-2E**-PW

68

63

-

12

-

8

PH1284-2E**-PW

68

63

-

12

-

8

PH1296-2E**-PW

68

63

-

12

-

7

PH12120-2E**-PW

68

63

-

12

-

7

PH12144-4E**-PW

136

125

-

-

24

8

For ampacity, multiply FLA X 1.25       

* - Use corresponding letters in "Voltage Code" and

     "Wattage Code" to complete the model numbers.

 Single Phase

Electrical Data

(FLA)

Heater kilowatts

(Wattage Code)

kW

Unit Voltage

(Voltage Code)

Amperage

Motor amps per motor: 5A @ 208/230v/1Ø

Model

Distance 

from nozzle 

(in)

Avg. Core 

Velocity 

(FPM)

40

1494

80

1053

120

986

160

953

200

948

Projection Velocity

PH1236-1E*

Содержание PH12 Series

Страница 1: ...hout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH12 Electric Heated Series Phantom 12 Series Commercial Air Curtain Submittal Package Submitted by Mars Air Systems LLC 14716 S Broadway Gardena CA 90248 P O S Q Company Print Name Signature Date Company Seal or ...

Страница 2: ...entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Page Content 3 4 PH12 Electric Submittals 5 6 Typical Electric Heated Wiring Diagrams 7 Thermostat Submittals 8 9 Accessory Installation Supplement 10 13 Installation Operation and Maintenance 14 15 Heated Products Supplement 16 ...

Страница 3: ......

Страница 4: ...emand o INS 2S Unit mounted 2 speed switch 460 575V 3PH needs additional 115 230V 1PH power o BMS 300 BMS for monitor and control Note Dry contact provided in panel for monitoring motor and heater 24Vac signal provided from panel for controlling motor and heater Disconnects o 99 122 99 123 Non Fused Disconnect remote mounted 600V 32A 80A respectively 3 Pole IP65 o 99 Fused Disconnect remote mounte...

Страница 5: ......

Страница 6: ......

Страница 7: ...models Low voltage 24V control Fan and Heat Control Switch Remote Wall Mounted by others Do not mount low voltage thermostat greater than 30ft from the air curtain Mounting the low voltage thermostat too far from the air curtain may cause a voltage drop and cause chattering Options and Accessories 2 Stage Line Voltage Thermostat Digital Programmable Low Voltage Thermostat Digital Low Voltage Therm...

Страница 8: ...inged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical installation of the combination plunger roller type NEMA 1 door limit switch for all non hinged style doors FIG 2 3 All wiring must be per local and NEC National Electric Code codes 4 Panels or cont...

Страница 9: ... 6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use in conjunction with the threaded holes provided on top of unit Note Angle brackets threaded rods and I Beams are provided by others FIGS 7 8 All optional brackets are not available ...

Страница 10: ...e standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any questions contact the manufacturer Only qualified personnel should install this product Installing personnel should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in el...

Страница 11: ...an Assembly MFA shipped internally mounted 4 All units are equipped with 4 3 8 threaded inserts on top for overhead installation FIG 2 5 Determine the exact mounting locations to suspend the unit above the ceiling so that the unit is centered and parallel with the door opening Use 4 threaded rods to suspend the enclosure to the ceiling Note When installed in the ceiling above the door the air curt...

Страница 12: ...on any metal surface C Verify proper voltage prior to powering the product See product label for reference D Check all field wired components if supplied are wired correctly E Check that the inlet air supply and the discharge air supply are free of obstructions F Check that all air filter s and or air intake grille s are in place and installed properly as originally shipped G Verify voltage to the...

Страница 13: ...the outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive VFD is strongly recommended to control the air curtain air flow velocity at the floor level High humid areas may require de humidifier or additional defrost cycle to minimize condensation and freezing...

Страница 14: ... switch with terminals provided The thermostat should be mounted as close to the product s discharge air flow as possible in order to best sense the discharged air temperature around the door opening Connect proper voltage to the product per local and NEC codes Thermal overload protection is built into the heater coil assembly assemblies In the event of an overload condition electrical power will ...

Страница 15: ...its Note Low Profile and Wind Stopping units require the removal of the coil to access the motor and or fans All piping should be done by a licensed pipe fitter and in accordance with local codes and regulations Connect the supply and return fittings as required All traps and valves are sized and field installed by others For Standard High Velocity and Extra Power units front intake screen must be...

Страница 16: ...ion on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed Apply proper voltage per unit requirement see unit label Adjust adjustable motor speed knob if applicable Fan rubbing against housing Free fan from housing Blower wheels clogged with dirt Clean and remove d...

Страница 17: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black Motor Wire L1 Red Motor Wire L2 Black Motor Wire L1 White Motor Wire L3 Red Motor Wire L2 White Motor Wire L3 03 008 P55YYDHB 1527 US Nema 1 1 2 208 230 3 16 1 16 1 16 1 03 008 P55YYDHB 1527 US Nema ...

Страница 18: ...tomer may be responsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 third party claims against you for damages 2 special incidental or indirect damages or 3 any economic consequential damages including lost profits and savings regard...

Страница 19: ...for pedestrian entrances B Air curtains for vehicular entrances 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentry C Section 05 41 00 Structural Metal Studs D Section 07 62 00 Sheet metal flashing E Section 07 92 00 Joint Sealants F Section 08 10 00 Metal Doors and Frames G Section 08 33 00 Overhead Coiling Doors H Section ...

Страница 20: ...vices Listed for US and Canada F AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils G Electrical components UL CUL listed H AMCA 211 Certified I ELT J NEC National Electric Code K Meets NEC and CEC tested by ETL Certified to conform to UL2021 US and CSA22 2 Canada Standards L UL CUL listed M U S Green Building Council LEED Building Design and Construction BD C Version ...

Страница 21: ...acturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in this Section B Installer Qualifications Minimum five years documented experience installing prod...

Страница 22: ...nance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a Wired for single speed operation b Wired for two speed operation c Wired for three speed operation d Provide wash down type motors NEC IP 54 for the locations indicated e Provide explosion proof type motors NEC Class 1 Division 1 Group D for th...

Страница 23: ...dipped galvanized steel sheet housing conforming to ASTM A 591 and or ASTM A 653 b Provide type 304 stainless steel housing with brushed finish ASTM A 240 A 240M 4 Air Inlet Grille and or Filters Provide air inlet grille and or filters specified 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resistant polyurethane powder coated finish for s...

Страница 24: ... d Four Motor Fan Units 75 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature limit controller 2 Thermostat Wall mounted 24 Volt operation with heater on off selection 3 Heating Coils ETL approved as part of unit Meets NEC and CEC tested by ETL Certified to conform to UL2021 US an...

Страница 25: ...n right hand side of air curtain housing 2 Mounting Factory mounted on left hand side of air curtain housing 3 Electrical components UL CUL listed 4 Optional Digital Programmable Controller a Remote Mounted High Resolution 5 Color LCD Display with Capacitive Touch technology b Fully programmable controller c Pre set and fully customizable programs d Time delay Passive Adaptive e 24 7 timer f Maint...

Страница 26: ...ounted outdoor temperature sensors required F Motor Control Panels For Hot Water and Steam Heated Units Recommended for all three phase units and single phase units with combined motor capacities of more than 1HP whenever a door limit switch is used to automatically start and stop the air curtain Provide motor control panels as follows 1 Mounting Shipped loose to be field mounted 2 Mounting Factor...

Страница 27: ...olled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA 1 20 amps ratings in locations indicated b Provide limit switches with NEMA 4X 10 amps ratings in locations indicated c Provide limit switches with NEMA 4X 15 amps ratings in locations indicated d Provide limit switches with NEMA 7 10 amps ratings in locations indicated 2...

Страница 28: ...services and utilities as specified in Section 22 10 00 and 23 21 00 3 3 FIELD QUALITY CONTROL A Adjust air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temp...

Страница 29: ...Mars Phantom 12 CSI Spec Revised 2 3 2021 MARS AIR SYSTEMS LLC 23 34 33 11 3 6 SCHEDULES A Refer to Air Curtain Schedule appended to this section END OF SECTION ...

Страница 30: ...revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description https marsair com Main website https marsair com document library Submittals for all Mars Air Curtains Accessories Installation and Brochures https www marsair com Content Downloads CSISpecs PH10 C...