MAINTENANCE

 

 

Routine maintenance is required to keep this product 

operating at its peak performance and efficiency. Over 

time, the housing, air intake grille, air intake filter, blower 

wheels and motor(s) will accumulate a build up of dust, 

debris and other residue. It is imperative to keep these 

components clean.  Failure to do so will not only lower 

operational efficiency and performance, but also reduce 

the useful life of the product. The time between cleanings 

depends on the application, location, and daily hours of 

use.  On average, under normal use conditions, the 

product should require a thorough cleaning once every 

six (6) months.  

 

To clean the product, perform the following: 

 

1.  Verify the product has been disconnected from the 

power source. 

2.  Use a damp cloth and either a warm mild soapy water 

solution or bio-degradable degreaser, to wipe down the 

exterior components of the housing. 

3.  To access the interior of the product, remove the air 

intake grille(s) and/or air intake filter(s).  This  is 

accomplished by removing the screws on the face of the 

air intake grille(s)/filter(s)  and releasing the grille by 

pulling on the spring hinge. 

4.  Thoroughly clean the air intake grille(s)  and clean  or 

replace the intake filter(s). 

5.  Thoroughly wipe down the motor, blower wheels and 

blower wheel housings.  Be careful not to spray the 

motor with a water hose.  

6.  The motor(s) require no additional lubrication. They are 

permanently lubricated and feature double sealed ball 

bearings. 

7.  To re-install the product, reverse the procedures above. 

8.  Reconnect the power source to the product. 

9.  If you have any questions regarding the maintenance of 

the product, contact the manufacturer. 

 

 

SPECIAL APPLICATIONS 

 

Outdoor Installation 

 

For outdoor unit special consideration may be required 

for enclosure, motor, wheel,  and other components to 

minimize damage caused by exposure to the outdoor 

elements. Contact factory for special construction and 

costing. 

 

Freezer and Cooler Installation 

 

Air curtain must be mounted on the warm side for optimal 

performance. Variable Frequency Drive (VFD) is strongly 

recommended to control the air curtain air flow velocity at 

the floor level. 

 

High humid areas may require de-humidifier or additional 

defrost cycle to minimize condensation and freezing for 

freezer applications. We recommend the air curtain unit 

to not replace doors but work in conjunction with door 

opening sequence cycle.  

Contact factory for details. 

 

DISCLAIMER 

 

Mars reserves the right to change specifications and 

product design without notice. Such revisions do not 

entitle the buyer to corresponding changes, 

improvements, additions, or replacements for previously 

purchased equipment.

 

L. 

VERY IMPORTANT

  Using a clamp meter, measure 

the amperage to each motor and ensure that they do 

not exceed the amperage listed on the product label. 

M.  If applicable, adjust the air intake grille(s) such that the 

output air stream reaches the floor. For temperature 

control and environmental separation applications, the 

air stream should reach the floor with sufficient 

strength to create an air seal around the door opening 

without creating turbulent mixing of the inside and 

outside air. If applicable, adjust the air intake grille(s) 

such that the output air stream reaches the floor. For 

flying insect control applications, the air stream should 

reach the floor with maximum strength. If after proper 

installation and adjustment, the product appears to be 

producing too little or too much air for the application, 

contact the manufacturer. 

 

 WARNING 

To reduce the risk of fire, electrical shock,  or injury to 

persons, observe the following: 

A. Maintenance is to be performed only by qualified 

personnel who are familiar with local codes and 

regulations and are experienced with this type of 

product. 

B. Before servicing or cleaning the product switch power 

off at service panel and lock service panel to prevent 

power from being switched “ON” accidentally.

 

Содержание PH12 Series

Страница 1: ...hout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH12 Electric Heated Series Phantom 12 Series Commercial Air Curtain Submittal Package Submitted by Mars Air Systems LLC 14716 S Broadway Gardena CA 90248 P O S Q Company Print Name Signature Date Company Seal or ...

Страница 2: ...entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Page Content 3 4 PH12 Electric Submittals 5 6 Typical Electric Heated Wiring Diagrams 7 Thermostat Submittals 8 9 Accessory Installation Supplement 10 13 Installation Operation and Maintenance 14 15 Heated Products Supplement 16 ...

Страница 3: ......

Страница 4: ...emand o INS 2S Unit mounted 2 speed switch 460 575V 3PH needs additional 115 230V 1PH power o BMS 300 BMS for monitor and control Note Dry contact provided in panel for monitoring motor and heater 24Vac signal provided from panel for controlling motor and heater Disconnects o 99 122 99 123 Non Fused Disconnect remote mounted 600V 32A 80A respectively 3 Pole IP65 o 99 Fused Disconnect remote mounte...

Страница 5: ......

Страница 6: ......

Страница 7: ...models Low voltage 24V control Fan and Heat Control Switch Remote Wall Mounted by others Do not mount low voltage thermostat greater than 30ft from the air curtain Mounting the low voltage thermostat too far from the air curtain may cause a voltage drop and cause chattering Options and Accessories 2 Stage Line Voltage Thermostat Digital Programmable Low Voltage Thermostat Digital Low Voltage Therm...

Страница 8: ...inged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical installation of the combination plunger roller type NEMA 1 door limit switch for all non hinged style doors FIG 2 3 All wiring must be per local and NEC National Electric Code codes 4 Panels or cont...

Страница 9: ... 6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use in conjunction with the threaded holes provided on top of unit Note Angle brackets threaded rods and I Beams are provided by others FIGS 7 8 All optional brackets are not available ...

Страница 10: ...e standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any questions contact the manufacturer Only qualified personnel should install this product Installing personnel should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in el...

Страница 11: ...an Assembly MFA shipped internally mounted 4 All units are equipped with 4 3 8 threaded inserts on top for overhead installation FIG 2 5 Determine the exact mounting locations to suspend the unit above the ceiling so that the unit is centered and parallel with the door opening Use 4 threaded rods to suspend the enclosure to the ceiling Note When installed in the ceiling above the door the air curt...

Страница 12: ...on any metal surface C Verify proper voltage prior to powering the product See product label for reference D Check all field wired components if supplied are wired correctly E Check that the inlet air supply and the discharge air supply are free of obstructions F Check that all air filter s and or air intake grille s are in place and installed properly as originally shipped G Verify voltage to the...

Страница 13: ...the outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive VFD is strongly recommended to control the air curtain air flow velocity at the floor level High humid areas may require de humidifier or additional defrost cycle to minimize condensation and freezing...

Страница 14: ... switch with terminals provided The thermostat should be mounted as close to the product s discharge air flow as possible in order to best sense the discharged air temperature around the door opening Connect proper voltage to the product per local and NEC codes Thermal overload protection is built into the heater coil assembly assemblies In the event of an overload condition electrical power will ...

Страница 15: ...its Note Low Profile and Wind Stopping units require the removal of the coil to access the motor and or fans All piping should be done by a licensed pipe fitter and in accordance with local codes and regulations Connect the supply and return fittings as required All traps and valves are sized and field installed by others For Standard High Velocity and Extra Power units front intake screen must be...

Страница 16: ...ion on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed Apply proper voltage per unit requirement see unit label Adjust adjustable motor speed knob if applicable Fan rubbing against housing Free fan from housing Blower wheels clogged with dirt Clean and remove d...

Страница 17: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black Motor Wire L1 Red Motor Wire L2 Black Motor Wire L1 White Motor Wire L3 Red Motor Wire L2 White Motor Wire L3 03 008 P55YYDHB 1527 US Nema 1 1 2 208 230 3 16 1 16 1 16 1 03 008 P55YYDHB 1527 US Nema ...

Страница 18: ...tomer may be responsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 third party claims against you for damages 2 special incidental or indirect damages or 3 any economic consequential damages including lost profits and savings regard...

Страница 19: ...for pedestrian entrances B Air curtains for vehicular entrances 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentry C Section 05 41 00 Structural Metal Studs D Section 07 62 00 Sheet metal flashing E Section 07 92 00 Joint Sealants F Section 08 10 00 Metal Doors and Frames G Section 08 33 00 Overhead Coiling Doors H Section ...

Страница 20: ...vices Listed for US and Canada F AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils G Electrical components UL CUL listed H AMCA 211 Certified I ELT J NEC National Electric Code K Meets NEC and CEC tested by ETL Certified to conform to UL2021 US and CSA22 2 Canada Standards L UL CUL listed M U S Green Building Council LEED Building Design and Construction BD C Version ...

Страница 21: ...acturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in this Section B Installer Qualifications Minimum five years documented experience installing prod...

Страница 22: ...nance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a Wired for single speed operation b Wired for two speed operation c Wired for three speed operation d Provide wash down type motors NEC IP 54 for the locations indicated e Provide explosion proof type motors NEC Class 1 Division 1 Group D for th...

Страница 23: ...dipped galvanized steel sheet housing conforming to ASTM A 591 and or ASTM A 653 b Provide type 304 stainless steel housing with brushed finish ASTM A 240 A 240M 4 Air Inlet Grille and or Filters Provide air inlet grille and or filters specified 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resistant polyurethane powder coated finish for s...

Страница 24: ... d Four Motor Fan Units 75 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature limit controller 2 Thermostat Wall mounted 24 Volt operation with heater on off selection 3 Heating Coils ETL approved as part of unit Meets NEC and CEC tested by ETL Certified to conform to UL2021 US an...

Страница 25: ...n right hand side of air curtain housing 2 Mounting Factory mounted on left hand side of air curtain housing 3 Electrical components UL CUL listed 4 Optional Digital Programmable Controller a Remote Mounted High Resolution 5 Color LCD Display with Capacitive Touch technology b Fully programmable controller c Pre set and fully customizable programs d Time delay Passive Adaptive e 24 7 timer f Maint...

Страница 26: ...ounted outdoor temperature sensors required F Motor Control Panels For Hot Water and Steam Heated Units Recommended for all three phase units and single phase units with combined motor capacities of more than 1HP whenever a door limit switch is used to automatically start and stop the air curtain Provide motor control panels as follows 1 Mounting Shipped loose to be field mounted 2 Mounting Factor...

Страница 27: ...olled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA 1 20 amps ratings in locations indicated b Provide limit switches with NEMA 4X 10 amps ratings in locations indicated c Provide limit switches with NEMA 4X 15 amps ratings in locations indicated d Provide limit switches with NEMA 7 10 amps ratings in locations indicated 2...

Страница 28: ...services and utilities as specified in Section 22 10 00 and 23 21 00 3 3 FIELD QUALITY CONTROL A Adjust air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temp...

Страница 29: ...Mars Phantom 12 CSI Spec Revised 2 3 2021 MARS AIR SYSTEMS LLC 23 34 33 11 3 6 SCHEDULES A Refer to Air Curtain Schedule appended to this section END OF SECTION ...

Страница 30: ...revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description https marsair com Main website https marsair com document library Submittals for all Mars Air Curtains Accessories Installation and Brochures https www marsair com Content Downloads CSISpecs PH10 C...

Отзывы: