TROUBLESHOOTING 

 

PROBLEM 

CAUSE 

SOLUTION 

NO AIR BLOWING 
OUT OF DISCHARGE 
NOZZLE 

- No power being supplied to the unit 

from the electrical power source 

 - Confirm power source / check if in on position 

  

 - Circuit breaker is tripped 

 - Reset circuit breaker 

  

 - Blown fuses on power supply  

 - Replace fuses 

  

 - Motor overload is open or tripped 

 - Allow the motor to cool down; motor has auto reset 

internal overload; if unit is panel equipped, press 
reset button on overload inside panel, or replace 
motor overload if overload remains tripped 

  

 - Motor contactor / relay defective  

(if applicable) 

 - Check voltage to coil; check contacts to see if they 

are pulling in 

  

 - Failed switch 

 - Replace or repair limit switch 

MOTOR IS RUNNING 
BUT FANS ARE NOT 
SPINNING 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

ELECTRICAL 
CONTROLS NOT 
WORKING WHEN 
DOOR IS OPEN 

 - Switch is in off position 

 - Turn unit's switch to the on position 

  

 - Door limit switch is not operating 

 - Repair or replace door limit switch 

UNIT WILL NOT TURN 
OFF 

 - Door limit switch is permanently 

closed or energized 

 - Position the door switch in a manner that turns off the 

unit when the door closes and turns on the unit when 
the door opens.  Only light pressure required. 

LOW AIR FLOW 

 - Discharge air vanes out of 

adjustment 

 - Adjust vanes to proper position                           

(Refer to Start-Up Section in this manual) 

  

 - Obstruction on intake or discharge 

 - Remove obstruction or move air curtain  

  

 - Power leads out of polarity                                       

 - Switch power leads to correct polarity                       

(3 phase models only) 

  

 - Blower motor rotating below normal 

speed 

 - Apply proper voltage per unit requirement             

(see unit label) / Adjust adjustable motor speed knob 
(if applicable) 

  

 - Fan rubbing against housing 

 - Free fan from housing 

  

 - Blower wheels clogged with dirt 

 - Clean and remove dirt from blower wheels 

EXCESSIVE AIR 
VELOCITY AT DOOR 
OPENING 

 - Nozzle out of adjustment and not 

angled far out enough (BD only) 

 - Adjust nozzle angle to outside 

  

 - Air temperature too cold 

 - Add auxiliary heat to overcome wind chill 

  

 - Air stream pushing air outside of the 

building 

 - Adjust discharge angle back into building 

  

 

  

AIR NOT HITTING 
THE FLOOR 

 -  Low air velocity  

 - Adjust vanes to proper position or check installation 

height (Refer to Start-Up Section in this manual) 

  

 -  Obstruction in the direction of air flow 

 - Remove obstruction or move air curtain                                                                

(Move out 3/8" for every 1" up from the door) 

  

 -  Negative building pressure 

 - Provide a make-up air system to relieve negative 

building pressure 

UNEVEN AIR 

 - Shaft rotating inside fan 

 - Replace fan or tighten fan on shaft 

  

 - One motor not functioning 

 - Replace or repair motor 

EXCESSIVE NOISE 
AND OR VIBRATION 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

  

 - Bearing end caps worn 

 - Replace Bearing end caps 

  

 - Damaged blower wheel 

 - Replace Blower Wheel 

  

 - Bearing end caps worn 
 - Pillow block bearings make noise 

 - Replace Bearing end caps 
 - Grease Bearing 

  

 - Balancing clips missing 

 - Replace Blower Wheel 

Содержание 03-001

Страница 1: ...come standard with an expanded metal air intake grille s The BD Series can be configured with Flat Bank or V Bank Sections as options GENERAL SAFETY INFORMATION Use this product only in the manner int...

Страница 2: ...acket Support mounting is not generally recommended for Air Curtains equipped with steam or hot water coils Overhead installation using threaded rods with independent suspension of coils is recommende...

Страница 3: ...shipped G Verify voltage to the product once more and turn power on H Regardless of whether the product is mounted on the inside or outside of the door opening set the air directional vanes in the dis...

Страница 4: ...ck bearings require periodic greasing depending on use The Zerk fittings are provided on bearing 7 To re install the product reverse the procedures above 8 Reconnect the power source to the product 9...

Страница 5: ...on on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed Apply p...

Страница 6: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black...

Страница 7: ...rrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 Third party claims against you for damages or 2 Special incidental or indirect damages o...

Отзывы: