Proflame 2 IFC Module and Remote Control
Pairing Remote Control:
Install the 3 AAA type batteries in the battery bay,
located on the base of the Remote Control. Note
polarity of the batteries and insert them as indicated.
Connect the AC power supply to the IFC Module.
Press the SW1 button on the IFC Module so the IFC
will “beep” and a red LED is illuminated to indicate
that the IFC Module is ready to synchronize with a
Remote Control within 10 seconds. With the batteries
already installed in the Remote Control, push the ON
button. The receiver will “beep” four times to indicate
the Remote Control’s command is accepted.
The system is now initialized.
Resetting Proflame 2 IFC Module for Manual Use
If the transmitter gets misplaced, is broken, or is no longer
wanted the PF2 Module can be reset to a manual system.
A manual on/off switch or thermostat may be installed at
the X4 connector (this connection is Jumped at the
factory) no power is required.
The following sequence must be followed to reset the PF2
Module:
Press the Red
SW1
button until you hear three beeps.
Within 10 seconds press the
SW1
button again until
you hear it beep.
The PF2 Module may now be turned on/off manually
(x4 connector) by a switch (not supplied), the pilot will
remain on CPI (continuous pilot ignition) mode, all
other functions of main burner, fan and lights will be
on the high setting.
Fan Startup and Shutdown Timings:
Fan setting is started with a delay of 5 minutes from the
fireplace ignition and stopped with a delay of 12 minutes
from the fireplace switching off.
Low Battery Power Detection
When the Remote Control’s batteries are low, a Battery
Icon will appear on the LCD display before all power is
lost. When the batteries are replaced this icon will
disappear.
Battery Backup
The PF2 module is powered by line voltage (AC) with
provision of battery backup in case of main power loss.
Fans and lighting features will not function with the PF2
Module is powered by battery backup. It is recommended
that the 4 x AA batteries are changed before each heating
season.
LCD Display
ON / OFF Key
Thermostat Key
UP / DOWN Arrow Key
Mode Key
Batteries
SW1
Button
IFC Module
57
Содержание Capri IDV34 Series
Страница 46: ...Gas Conversion for Modulator PART C 46...
Страница 59: ...Proflame 2 Remote Control 59...
Страница 61: ...61...