background image

MAINTENANCE

Your heater is designed for years of trouble-free operation and
requires no special maintenance other than occasional cleaning.
The motor is permanently lubricated.

Cleaning

At least once each year (or more often in dirty environments),
the heater should be cleaned to remove dust and other foreign
material which has collected during the heating season, as 
follows:

1. Turn power off at main switch.

NOTE: With grille removed, the ON/OFF switch located in upper
right corner of heater may be used to turn off power to heater
during cleaning and servicing.

2. Remove front grille by removing the four screws in each 

corner.

3. Use vacuum cleaner with brush attachment to remove dust

and dirt that has accumulated in heater (especially around
element and blower blade). Do not use water or any cleaners
to clean heater components.

4. Replace grille.

5. Wipe grille clean with a damp cloth. DO NOT use waxes or

any cleaners that leave a residue since these may discolor
during heater operation.

6. Turn the main line switch on at the switch panel to restore

power to heater. The heater is now ready for another season
of operation.

THE  OUTSIDE  SURFACES  MAY  BE  CLEANED  WITH  MILD
DETERGENT  AND  A  DAMP  CLOTH  BY  THE  USER. 
ALL OTHER SERVICING SHOULD BE PERFORMED BY AN
ELECTRICIAN OR QUALIFIED PERSON

6

Содержание HTWH Series

Страница 1: ...terials such as furniture pillows bedding papers clothes and curtains away from heater Do not block air intakes or exhaust in any manner For efficient and safe operation we recommend keeping all items at least 3 feet from front of heater 11 Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock fire or damage the heater 12 Should the ...

Страница 2: ... metallic sheathed cable Romex and the supply voltage is 240 or 208 volts two power wires the white wire color must be changed using black electrical tape to comply with the NEC White is only allowed for a Neutral conductor 8 Connect building ground conductor to the back box using the green screw located in the inside top of the back box 9 Secure disconnect switch bracket in place by tightening sc...

Страница 3: ...x Ensure that the back edge of the surface mounting frame is flush against the wall Note If heater is located in a high traffic area where it may be subjected to vandalism or abuse take extreme care to see that the box is firmly attached to the wall 3 Run a power supply cable to the top right corner of the mounting frame Arrangement of wiring to this point must be in accordance with National and L...

Страница 4: ... grille with the flange along top of back box 3 Attach the grille using the 4 mounting screws provided OPERATION Initial Setup Instructions Performed by Installer NOTE After installation the installer should perform the follow ing procedures to ensure proper operation of the heater 1 Turn Unit ON When the heater is first powered up the buzzer beeps for one second and displays all icons in high lum...

Страница 5: ...an be removed and replaced by a Building Management System Switch DO NOT REMOVE THE RED JUMPER UNLESS CONTROL BY A BUILDING MANAGE MENT SYSTEM IS BEING USED A remote dry contact switch connected to terminals A B on the control power board enables or disables control of the heater Only a dry contact is required since it will not carry any load This con tact if open puts the heater in a standby BMS ...

Страница 6: ...ing and servicing 2 Remove front grille by removing the four screws in each corner 3 Use vacuum cleaner with brush attachment to remove dust and dirt that has accumulated in heater especially around element and blower blade Do not use water or any cleaners to clean heater components 4 Replace grille 5 Wipe grille clean with a damp cloth DO NOT use waxes or any cleaners that leave a residue since t...

Страница 7: ...power board 1414 11021 000 1414 11021 000 1414 11021 001 1 6 Thermistor 5262 11006 000 5262 11006 000 5262 11006 000 1 7 Touch Pad Bezel Assembly 1016 11071 000 1016 11071 000 1016 11071 000 1 8 Bezel 1219 11006 000 1219 11006 000 1219 11006 000 1 9 Element Assembly 1802 11005 000 1802 11005 001 1802 11005 002 1 10 Safety Limit Manual 4520 2027 000 4520 2027 000 4520 2027 000 1 11 Fan Motor 3900 2...

Страница 8: ...d Products THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT WHETHER BASED UP...