Page 56
001223MAN-05
1-Jul-2017
HYDRONIC OPERATION TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Low Suction
Pressure
(continued)
TXV stuck almost closed or
partially blocked by foreign
object.
Adjusting the TXV does not affect the
superheat or the suction pressure. TXV
may be frosting up.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Faulty NC solenoid valve or
wiring (valve is open or leak-
ing).
Coil is energized when it should not be,
or valve is cold.
Replace valve or correct wiring.
Low refrigerant charge.
Entering liquid temperature, flow and
entering air temperature are good but
suction is low. Check static refrigeration
pressure of the unit for a very low value.
Locate the leak and repair it. Spray
nine, a sniffer, and dye are common
methods of locating a leak.
High Suction
Pressure
(may appear to
not be pumping)
Leaking reversing valve.
Reversing valve is the same tempera-
ture on both ends of body, common
suction line is warm, compressor is run-
ning hot.
Replace reversing valve.
TXV adjusted too far open.
Verify superheat. It should be between
8-12°F (3-6°C). Superheat will be low if
TXV is open too far.
Adjust TXV to obtain 8-12°F (3-6°C)
superheat.
Faulty compressor, not
pumping.
Pressures change only slightly from stat-
ic values when compressor is started.
Replace compressor.
TXV stuck open.
Adjusting the TXV does not affect the
superheat or the suction pressure. Low
super heat and discharge pressure.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Compressor
frosting up
See Low Suction
Pressure in this section.
TXV frosting up
TXV stuck almost closed or
partially blocked by foreign
object.
Adjusting the TXV does not affect the
superheat or the suction pressure.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Random high
pressure trip
(does not occur
while on site)
Faulty compressor contactor. Points pitted or burned. Contactor
sometimes sticks causing the compres-
sor to run when it shouldn’t, tripping the
high pressure control.
Replace contactor.
Intermittent Indoor circulator. Verify wiring is good.
Correct the wiring or replace the cir-
culator.
Leaking reversing valve.
Reversing valve is the same tempera-
ture on both ends of body, common suc-
tion line is warm, compressor is running
hot.
Tap reversing valve, and switch it
back and forth between heating and
cooling positions. If this does not
work, replace reversing valve.
Leaking 4-way (condenser
select) valve.
4-way valve is the same temperature on
both ends of body, common suction line
is warm, compressor is running hot.
Does not work in air heat or water heat
but does work in air cool.
Replace 4-way valve.
Содержание TF-45
Страница 12: ...Page 12 001223MAN 05 1 Jul 2017 ...
Страница 13: ...1 Jul 2017 Page 13 001223MAN 05 ...
Страница 14: ...Page 14 001223MAN 05 1 Jul 2017 ...
Страница 15: ...1 Jul 2017 Page 15 001223MAN 05 ...
Страница 16: ...Page 16 001223MAN 05 1 Jul 2017 ...
Страница 19: ...1 Jul 2017 Page 19 001223MAN 05 ...
Страница 20: ...Page 20 001223MAN 05 1 Jul 2017 ...
Страница 23: ...1 Jul 2017 Page 23 001223MAN 05 ...
Страница 24: ...Page 24 001223MAN 05 1 Jul 2017 ...
Страница 25: ...1 Jul 2017 Page 25 001223MAN 05 ...
Страница 26: ...Page 26 001223MAN 05 1 Jul 2017 ...
Страница 27: ...1 Jul 2017 Page 27 001223MAN 05 ...
Страница 30: ...Page 30 001223MAN 05 1 Jul 2017 ...
Страница 31: ...1 Jul 2017 Page 31 001223MAN 05 ...
Страница 32: ...Page 32 001223MAN 05 1 Jul 2017 ...
Страница 33: ...1 Jul 2017 Page 33 001223MAN 05 ...
Страница 34: ...Page 34 001223MAN 05 1 Jul 2017 ...
Страница 38: ...Page 38 001223MAN 05 1 Jul 2017 ...
Страница 39: ...1 Jul 2017 Page 39 001223MAN 05 ...
Страница 40: ...Page 40 001223MAN 05 1 Jul 2017 ...
Страница 74: ...Page 74 001223MAN 05 1 Jul 2017 Wiring Diagram 208 230 1 60 ...
Страница 75: ...1 Jul 2017 Page 75 001223MAN 05 Electrical Box Layout 208 230 1 60 ...
Страница 76: ...Page 76 001223MAN 05 1 Jul 2017 Wiring Diagram 208 3 60 ...
Страница 77: ...1 Jul 2017 Page 77 001223MAN 05 Electrical Box Layout 208 3 60 ...
Страница 78: ...Page 78 001223MAN 05 1 Jul 2017 Wiring Diagram 460 3 60 ...
Страница 79: ...1 Jul 2017 Page 79 001223MAN 05 Electrical Box Layout 460 3 60 ...
Страница 80: ...Page 80 001223MAN 05 1 Jul 2017 Wiring Diagram 220 1 50 ...
Страница 81: ...1 Jul 2017 Page 81 001223MAN 05 Electrical Box Layout 220 1 50 ...
Страница 82: ...Page 82 001223MAN 05 1 Jul 2017 ...
Страница 83: ...1 Jul 2017 Page 83 001223MAN 05 ...
Страница 84: ...Page 84 001223MAN 05 1 Jul 2017 ...
Страница 85: ...1 Jul 2017 Page 85 001223MAN 05 Dimensions TF 45 Left Return ...
Страница 86: ...Page 86 001223MAN 05 1 Jul 2017 Dimensions TF 45 Right Return ...
Страница 87: ...1 Jul 2017 Page 87 001223MAN 05 Dimensions TF 55 65 75 80 Left Return ...
Страница 88: ...Page 88 001223MAN 05 1 Jul 2017 Dimensions TF 55 65 75 80 Right Return ...