![Maritime Geothermal TF-45 Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/maritime-geothermal/tf-45/tf-45_installation-and-service-manual_1727434029.webp)
1-Jul-2017
Page 29
001223MAN-05
TABLE 14 - Volume of fluid per 100 ft. of pipe
Volume /100ft.
Type of Pipe
Diameter
I.gal
gal
L
Copper
1”
3.4
4.1
15.5
1-1/4”
5.3
6.4
24.2
1-1/2”
7.7
9.2
34.8
Rubber Hose
1”
3.2
3.9
14.8
Polyethylene
3/4” IPS SDR11
2.3
2.8
10.6
1” IPS SDR11
3.7
4.5
17.0
1-1/4” IPS SDR11
6.7
8.0
30.3
1-1/2” IPS SDR11
9.1
10.9
41.3
2” IPS SDR11
15.0
18.0
68.1
Other Item Volumes
Heat Exchanger
Average
1.2
1.5
5.7
Purge Cart Tank See cart manual
TBD
TABLE 13 - Antifreeze Percentages
BY VOLUME
Protection to:
10°F
15°F
20°F
25°F
Methanol
25%
21%
16%
10%
Propylene Glycol
38%
30%
22%
15%
Protection to:
10°F
15°F
20°F
25°F
Methanol 16.8%
13.6%
10%
6.3%
Propylene Glycol
30%
23.5%
18.3%
12.9%
BY WEIGHT
When using alcohols, be sure to inject below the water
line to reduce initial volatility of the pure antifreeze.
If the
loop is large it may be necessary to refill the tank with antifreeze
several times to get all the antifreeze into the loop. Pump the
loop for 5 to 10 minutes longer to ensure the remaining fluid has
been well mixed.
Initial Pressurization
At this point open all valves in the flow circuit and slowly
close off the supply and return flush cart valves in a manner that
leaves about
20-30 psig
. on the system. If an air bladder
expansion tank is used it should be charged to the above
pressure before actual water pressure is put on the system .
Systems without an expansion tank will experience greater fluc-
tuations in pressure between the heating and cooling seasons,
causing pressure gauges to have different values as the loop
temperature changes. This fluctuation is normal since
expansion and contraction of the loop fluid must be handled by
the elasticity of the plastic loop.
Pressurize the loop to a static pressure of
45 psig
. when
installing a system in the fall going into the heating season.
Pressurize the loop to a static pressure of
25 psig
. when
installing a system in the spring or summer going into the
cooling season.
After operating the heat pump for a period of time, any
residual air in the system should be bled off and the static pres-
sure should be verified and adjusted if necessary. Add
additional water / antifreeze mix with the purge cart to bring the
pressure back to the original setting if required.
Pipe Insulation
All ground loop piping inside the structure (between the
structure entry point and the heat pump) should be insulated
with 3/8” thick closed cell pipe insulation to prevent condensa-
tion and dripping onto floors or walls.
Although many different antifreeze solutions have been
employed in geothermal systems, the alcohols such as
methanol or ethanol have the most desirable characteristics for
groundloop applications. The overall heat transfer
characteristics of these fluids remain high although care must be
taken when handling pure alcohols since they are extremely
flammable. Once mixed in a typical 25% by volume ratio with
water the solution is not flammable. In situations where alcohols
are not allowed as a loop fluid due to local regulations then
propylene glycol is a non-toxic alternative which can be
substituted . Propylene glycol should only be used in cases
where alcohols are not permitted since the heat transfer
characteristics are less desirable and it becomes more viscous
at low temperatures, increasing pumping power.
The volume of fluid that your loop system holds can be
closely estimated by totaling the number of ft. of each size pipe
in the system and referencing
TABLE 13
the for approximate
volume per 100 ft.
When the volume of the loop has been calculated and the
appropriate amount of antifreeze is ready for addition by
referencing
TABLE 12
, drain the equivalent amount of water
from the flush cart or mixing barrel and replace it with the
antifreeze.
Once the lines have been filled and no more air bubbles are
appearing in the line, adjust the circulator pump module valves
to circulate water through the heat pump using the same
technique as described above. When all air is removed reverse
the flow of water through the lines by interchanging the flush
cart lines and purge again. You will be able to visibly tell when
all air is removed.
Adding Antifreeze Solution
In most mid and northern areas of the US and in all of
Canada it is necessary to condition the loop fluid by the addition
of some type of antifreeze solution so that it will not freeze
during operation in the winter months. This antifreeze is required
because the loop fluid will normally reach a low entering
temperature of
28°F to 32°F (-2°C to 0°C)
and refrigerant
temperatures inside the heat pump’s heat exchanger may be as
low as
20°F (11°C)
cooler. See
TABLE 12
for details of freeze
protection provided by different concentrations.
WARNING: Add enough antifreeze to allow
for a temperature 20°F (11°C) lower than the
expected lowest loop fluid temperature
entering the heat pump. Insufficient anti-
freeze concentration could cause the heat
exchanger to freeze and rupture, voiding the
warranty.
Содержание TF-45
Страница 12: ...Page 12 001223MAN 05 1 Jul 2017 ...
Страница 13: ...1 Jul 2017 Page 13 001223MAN 05 ...
Страница 14: ...Page 14 001223MAN 05 1 Jul 2017 ...
Страница 15: ...1 Jul 2017 Page 15 001223MAN 05 ...
Страница 16: ...Page 16 001223MAN 05 1 Jul 2017 ...
Страница 19: ...1 Jul 2017 Page 19 001223MAN 05 ...
Страница 20: ...Page 20 001223MAN 05 1 Jul 2017 ...
Страница 23: ...1 Jul 2017 Page 23 001223MAN 05 ...
Страница 24: ...Page 24 001223MAN 05 1 Jul 2017 ...
Страница 25: ...1 Jul 2017 Page 25 001223MAN 05 ...
Страница 26: ...Page 26 001223MAN 05 1 Jul 2017 ...
Страница 27: ...1 Jul 2017 Page 27 001223MAN 05 ...
Страница 30: ...Page 30 001223MAN 05 1 Jul 2017 ...
Страница 31: ...1 Jul 2017 Page 31 001223MAN 05 ...
Страница 32: ...Page 32 001223MAN 05 1 Jul 2017 ...
Страница 33: ...1 Jul 2017 Page 33 001223MAN 05 ...
Страница 34: ...Page 34 001223MAN 05 1 Jul 2017 ...
Страница 38: ...Page 38 001223MAN 05 1 Jul 2017 ...
Страница 39: ...1 Jul 2017 Page 39 001223MAN 05 ...
Страница 40: ...Page 40 001223MAN 05 1 Jul 2017 ...
Страница 74: ...Page 74 001223MAN 05 1 Jul 2017 Wiring Diagram 208 230 1 60 ...
Страница 75: ...1 Jul 2017 Page 75 001223MAN 05 Electrical Box Layout 208 230 1 60 ...
Страница 76: ...Page 76 001223MAN 05 1 Jul 2017 Wiring Diagram 208 3 60 ...
Страница 77: ...1 Jul 2017 Page 77 001223MAN 05 Electrical Box Layout 208 3 60 ...
Страница 78: ...Page 78 001223MAN 05 1 Jul 2017 Wiring Diagram 460 3 60 ...
Страница 79: ...1 Jul 2017 Page 79 001223MAN 05 Electrical Box Layout 460 3 60 ...
Страница 80: ...Page 80 001223MAN 05 1 Jul 2017 Wiring Diagram 220 1 50 ...
Страница 81: ...1 Jul 2017 Page 81 001223MAN 05 Electrical Box Layout 220 1 50 ...
Страница 82: ...Page 82 001223MAN 05 1 Jul 2017 ...
Страница 83: ...1 Jul 2017 Page 83 001223MAN 05 ...
Страница 84: ...Page 84 001223MAN 05 1 Jul 2017 ...
Страница 85: ...1 Jul 2017 Page 85 001223MAN 05 Dimensions TF 45 Left Return ...
Страница 86: ...Page 86 001223MAN 05 1 Jul 2017 Dimensions TF 45 Right Return ...
Страница 87: ...1 Jul 2017 Page 87 001223MAN 05 Dimensions TF 55 65 75 80 Left Return ...
Страница 88: ...Page 88 001223MAN 05 1 Jul 2017 Dimensions TF 55 65 75 80 Right Return ...