OPERATION TROUBLESHOOTING -
COOLING MODE
Fault
Possible Cause
Verification
Recommended Action
High Discharge
Pressure
Unit is overcharged.
(Only possible if unit has
been field serviced and incor-
rectly charged.)
High subcooling, low delta T across
water coil.
Remove 1/2lb of refrigerant at a time
and verify that the discharge pressure
reduces. Or remove charge and weigh
back in the amount listed on name-
plate.
High Suction
Pressure
(may appear to
not be pumping)
TXV adjusted too far open.
Verify superheat. It should be between
8-12°F (3-6°C). Superheat will be low if
TXV is open too far.
Adjust TXV to obtain 8-12°F (3-6°
C) superheat.
TXV stuck open.
Adjusting the TXV does not affect the
superheat or the suction pressure. Low
super heat and discharge pressure.
Adjust the TXV all the way in and out a
few times to loosen it. Replace TXV if
this does not work.
Leaking reversing valve.
Reversing valve is the same tempera-
ture on both ends of body, common
suction line is warm, compressor is
running hot.
Replace reversing valve.
Faulty compressor, not
pumping.
Pressures change only slightly from
static values when compressor is start-
ed.
Replace compressor.
Low Suction
Pressure
Low airflow
See Fan Troubleshooting section.
Note:
low airflow will cause the air
coil to ice up once the suction drops
below
90PSIG
.
Correct the problem.
TXV stuck almost closed or
partially blocked by foreign
object.
Adjusting the TXV does not affect the
superheat or the suction pressure.
TXV may be frosting up.
Adjust the TXV all the way in and out a
few times to loosen it. Replace TXV if
this does not work.
Low or no refrigerant charge. Entering air temperature and airflow
are good but suction is low. Check
static refrigeration pressure of the unit
for a very low value. Weigh refrigerant
out and compare to charge listed on
nameplate.
Locate the leak and repair it.
Spray 9, a sniffer, and dye are com-
mon methods of locating a leak.
Compressor
frosting up
See Low Suction
Pressure in this section.
TXV frosting up
TXV stuck almost closed or
partially blocked by foreign
object.
Adjusting the TXV does not affect the
superheat or the suction pressure.
Adjust the TXV all the way in and out a
few times to loosen it. Replace TXV if
this does not work.
Random Low
Pressure trip
(does not occur
while there)
Faulty compressor contactor. Points pitted or burned. Contactor
sometimes sticks causing the compres-
sor to run without the fan, tripping the
low pressure control.
Replace contactor.
Intermittent fan.
See Fan Troubleshooting section.
Correct the problem.
Leaking check valve (located
in the indoor water coil “out”
refrigerant line).
Check valve is cold.
Try tapping the valve and switching
from air cool to water heat a few times.
Replace the check valve if the problem
persists.
Faulty NC solenoid valve or
coil.
Verify solenoid by removing it from the
shaft while the unit is running. There
should be an audible click sound if the
solenoid is working. Valve may be cold
if restricted.
Replace solenoid or valve if faulty.
Faulty NC solenoid valve or
coil.
Verify solenoid by removing it from the
shaft while the unit is running. There
should be an audible click sound if the
solenoid is working. Valve may be cold
if restricted.
Replace solenoid or valve if faulty.
Содержание TF-45
Страница 12: ...Page 12 001223MAN 05 1 Jul 2017 ...
Страница 13: ...1 Jul 2017 Page 13 001223MAN 05 ...
Страница 14: ...Page 14 001223MAN 05 1 Jul 2017 ...
Страница 15: ...1 Jul 2017 Page 15 001223MAN 05 ...
Страница 16: ...Page 16 001223MAN 05 1 Jul 2017 ...
Страница 19: ...1 Jul 2017 Page 19 001223MAN 05 ...
Страница 20: ...Page 20 001223MAN 05 1 Jul 2017 ...
Страница 23: ...1 Jul 2017 Page 23 001223MAN 05 ...
Страница 24: ...Page 24 001223MAN 05 1 Jul 2017 ...
Страница 25: ...1 Jul 2017 Page 25 001223MAN 05 ...
Страница 26: ...Page 26 001223MAN 05 1 Jul 2017 ...
Страница 27: ...1 Jul 2017 Page 27 001223MAN 05 ...
Страница 30: ...Page 30 001223MAN 05 1 Jul 2017 ...
Страница 31: ...1 Jul 2017 Page 31 001223MAN 05 ...
Страница 32: ...Page 32 001223MAN 05 1 Jul 2017 ...
Страница 33: ...1 Jul 2017 Page 33 001223MAN 05 ...
Страница 34: ...Page 34 001223MAN 05 1 Jul 2017 ...
Страница 38: ...Page 38 001223MAN 05 1 Jul 2017 ...
Страница 39: ...1 Jul 2017 Page 39 001223MAN 05 ...
Страница 40: ...Page 40 001223MAN 05 1 Jul 2017 ...
Страница 74: ...Page 74 001223MAN 05 1 Jul 2017 Wiring Diagram 208 230 1 60 ...
Страница 75: ...1 Jul 2017 Page 75 001223MAN 05 Electrical Box Layout 208 230 1 60 ...
Страница 76: ...Page 76 001223MAN 05 1 Jul 2017 Wiring Diagram 208 3 60 ...
Страница 77: ...1 Jul 2017 Page 77 001223MAN 05 Electrical Box Layout 208 3 60 ...
Страница 78: ...Page 78 001223MAN 05 1 Jul 2017 Wiring Diagram 460 3 60 ...
Страница 79: ...1 Jul 2017 Page 79 001223MAN 05 Electrical Box Layout 460 3 60 ...
Страница 80: ...Page 80 001223MAN 05 1 Jul 2017 Wiring Diagram 220 1 50 ...
Страница 81: ...1 Jul 2017 Page 81 001223MAN 05 Electrical Box Layout 220 1 50 ...
Страница 82: ...Page 82 001223MAN 05 1 Jul 2017 ...
Страница 83: ...1 Jul 2017 Page 83 001223MAN 05 ...
Страница 84: ...Page 84 001223MAN 05 1 Jul 2017 ...
Страница 85: ...1 Jul 2017 Page 85 001223MAN 05 Dimensions TF 45 Left Return ...
Страница 86: ...Page 86 001223MAN 05 1 Jul 2017 Dimensions TF 45 Right Return ...
Страница 87: ...1 Jul 2017 Page 87 001223MAN 05 Dimensions TF 55 65 75 80 Left Return ...
Страница 88: ...Page 88 001223MAN 05 1 Jul 2017 Dimensions TF 55 65 75 80 Right Return ...