Revision 1.6
Page 21
3.5.3.3 Manufacturer Code
This parameter allows you to configure the manufacturer code that must be reported by the
device transmitting the 127501 Binary Status Report message that will be used to control this
discrete I/O circuit. Setting this value to 2047 means that any manufacturer code will be
accepted.
3.5.3.4 Discrete I/O Function
This parameter allows you to configure how the specified 127501 Binary Status Report
indicator will control the assigned breaker. The following functions may be selected:
Discrete I/O Function
Description
Always Turn ON
Turns the breaker ON when the monitored signal becomes active
Always Turn OFF
Turns the breaker OFF when the monitored signal becomes active
Toggle ON/OFF
An inactive to active edge on the monitored signal toggles the breaker from OFF
to ON or from ON to OFF
Brighten
An inactive to active edge on the monitored signal increases the dimming
level by 1%
Dim
An inactive to active edge on the monitored signal decreases the dimming
level by 1%
Flash
An inactive to active edge on the monitored signal turns the breaker ON
and uses the assigned flash map
Turn OFF w/Lock
The breaker turns OFF and stays LOCKED as long as the monitored signal
is active. The breaker stays OFF but becomes UNLOCKED when the
monitored signal becomes inactive
Unlock
Unlocks breaker (state does not change)
One Button Smooth High-
to-Low
Single press changes breaker state. Press and hold wall switch to turn ON;
hold for High to Low voltage decrease (1% increments). Continuing to hold
will reset to 100% intensity and repeat.
One Button Smooth Low-
to-High
Single press changes breaker state. Press and hold wall switch to turn ON;
hold for Low to High dimming level increase (1% increments). Continuing to
hold will reset to 5% dimming level and repeat.
Smooth Scroll
A momentary touch turns breaker ON only; continuing to hold scrolls
dimming level UP and DOWN (last known state is retained).
One Button Smooth Scroll
A momentary touch changes breaker state; continuing to hold scrolls dimming
level UP and DOWN (last known state is retained).
Discrete Momentary
The breaker stays on as long as the monitored signal remains active. The
breaker turns OFF when the input becomes inactive.
3.5.3.5 Assigned Breakers
This parameter allows you to configure the breakers that will be controlled by this discrete I/O
channel. You may select any number of the breakers.
3.5.4 Inputs
The CLMD12 has seven digital inputs. These inputs can be configured on the Inputs tab. The
states of these input channels are transmitted in a 127501 Binary Status Report message as
indicators 13 (Input Channel #1) through 19 (Input Channel #7).