background image

 

CLMD12 User's Manual  

 

 

 

 

Page 

6

 

 

 

Revision 1.6 

 

 
 

2.6  Load protection current limit 

The configurable load protection current limit provides three parameters to customize the 
overcurrent protection of the load.  

  Current rating: Constant load current above this level will trip the breaker OFF.  

  Inrush Delay: An adjustable delay (0 to 1500 milliseconds) that starts at the time of 

breaker turn ON. The configurable current limit trip is blocked during this period. 

  Trip Delay: An adjustable delay (0 to 750 milliseconds) that starts when currents 

exceeding the current rating setting are detected after the Inrush Delay has expired. 
The configurable current limit trip is blocked during this period. 

2.7  Pulse Width Modulation (PWM) 

Breakers can be operated in pulse width modulation (PWM) mode, also referred to as 
dimming, to control the brightness of incandescent or LED lighting. The breaker may be 
configured with a duty cycle of 5% to 100% with a resolution of 1%. 
 

 

WARNING 

  The breaker being used as a dimming module will provide an active high 

output at full battery voltage to the LED control module. Verify that the 
LED control module can accept this type of input prior to use. When a 
breaker is configured to provide a PWM output (dimming), the PWM 
frequency is 200Hz, and the output current of the breaker is limited to 
3.0A. Use of a breaker in a PWM mode (duty cycle less than 100%) for 
control of motors or other inductive loads is prohibited. 

 

0

20

40

60

80

100

120

140

160

180

0

0.015

0.03

0.045

0.06

0.075

0.09

0.105

0.12

0.135

0.15

0.165

0.18

0.195

0.21

0.225

0.24

0.255

0.27

0.285

0.3

0.315

0.33

0.34

5

0.36

0.375

0.39

Curr

en

(ampere

)

Time (sec)

Channel current in Amperes VS time to non-configurable 

overcurrent shutdown in Seconds for a steady current.

10A channel

5A channel

12A channel

Содержание MPOWER CLMD12

Страница 1: ...ion 1 6 Page i CLMD12 12 Channel DC Load Controller Module User s Manual Revision 1 6 Copyright 2021 Carling Technologies Inc 60 Johnson Ave Plainville CT 06062 USA All Rights Reserved http www maretron com ...

Страница 2: ...tion 1 0 Internal Review 1 1 Second Review 1 2 Initial Release 1 3 Updated Accessory Part Numbers 1 4 Removed requirement for parallel resistors for LED loads 1 5 Added ability to parallel breakers together for increased current 1 6 Added Product Image Update table of contents ...

Страница 3: ...g the Box 8 3 2 Choosing a Mounting Location 8 3 3 Mounting the CLMD12 8 3 4 Connecting the CLMD12 8 3 4 1 NMEA 2000 Connection 9 3 4 2 Breaker Connections 10 3 4 3 Discrete Input Connections 10 3 4 4 DC Power Connection 11 3 4 5 Checking Connections 11 3 5 Configuring the CLMD12 11 3 5 1 General Tab 11 3 5 1 1 Label 14 3 5 1 2 Instance 14 3 5 1 3 Input Voltage 15 3 5 1 4 Not Configured 15 3 5 1 5...

Страница 4: ...Control by Flash Function 28 4 3 Automatic Breaker Control by Discrete I O Function 28 4 4 Manual Bypass 29 5 Maintenance 30 6 Troubleshooting 31 7 Technical Specifications 33 8 Mechanical Drawing 35 9 Technical Support 36 10 Installation Template 37 11 Maretron 2 Year Limited Warranty 38 Table of Figures Figure 1 Output Channel Schematic 5 Figure 2 Discrete Input Impedance Model 8 Figure 3 CLMD12...

Страница 5: ...Revision 1 6 Page v Table of Appendices Appendix A NMEA 2000 Interfacing A1 ...

Страница 6: ......

Страница 7: ...to 5 10 or 12 Amps with a total current capacity of 75 Amps In addition to fast switching low loss solid state ON OFF switches it provides accurate current measurement for each load along with short circuit protection The CLMD12 additionally contains 7 input channels implemented by DC digital inputs programmable to sense whether the input is connected to a high level connected to a low level or le...

Страница 8: ...Network Each breaker Capable of Carrying Up to 5 10 or 12 Amps Individual Breaker Electrical Current Monitoring Breakers can have power up states defined ON OFF or Previous states Breakers can be locked against inadvertent actuation Seven 7 discrete inputs configurable as Active High Active Low Automatic ECB Overcurrent Shutdown Automatic ECB Thermal Shutdown Overtemperature Protection 2 3 Accesso...

Страница 9: ...x Section 3 1 2 Choose a mounting location Section 3 2 3 Mount the CLMD12 Section 3 3 4 Connect the CLMD12 Section 3 4 5 Configure the CLMD12 Section 3 5 2 5 Theory of Operation The CLMD12 provides the ability to turn on or off DC power to a load circuit using 12 independent solid state Electronic Circuit Breakers ECB s Each breaker contains protection against overcurrent overtemperature and short...

Страница 10: ...to the open OFF state The state that the breaker will be in when the NMEA 2000 power is restored can be configured to be ON OFF or in the last state the breaker was in before power was removed 2 5 1 Electronic Circuit Breakers The 12 high side output channels are switched with MOSFETs connected in a back to back arrangement so that back feeding is not possible when the breaker is turned off All ou...

Страница 11: ...2000 interface 2 5 1 2 Output control circuit protection current limit The non configurable output control circuit protection allows surge currents to occur without tripping the overcurrent shutdown function These surges are allowed any time the breaker is ON according to a single time constant characteristic Over current levels are allowed for a time that is inversely proportional to the magnitud...

Страница 12: ...ed to as dimming to control the brightness of incandescent or LED lighting The breaker may be configured with a duty cycle of 5 to 100 with a resolution of 1 WARNING The breaker being used as a dimming module will provide an active high output at full battery voltage to the LED control module Verify that the LED control module can accept this type of input prior to use When a breaker is configured...

Страница 13: ...8A Breaker 2 10A Breaker 10 10A 18A Breaker 1 10A Breaker 10 10A 18A You can parallel two breakers by assigning the same switch group number to the two breakers When you parallel breakers configure the CLMD12 to assign 50 of the maximum current to the Current Rating parameter for each of the two paralleled breakers For example if you parallel Breaker 7 and Breaker 4 and wish to use them to supply ...

Страница 14: ...cation Please consider the following when choosing a mounting location 1 The CLMD12 is waterproof so it can be mounted in a damp or dry location 2 The orientation is not important so the CLMD12 can be mounted on a horizontal deck vertical bulkhead or upside down if desired 3 The CLMD12 is temperature rated to 85 C 185 F so it should be mounted away from engines or engine rooms where the operating ...

Страница 15: ... see Figure 4 You connect the CLMD12 to an NMEA 2000 network using a Maretron NMEA 2000 cable or compatible cable by connecting the female end of the cable to the CLMD12 note the key on the male connector and keyway on the female connector Be sure the cable is connected securely and that the collar on the cable connector is tightened firmly Connect the other end of the cable male to the NMEA 2000 ...

Страница 16: ...nection may switch between open circuit and system ground or the supply voltage J2 Connector Pin No Description NMEA 2000 PGN 127501 Indicator Number 1 Discrete Input 3 active high open active low 15 2 Discrete Input 1 active high open active low 13 3 Discrete Input 7 active high open active low 19 4 Discrete Input 5 active high open active low 17 5 Discrete Input 6 active high open active low 18 ...

Страница 17: ...ing Connections Once all of the connections to the CLMD12 have been completed check to see that information is being properly transmitted by observing an appropriate NMEA 2000 display If you don t see channel on off status refer to Section 6 Troubleshooting 3 5 Configuring the CLMD12 The CLMD12 will transmit data over the NMEA 2000 network as it is shipped from the factory however it may require c...

Страница 18: ...CLMD12 User s Manual Page 12 Revision 1 6 ...

Страница 19: ...Revision 1 6 Page 13 ...

Страница 20: ...ducts and allows you to easily identify the particular device 3 5 1 2 Instance NMEA 2000 provides a unique instance number for each breaker box on a vessel This read only field shows the instance number assigned to this device This instance number value is reflected in the 127501 Binary Status Report message The instance number can be configured by changing the Device Instance field on the Advance...

Страница 21: ...s you to configure a text label for the breaker to identify it for example RUNNING LIGHTS or HATCH For each breaker set this to a value which describes the breaker so that you can easily identify it in display devices 3 5 1 6 2 State This read only field indicates the current state of the breaker It will contain one of the following values OFF ON 3 5 1 6 3 Default State This allows you to configur...

Страница 22: ... 11 Dimming Allowed This parameter allows you to configure whether the channel is dimmable Check this box to allow dimming commands to change the dimming level of the breaker and clear this box to force the breaker to operate at 100 dimming level 3 5 1 6 12 Combine With To parallel two breakers select the number of the breaker you wish to combine this breaker with The dropdown box will present a l...

Страница 23: ...h commands on the network The purpose of the lock feature is to avoid inadvertent or accidental breaker state changes The breaker must be unlocked before the breaker state can be remotely changed again 3 5 1 6 19 3 Breaker Tripped When lit this read only field indicates that the breaker has tripped due to an overcurrent condition Switch the breaker OFF to acknowledge the breaker tripped indication...

Страница 24: ... after a set period of time etc Three parameters dictate the behavior of the circuit and are detailed below A maximum of 15 flash table entries may be defined Figure 6 CLMD12 Flash Map Tab 3 5 2 1 Cycles This parameter allows you to configure the number of cycles that this flash map will execute after a breaker configured to use this flash map has been switched to the ON state A value of ...

Страница 25: ...ll disable this flash map 3 5 3 Discrete I O When a device transmitting the 127501 Binary Status Report message is part of the installation it can be configured to control the behavior of the breakers This includes the seven input channels present on the CLMD12 Up to thirty six Discrete I O s can be programmed One Discrete I O can control multiple breakers up to the box limit The Discrete I O stat...

Страница 26: ... O circuit To assign a discrete input from this device to this discrete I O circuit enter the instance value assign to this device the value of the Instance field on the General tab 3 5 3 2 Indicator This parameter allows you to configure the indicator number within the 127501 Binary Status Report status message whose instance field matches the Data Instance parameter for this channel that will be...

Страница 27: ... active The breaker stays OFF but becomes UNLOCKED when the monitored signal becomes inactive Unlock Unlocks breaker state does not change One Button Smooth High to Low Single press changes breaker state Press and hold wall switch to turn ON hold for High to Low voltage decrease 1 increments Continuing to hold will reset to 100 intensity and repeat One Button Smooth Low to High Single press change...

Страница 28: ...rs here can be changed by setting the Device Instance parameter on the Advanced tab 3 5 4 2 Channel 3 5 4 3 Label Each channel has a text label you can set to identify the input signal monitored by that channel for example BILGE PUMP or HATCH For each channel set this to a value which describes the input being monitored so that you can easily identify it in display devices ...

Страница 29: ...n the network Low a low voltage level on the input is represented as an ON value on the network A high impedance or a high voltage level on the input is represented as an OFF value on the network Both a high voltage level or a low voltage level on the input is represented as an ON value on the network A high impedance on the input is represented as an OFF value on the network 3 5 4 3 2 State This ...

Страница 30: ...tted by the device and can be seen on the General Tab as well as the Inputs Tab labeled as Instance 3 5 5 2 Transmit PGN 127501 This parameter allows you to configure whether the device transmits the 127501 Binary Status Report NMEA 2000 message If this field is set the device will transmit the 127501 Binary Status Report message along with proprietary messages If this field is cleared the device ...

Страница 31: ...is parameter allows you to configure when the CLMD12 sends the extended box status proprietary message There are two settings for this parameter Only send when an error is detected Only send upon request 3 5 5 6 127501 via 126208 Receive Filter This parameter allows you to configure from which devices the CLMD12 will accept 126208 NMEA Commands of the 127501 Binary Status Report message There are ...

Страница 32: ...n description fields You may program these fields with information specific to the device such as date installed the initials name of the installer the physical location of the device etc This configuration option will allow you to program the values of these fields 3 5 7 Control This tab allows you to control the ON OFF state and dimming level of the breakers on the device This is normally used f...

Страница 33: ...the breaker is in the OFF state 3 5 7 2 ON OFF Buttons The ON button allows you to switch the breaker into the ON state The OFF button allows you to switch the breaker into the OFF state 3 5 7 3 Dimmer Slider The blue slider bar allows you the configure the dimming level of a breaker between 5 and 100 The read only green bar graph shows the real time dimming level of the breaker ...

Страница 34: ...controlled from multiple input signals DIO s an out of state situation is possible when input signals are switched Example two wall switches are controlling the same light breaker depending on the state of the signal a second touch of the switch may be required to obtain the desired action Discrete I O Function Description Always Turn ON Turns the breaker ON when the monitored signal becomes activ...

Страница 35: ...e current rating of the fuse for each load is appropriate to protect the load and the wiring for that load Please note that the bypass module does not support paralleled outputs since each circuit is controlled by a separate switch Additionally the bypass module does not support dimming of circuits WARNING The CBMD12 Mechanical Bypass Module is not ignition protected Ensure that the area is free o...

Страница 36: ...er remote control Before servicing any load device connected to the CLMD12 you must first disconnect the wire between the CLMD12 load terminal and the load device Failure to do so can result in serious bodily harm Regular maintenance is important to ensure continued proper operation of the Maretron CLMD12 Perform the following tasks periodically ...

Страница 37: ...y connected to the NMEA 2000 network Ensure that the CLMD12 instance of the breaker switch component matches the instance programmed into the CLMD12 as described in Section 3 5 5 1 A breaker switch always reads Error The CLMD12 may have shut down the affected channel due to an overtemperature or overcurrent condition detected on the CLMD12 breaker itself Ensure that the current drawn by the load i...

Страница 38: ...trol the state of a breaker switch If you are controlling the load via a DSM Series display ensure that it is running at least firmware revision 1 4 10 If you are controlling the load via N2KView software ensure that you have a switch control license for the software ...

Страница 39: ...al Craft Directive 2014 35 EU NMEA 2000 Parameter Group Numbers PGNs Description PGN PGN Name Default Rate Periodic Data PGNs 65300 Carling Proprietary 1 time 4 seconds 127500 Load Controller Connection State Control 1 time 4 seconds and on switch change 127501 Binary Status Report 1 time 15 seconds and on switch change 127751 DC Voltage Current 1 time 1 5 seconds and on switch change Response to ...

Страница 40: ...nnels Absolute Voltage Limits 2 3 36 VDC Input Resistance 1KΩ Input Voltage Open Circuit 2 75 V Low Voltage Threshold 0 to 1 02 V Open Voltage Threshold 1 51 4 31 V High Voltage Threshold 4 82 32 0 V Mechanical Parameter Value Comment Size 5 7 x 5 x 1 6 144 8mm x 127mm x 40 6mm Including Flanges for Mounting Weight 1 32 lb 0 599 kg Power Stud Torque Value 20 in lbs 2 26 N m Environmental Parameter...

Страница 41: ...ical Resistance EN 60068 2 74 2000 Test method B Salt Spray EN 60068 2 52 1996 Chamber Temperature 35 C Ozone ASTM D1171 99 Method A rating 0 Electrical Operating Voltage SAE J1455 2011 Sect 4 13 1 Test for impaired function Electrical Over Voltage SAE J1455 2011 Sect 4 13 1 Test for impaired function 24V 36V Electrical Reverse Polarity SAE J1455 2011 Sect 4 13 1 Test for impaired function 24V 36V...

Страница 42: ...port for Maretron products you can reach us in any of the following ways Telephone 1 866 550 9100 Fax 1 602 861 1777 E mail support maretron com World Wide Web http www maretron com Mail Carling Technologies Inc Attn Maretron Technical Support 120 Intracoastal Pointe Dr Jupiter FL 33477 USA ...

Страница 43: ...stallation Template Please check the dimensions before using the following diagram as a template for drilling the mounting holes because the printing process may have distorted the dimensions Figure 13 Mounting Surface Template ...

Страница 44: ...OF ANTICIPATED PROFITS OR SAVINGS OR ANY OTHER LOSS INCURRED BECAUSE OF INTERRUPTION OF SERVICE IN NO EVENT SHALL CARLING S AGGREGATE LIABILITY EXCEED THE PURCHASE PRICE OF THE PRODUCT S INVOLVED CARLING SHALL NOT BE SUBJECT TO ANY OTHER OBLIGATIONS OR LIABILITIES WHETHER ARISING OUT OF BREACH OF CONTRACT OR WARRANTY TORT INCLUDING NEGLIGENCE OR OTHER THEORIES OF LAW WITH RESPECT TO PRODUCTS SOLD ...

Страница 45: ...er 1 through 11 Breaker 12 3 State This field indicates the state of the solid state breaker 4 Status This field indicates the status of the solid state breaker 5 Operational Status Control This field is used to lock and unlock the solid state breaker 6 PWM Duty Cycle This field is used to control and report the PWM duty cycle of the solid state breaker 7 TimeON This field is used to report the ON...

Страница 46: ...0 12 Indicator 11 This field indicates the state of the solid state breaker on output channel 11 13 Indicator 12 This field indicates the state of the solid state breaker on output channel 12 14 Indicator 13 This field indicates the state sensed by the digital input on input channel 1 The state will be one of the following values OFF The digital input voltage level is outside the range s programme...

Отзывы: