Mareli Systems

If the facility does not operate satisfactorily:

• 

Check the quality of pellets (must be free from dust). Upon normal operation of the burner, the quantity 

of the pellets on the grate (combustion basin) must be such so that its holes are covered.

• 

Check the exhaust temperature (175- 240°C).

• 

If the temperature is very high, decrease the pellets fed. If the temperature is very low, increase the 

amount of input air.

It is important to replace faulty parts immediately!!!

Always keep in stock additional photo sensor and heater for replacement.
The criterion for good operation of the burner is the colour of the flame - IT MUST BE YELLOW. When it is 

dark red, mixed with smoke it is most likely that the volume of input air is less than required for good com-

bustion and must be increased.

Adjustment of the air affects essentially the combustion mode, the aim must be a calm, stable combustion, 

without residue.

Sometimes, if the initial loading dose for ignition is large (Parameter 02), “choking” of the burner may occur, 

i.e. it may not ignite and upon re-activation of the ignition (second attempt) the basin may clog up with pel-

lets. The volume of the first dose must be decreased so as to avoid choking.
NOTE: It is desirable when adjusting the burner settings to use exhaust gas analyser.

IMPORTANT:

Default values of the parameters should not be taken for granted. The settings must be adjusted individually 

according to REQUIRED POWER, TILT OF THE SCREW CONVEYOR, QUALITY OF PELLETS, CHIM-

NEY DRAUGHT, CUSTOMER REQUIREMENTS!

Switching off the burner and the boiler

Switching off the automated pellet burner should be done according to the guidelines in its manual. After 

cooling of the boiler, the burner also should be switched off. It is also recommended that the facility is cleaned 

from the accumulated ash.

An emergency stop of burner and boiler

During operation of the automated pellet burner an emergency situation may arise. Some situations of this 

kind are recorded by the burner controller and a procedure for their prevention is automatically performed. 

The monitoring controller also indicates the burner status.  In the event of an accident check the reason for its 

occurrence and take appropriate measures for its removal.

ATTENTION

: In the event of emergency situation - overheating the boiler, the additionally mounted manda-

tory emergency thermostat is activated. Determine the cause of this accident and take appropriate measures 

for its removal. This thermostat must be manually switched by unscrewing and removing the protective cap 

and pressing its button until it switches, then replace back the protective cap. Also, the burner needs to be 

restarted by switching it off and on.

Содержание SMB 35

Страница 1: ...SMB 35 Pellet burner Assembly and exploitation manual Mareli Systems...

Страница 2: ...y an adult who is familiar with the operating conditions Introduction of inflammable liquids in room with a working burner is strictly prohibited Children should not be left unattended in the room whe...

Страница 3: ...lied to the flexible tube The flexible tube is made of special heat resistant material which in the case of combustion does not emit toxic substances and connects the auger and pellet burner End view...

Страница 4: ...ach a pellet burner to the door through M8 screws which are screwed where the thread is made on the door itself which holds the burner to the door Explanation It must be checked whether sealing ropes...

Страница 5: ...about 3 hours for the chimney to be warmed up and measure the draught Install addition al chimney fan controlled by the control unit of the burner if necessary The heat exchange surface is made of hi...

Страница 6: ...omical and efficient operation of the boiler burner system in the installation Why is regular maintenance important Heating systems should be maintained on a regular basis for the following reasons To...

Страница 7: ...aintenance The use of special protec tive equipment safety goggles tightly fitted is recommended CAUTION Periodic cleaning as well as supervision of the burner will prevent any incidents caused by fau...

Страница 8: ...from the burner and collect the pellets passed from the conveyor into a bag for 10 min Weigh the pellets passed and multiply by the factor 0 03 The calculated value is the power in KW h Example If th...

Страница 9: ...ner settings to use exhaust gas analyser IMPORTANT Default values of the parameters should not be taken for granted The settings must be adjusted individually according to REQUIRED POWER TILT OF THE S...

Страница 10: ...user you may only make repairs which involve just a simple replacement of the grate In case of first commissioning of the boiler condensation of water vapour on the heating surfaces of the heat excha...

Страница 11: ...stat open flame return from the brazier Er07 Encoder Error The error may occur due to lack signal from Encoder Er08 Encoder Error The error can occur due to problems of adjustment of the number of rev...

Страница 12: ...ond case the user selects the desired power On the left side of the display are signalled the combustion modality A automatic combustion M manual combustion and the working power of the system Recipe...

Страница 13: ...day at the desired time Ex 6 30 The system turns on at 20 30 on Tuesday and turns off at 6 30 on Wednesday Weekly The programs are the same for all days of the week Week end Choose between Monday Fri...

Страница 14: ...14 Mareli Systems WIRING DIAGRAM...

Страница 15: ...15 Mareli Systems...

Страница 16: ...hey are due to printing or transcription errors We reserve the right to make any change that appears to be necessary or useful without harm the essential characteristics Mareli Systems MareliSystems I...

Отзывы: