Mareli Systems

Ensuring the temperature of return water

For normal operation, the return water temperature should not drop below 55ºC. Therefore a thermostatic 

mixer to raise the temperature of return water must be mounted to the reverse heating pipe.

Establishing operating pressure

To start you need to establish normal operating pressure

Instruction!!! Installation damages due to pressure in the material as a consequence of temperature differences.

• 

Fill the heating installation in cold condition only (the maximum incoming temperature can be 40º С).

• 

Set the red arrow to gauge the correct pressure of at least 1 bar overpressure (valid for closed systems). 

In open systems the maximum water level in expansion tank is 25 m above the bottom of the boiler.

• 

Add and relief water in the heating network through the loading and unloading valve until the desired 

working pressure is reached.

• 

During the filling process make sure the heating installation is air tightened.

Adjustment of the reducing valve of the exhaust gas pipe

The reduction valve of the exhaust gas pipe must be adjusted according to the exhaust gas installation and the 

fuel type. In open position (the lever is horizontal to the exhaust gas pipe) a higher temperature of the exhaust 

gases can occurs, but with lower energy conversion efficiency. Inform and explain the adjustment to the user 

of the unit.

Servicing the heating installation (for user)
Attention!!! Hazard to life in case of non-observation of the safety prescriptions

Functions of Individual Elements

Strong fanning can lead to flame extinguishing due to excessive production of gaseous products of combus-

tion. In this case you should readjust air supply.

Boiler Cleaning

Empty the ash drawer before it fills up so that there is air supply from beneath.
Attention!!! Fire risk due to hot ashes.

• 

 If the ashes are still hot wear protective gloves.

• 

 Empty the ashes in non-flammable pot with lid

Boiler cleaning

Soot and ash deposits on the walls of the hot gas ducts reduce heat transfer. Formation deposits of tar and 

condensation depend on the fuel used. We recommend at least one cleaning per week in cold state.
Instruction!!! Inefficient operation

• 

Due to insufficient cleaning the fuel consumption may increase which may lead to environmental pollu-

tion. Clean the heating boiler at least once a week.

• 

Clean the walls of the combustion chamber carefully in order to avoid damage to the fire-clay bricks.

• 

Open the doors and the manhole behind

• 

Clean the walls of the heating surfaces, of the burning chamber and of the pipes with a cleaning spade.

• 

Clean the grids with an ash knife.

• 

Gather the removed soot and ash in the ash drawer.

• 

We recommend yearly boiler inspection by a company specialized in heating systems.  

• 

Check up on the technical data of the installation, for example exhaust fumes temperature.

Boiler Decommissioning

In order to decommission the boiler, let the fire in the boiler to go out completely. Acceleration of the process 

is not recommended.

Содержание CBM 45

Страница 1: ...Pellet Water Boiler CBM 45 Assembly and exploitation manual Mareli Systems...

Страница 2: ...ion and exploitation manual of the pellet bunker if the device is provided with one The non fulfillment of prescriptions and violation of active regulations and directives may lead to damage and unexp...

Страница 3: ...ed service technician to establish whether the equipment is safe There is a risk of thermostat damage and melting the flexible pellet feeding tube To prevent backfire it should be checked if the burne...

Страница 4: ...oiler needs to be well levelled thus ensuring its proper venting Attention Fire risk due to flammable materials and liquids Make sure no flammable materials and or liquids are in the vicinity of the h...

Страница 5: ...pressure of the water must be equal to 2 bar the maximum to 6 0 bar There must be an available capacity of at least 11 l min Connect the safety heat exchanger according to the hydraulic chart with a...

Страница 6: ...installation for user Attention Hazard to life in case of non observation of the safety prescriptions Functions of Individual Elements Strong fanning can lead to flame extinguishing due to excessive...

Страница 7: ...a temperature of around 90 is reached Remove the tar from the floor and the heating surfaces by the cleaning spade Boiler Inspection and Maintenance Why is regular maintenance important These are the...

Страница 8: ...an be monitored on the display Warranty The manufacturer guarantees correct and reliable operation of the product only when requirements for in stallation and operation are met according to the manual...

Страница 9: ...tat open flame return from the brazier Er07 Encoder Error The error may occur due to lack signal from Encoder Er08 Encoder Error The error can occur due to problems of adjustment of the number of revo...

Страница 10: ...ond case the user selects the desired power On the left side of the display are signalled the combustion modality A automatic combustion M manual combustion and the working power of the system Recipe...

Страница 11: ...day at the desired time Ex 6 30 The system turns on at 20 30 on Tuesday and turns off at 6 30 on Wednesday Weekly The programs are the same for all days of the week Week end Choose between Monday Fri...

Страница 12: ...12 Mareli Systems WIRING DIAGRAM SMB 50...

Страница 13: ...13 Mareli Systems WIRING DIAGRAM PB 40 52...

Страница 14: ...14 Mareli Systems NOTES...

Страница 15: ......

Страница 16: ...hey are due to printing or transcription errors We reserve the right to make any change that appears to be necessary or useful without harm the essential characteristics MareliSystems IndustrialZone S...

Отзывы: