66
Part Number: 040006847 12/19
Procedure
Connect a temperature probe on the compressor discharge
line.
Observe the discharge line temperature and record the
maximum reading.
DISCHARGE LINE TEMPERATURE ABOVE 71 °C AT END
OF FREEZE CYCLE:
Ice machines that are operating normally will have
consistent maximum discharge line temperatures above
71 °C (155°F).
DISCHARGE LINE TEMPERATURE BELOW 71 °C (155°F)
AT END OF FREEZE CYCLE:
Ice machines that have a flooding expansion valve will have
a maximum discharge line temperature that decreases
each cycle.
Verify the expansion valve sensing bulb is 100% insulated
and sealed airtight. Condenser air contacting an incorrectly
insulated sensing bulb will cause overfeeding of the
expansion valve.
Verify the expansion valve sensing bulb is positioned and
secured correctly.
Содержание UG Series
Страница 1: ...Part Number 040006847 12 19 UnderCounter Ice Machines UG Series Technician s Handbook ...
Страница 2: ......
Страница 12: ...PAGE INTENTIONALLY LEFT BLANK ...
Страница 19: ...Part Number 040006847 12 19 19 Model Serial Number Location Model Serial Number Location ...
Страница 30: ...PAGE INTENTIONALLY LEFT BLANK 30 Part Number 040006847 12 19 ...
Страница 80: ...PAGE INTENTIONALLY LEFT BLANK 80 Part Number 040006847 12 19 ...
Страница 92: ...PAGE INTENTIONALLY LEFT BLANK 92 Part Number 040006847 12 19 ...
Страница 108: ...108 Part Number 040006847 12 19 PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ......
Страница 126: ......
Страница 127: ......