MILD SYSTEM CONTAMINATION CLEANUP
PROCEDURE
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE: If the contamination is from moisture, use heat
lamps during evacuation. Position them at the compressor,
condenser and evaporator prior to evacuation. Do not
position heat lamps too close to plastic components, or
they may melt or warp.
4. Follow the normal evacuation procedure, except
replace the evacuation step with the following:
A. Pull vacuum to 1000 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig.
B. Pull vacuum to 500 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig.
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum
pump for 1/2 hour on self-contained models, 1
hour on remotes.
NOTE: You may perform a pressure test as a preliminary
leak check. You should use an electronic leak detector after
system charging to be sure there are no leaks.
5. Charge the system with the proper refrigerant to the
nameplate amount.
6. Operate the ice machine.
Содержание UG Series
Страница 1: ...Part Number 040006847 12 19 UnderCounter Ice Machines UG Series Technician s Handbook ...
Страница 2: ......
Страница 12: ...PAGE INTENTIONALLY LEFT BLANK ...
Страница 19: ...Part Number 040006847 12 19 19 Model Serial Number Location Model Serial Number Location ...
Страница 30: ...PAGE INTENTIONALLY LEFT BLANK 30 Part Number 040006847 12 19 ...
Страница 80: ...PAGE INTENTIONALLY LEFT BLANK 80 Part Number 040006847 12 19 ...
Страница 92: ...PAGE INTENTIONALLY LEFT BLANK 92 Part Number 040006847 12 19 ...
Страница 108: ...108 Part Number 040006847 12 19 PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ......
Страница 126: ......
Страница 127: ......