Part Number 80-1479-3 7/10
167
LOW PRESSURE CUTOUT (LPCO) CONTROL
(S3300 Only)
FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint..
CHECK PROCEDURE
1. Connect manifold gauges at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Isolate LPCO electrical leads, connect a
multimeter and read resistance.
Open = Replace Switch
Closed = Switch OK
Specifications
Cut-Out
Cut-In
12 psig ±3
35 psig ±3
Содержание S300
Страница 2: ......
Страница 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Страница 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Страница 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Страница 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Страница 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Страница 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Страница 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Страница 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Страница 298: ...298 Part Number 80 1479 3 7 10 ...
Страница 299: ......