Part Number 80-1479-3 7/10
157
PTCR Operation Check
1. Visually inspect the PTCR. Check for signs of
physical damage.
NOTE:
The PTCR case temperature may reach
210°F (100°C) while the compressor is running. This is
normal. Do not change a PTCR just because it is hot.
2. Wait at least 10 minutes for the PTCR to cool to
room temperature.
3. Remove the PTCR from the ice machine.
4. Measure the resistance of the PTCR as shown.
The resistance reading must be between:
• S600/S850/S1000 =18 to 40 ohms
• S1200/S1400/S1600/S1800 =
8 to 22 ohms.
S1200/S1400/S1600/S1800
S600/S850/S1000
Содержание S300
Страница 2: ......
Страница 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Страница 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Страница 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Страница 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Страница 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Страница 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Страница 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Страница 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Страница 298: ...298 Part Number 80 1479 3 7 10 ...
Страница 299: ......