Part Number 80-1479-3 7/10
155
Relay
The relay has a set of contacts that connect and
disconnect the start capacitor from the compressor
start winding. The contacts on the relay are normally
closed (start capacitor in series with the start winding).
The relay senses the voltage generated by the start
winding and opens the contacts as the compressor
motor starts. The contacts remain open until the
compressor is de-energized.
RELAY OPERATION CHECK
1. Disconnect wires from relay terminals.
2. Verify the contacts are closed.
Measure the resistance between terminals 1 and
2. No continuity indicates open contacts. Replace
the relay.
3. Check the relay coil.
Measure the resistance between terminals 2 and
5. No resistance indicates an open coil. Replace
the relay.
Содержание S300
Страница 2: ......
Страница 20: ...20 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number 80 1479 3 7 10 A B C D E ...
Страница 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G ...
Страница 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I ...
Страница 79: ...Part Number 80 1479 3 7 10 79 This Page Intentionally Left Blank ...
Страница 80: ...80 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 133: ...Part Number 80 1479 3 7 10 133 This Page Intentionally Left Blank ...
Страница 134: ...134 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 175: ...Part Number 80 1479 3 7 10 175 REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL ...
Страница 189: ...Part Number 80 1479 3 7 10 189 This Page Intentionally Left Blank ...
Страница 190: ...190 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 296: ...296 Part Number 80 1479 3 7 10 This Page Intentionally Left Blank ...
Страница 297: ...Part Number 80 1479 3 7 10 297 This Page Intentionally Left Blank ...
Страница 298: ...298 Part Number 80 1479 3 7 10 ...
Страница 299: ......