Section 5
Customer Support
Part Number 000007282 4/10
25
Problem
Possible Cause
To Correct
Low ice capacity.
Water inlet valve filter screen is dirty.
Remove the water inlet valve and clean
the filter screen.
Incoming water supply is shut off.
Open the water service valve.
(RN1000/RN1400 Only) Water inlet valve
stuck open or leaking.
Place toggle switch in OFF position, if
water continues to enter water trough
replace the water inlet valve.
The condenser is dirty.
Clean the condenser. (See Section 4)
(RN0400 Only) Float valve will not close.
Depress float to attempt to clear debris
from valve seat. Call for service if valve
will not close.
High air temperature entering condenser.
Air temperature must not exceed 120°F
(48.9°C) for QuietQube Condensing Unit
or 110°F (43.3°C) for Self-Contained Air-
Cooled.