142
Part Number 80-01111-9 7/10
5. Install thermometer thermocouples on Suction
and Discharge line:
• Digital thermometers with remote
thermocouples must be used to obtain
temperatures
• Suction and Discharge line thermocouples
must be within 3" (76.2 mm) of the compressor
• Thermocouples must be insulated
• Doors and all panels must be in place
• Initial freeze cycle is not used for diagnostics.
Start monitoring temperatures 3 minutes into
the second freeze cycle.
6. Compare Suction and Discharge temperatures to
“QM45 Operating Temperatures” on page 207.
The charts list
Normal
suction and discharge
temperatures.
Analysis
Discharge
Line Temp
Suction
Line
Temp
Ice Fill
Pattern
Refer to
Diagnostics
for:
Normal
Normal
Less fill on the
left side of the
evaporator
This is normal
operation
Low (20°F
[-7°C] or
more)
Low
(20°F
[-7°C] or
more)
Less fill on the
left side of the
evaporator
Expansion
Valve
Flooding
Normal or
High
High
(10°F
[-12°C] or
more)
Less fill on the
left side and
top 2 rows of
the
evaporator
Low on
Refrigerant/
Expansion
Valve Starving
Normal
Low (5°F
[-15°C] or
less)
Less fill on the
left side of the
evaporator
Refrigerant
Overcharge
Содержание Q210 series
Страница 2: ......
Страница 16: ...16 Part Number 80 01111 9 7 10 SM50 MODEL SERIAL NUMBER PLATE ...
Страница 36: ...36 Part Number 80 01111 9 7 10 This Page Intentionally Left Blank ...
Страница 98: ...98 Part Number 80 01111 9 7 10 This Page Intentionally Left Blank ...
Страница 195: ...Part Number 80 01111 9 7 10 195 Using Pinch Off Tool SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING ...
Страница 202: ...202 Part Number 80 01111 9 7 10 This Page Intentionally Left Blank ...
Страница 234: ...234 Part Number 80 01111 9 7 10 This Page Intentionally Left Blank ...
Страница 235: ......