Part Number Preliminary 6/11
251
FAN CYCLE CONTROL
FUNCTION
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and
opens on a decrease in discharge pressure.
SPECIFICATIONS
CHECK PROCEDURE
1. Verify fan motor windings are not open or
grounded, and fan spins freely.
2. Connect manifold gauges to ice machine.
3. Hook voltmeter in parallel across the fan cycle
control, leaving wires attached.
4. Refer to chart below.
Specifications
Model
Cut-In (Close)
Cut-Out
(Open)
I0300 / I0320 I0520 /
I0450 / I0500 / I0600
I0850
ICVD0695
ICVD0895
ICVD1095
ICVD1195
ICVD1295
ICVD1495
ICVD1895
ICVD2095
ICVD3095
250 ±5
(1723 kPa ±.34)
(17.23 bar ±.34)
200 ±5
(1517 kPa ±.34)
(15.17 bar ±.34)
I1000
I1400 / I1800
ICVD3095
275 psig ±5
(1896 kPa ±34)
(18.96 bar±.34)
225 psig ±5
(1551 kPa ±34)
(15.51 bar ±.34)
FCC Setpoint:
Reading Should
Be:
Fan
Should Be:
Above Cut-In
0 Volts
Running
Below Cut-Out
Line Voltage
Off
Содержание ICVD3095
Страница 2: ......
Страница 12: ...12 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 25: ...Part Number Preliminary 6 11 25 This Page Intentionally Left Blank ...
Страница 26: ...26 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 72: ...72 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 101: ...Part Number Preliminary 6 11 101 This Page Intentionally Left Blank ...
Страница 132: ...132 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 137: ...Part Number Preliminary 6 11 137 This Page Intentionally Left Blank ...
Страница 138: ...138 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 187: ...Part Number Preliminary 6 11 187 This Page Intentionally Left Blank ...
Страница 188: ...188 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 225: ...Part Number Preliminary 6 11 225 This Page Intentionally Left Blank ...
Страница 226: ...226 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 262: ...262 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 283: ...Part Number Preliminary 6 11 283 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Страница 291: ...Part Number Preliminary 6 11 291 This Page Intentionally Left Blank ...
Страница 298: ...298 Part Number Preliminary 6 11 USING PINCH OFF TOOL ...
Страница 303: ...Part Number Preliminary 6 11 303 This Page Intentionally Left Blank ...
Страница 304: ...304 Part Number Preliminary 6 11 ...
Страница 305: ...Part Number Preliminary 6 11 305 This Page Intentionally Left Blank ...
Страница 306: ...306 Part Number Preliminary 6 11 This Page Intentionally Left Blank ...
Страница 336: ...336 Part Number Preliminary 6 11 I0300 I0320 I0450 I0500 I0520 Self Contained Air Water cooled 1 Ph ...
Страница 337: ...Part Number Preliminary 6 11 337 I0500 Remote Air cooled 1Ph ...
Страница 338: ...338 Part Number Preliminary 6 11 I0600 I0850 I1000 I1200 Self Contained Air Water cooled 1 3 Ph ...
Страница 339: ...Part Number Preliminary 6 11 339 I0600 I0850 I1000 Remote Condenser Air cooled 1 3 Ph ...
Страница 340: ...340 Part Number Preliminary 6 11 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Страница 341: ...Part Number Preliminary 6 11 341 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Страница 342: ...342 Part Number Preliminary 6 11 I1400 I1800 Self Contained Air Water cooled 1 3 Ph ...
Страница 343: ...Part Number Preliminary 6 11 343 I1400 I1800 Remote Air cooled 1 3 Ph ...
Страница 349: ......