Part Number: 000015431 Rev01 5/19
151
HIGH PRESSURE CUTOUT (HPCO) CONTROL
FUNCTION
Stops the ice machine if subjected to excessive high-side
pressure. The HPCO control is normally closed, and opens
on a rise in discharge pressure.
SPECIFICATIONS
Specifications
Cut-Out
Cut-In
R404A
450 psig ±7
(3102 kPa ±48
31 bar ±0.48)
300 psig ±10
(2068 kPa ±69
20.68 bar ±0.69)
R410A
600 psig ±10
(3147 kPa ±69)
450 psig ±10
(3103 kPa ±69)
Automatic Reset
Opening the HPCO will initiate the 5 minute compressor
time delay. Repeated HPCO opening/closing or failure to
close will result in an E01 long freeze error.
CHECK PROCEDURE
1. Connect manifold gauges to ice machine.
2. Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
3. Refer to chart below.
HPCO Setpoint Reading Should Be
HPCO Contact Position
Below Cut-Out
0 Volts
Closed
Above Cut-In
Line Voltage
Open
Содержание CVDF0600
Страница 1: ...Part Number 000015431 Rev01 5 19 QuietQube Series Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 12: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 68: ...68 Part Number 000015431 Rev01 5 19 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 208: ...208 Part Number 000015431 Rev01 5 19 IF2100C 1 2 3 4 5 6 7 10 11 12 13 15 16 17 13 12 14 14 9 18 11 12 12 T4 T3 T1 T2 ...
Страница 210: ...210 Part Number 000015431 Rev01 5 19 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 211: ......