20
Check of damper blade displacement can be realize after actuating mechanism supply connec-
tion or signal connection from higher level control systems. Blade displacement from position
“OPEN” to position “CLOSED” and return displacement is checked.
Before entering the dampers into operation after assembly and after sequential revisions, checks
and functionality tests of all designs including operation of the electrical components must be
successfully provided and finished.
After entering into operation, these revisions must be done
according to requirement set by national regulations.
In case that dampers are found unable to serve for their function for any cause, it must be clearly
marked. The operator is obliged to ensure that the damper is put into condition in which it is ready
for function and meanwhile he is obliged to provide the fire protection by another appropriate way.
Results of regular checks, imperfections found and all-important facts connected with the damper
function must be recorded in the "FIRE BOOK" and immediately reported to the operator.
Before entering the dampers into operation after their assembly and by sequential checks, the
following checks must be carried out for all designs.
Visual inspection of proper damper integration, inside damper area, damper blade, contact
surfaces and silicon sealing.
Spare parts are supplied only on basis of an order.
Product label is placed on the damper casing
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
EN 12101-8:2011
TPM 121/16
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2020/0187, DoP: PM/SEDS-L/01/20/2
Содержание SEDS-L
Страница 1: ......