13
1
22.5
0.0937
BEN
1
27.5
0.1363
BEN
2
26.1
0.1115
BEN
2
32.0
0.1622
BEN
2
27.7
0.1445
BEN
2
33.9
0.2102
BEN
2
29.2
0.1775
BEN
2
35.7
0.2582
BEN
2
30.7
0.2105
BEN
2
37.6
0.3062
BEN
3
34.2
0.2284
BEN
3
42.0
0.3322
BEN
3
35.7
0.2614
BEN
3
43.9
0.3802
BEN
3
38.8
0.3274
BEN
3
50.3
0.4762
BEE
4
46.4
0.3782
BEE
4
56.5
0.5501
BE
4
49.5
0.4442
BEE
4
60.3
0.6461
BE
5
54.5
0.4950
BEE
5
66.5
0.7200
BE
5
57.5
0.5610
BE
5
70.2
0.8160
BE
6
62.5
0.6118
BE
6
76.5
0.8899
BE
6
65.6
0.6778
BE
6
80.2
0.9859
BE
1
24.2
0.1079
BEN
1
29.1
0.1505
BEN
2
28.1
0.1284
BEN
2
34.0
0.1791
BEN
2
29.7
0.1664
BEN
2
35.9
0.2321
BEN
2
31.4
0.2044
BEN
2
37.9
0.2851
BEN
2
33.0
0.2424
BEN
2
39.9
0.3381
BEN
3
36.8
0.2630
BEN
3
47.2
0.3668
BEE
3
38.4
0.3010
BEN
3
49.2
0.4198
BEE
3
41.7
0.3770
BEN
3
53.2
0.5258
BEE
4
49.8
0.4355
BEE
4
59.9
0.6074
BE
4
53.1
0.5115
BEE
4
63.8
0.7134
BE
5
58.5
0.5700
BE
5
70.5
0.7950
BE
5
61.8
0.6460
BE
5
74.5
0.9010
BE
6
67.2
0.7045
BE
6
81.1
0.9826
BE
6
70.5
0.7805
BE
6
85.1
1.0886
BE
1
25.8
0.1221
BEN
1
30.8
0.1647
BEN
2
30.0
0.1453
BEN
2
35.9
0.1960
BEN
2
31.8
0.1883
BEN
2
38.0
0.2540
BEN
2
33.5
0.2313
BEN
2
40.1
0.3120
BEN
2
35.3
0.2743
BEN
2
42.2
0.3700
BEN
3
39.4
0.2976
BEN
3
49.8
0.4014
BEE
3
41.1
0.3406
BEN
3
51.9
0.4594
BEE
3
47.3
0.4266
BEE
3
56.1
0.5754
BE
4
53.1
0.4928
BEE
4
63.2
0.6647
BE
4
56.7
0.5788
BE
4
67.4
0.7807
BE
5
62.5
0.6450
BE
5
74.5
0.8700
BE
5
66.0
0.7310
BE
5
78.7
0.9860
BE
6
71.8
0.7972
BE
6
85.8
1.0753
BE
6
75.4
0.8832
BE
6
90.0
1.1913
BE
Smoke extraction dampers single are designed to remove heat and combustion products (e.g.
smoke) from single fire compartment according EN1366-9.
Smoke extraction dampers single are designed for installation with horizontal or vertical axis of the blades.
Backtoback smoke exhaust duct has to be hung or supported so as all load transfer from the backtoback
smoke
exhaust
duct
to
the
damper
is
absolutely
excluded.
To
provide
needed
access space to the control device, all other objects must be situated at least 350 mm from the
control parts of the damper.
During installation the damper blade must be in position CLOSED. The damper body should
not be deformed in the course of installation. Once the damper built in, its blade should not grind
on the damper body during opening or closing.
Example, how to calculate effective area and size of SEDS-L damper [AxB], when knowing air volume in [m
³
/s] or [m
³
/h] on damper.
Maximum allowed air velocity on SEDS-L is 12 [m/s].
Formula:
Q … air volume [m
³
/s]
Sef … effective free area of damper [m
²
]
v … air velocity on damper [m/s]
Example:
Air volume needed is 26000 m
³
/h
26000 / 3600 = 7,222 m
³
/s
7,222 / 12 = 0,602 m
²
is min. effective free area [Sef]
Find the value Sef in the table 3.2.1. The effective are has to be the same or bigger. There will be more options of damper, sizes AxB.