background image

10

Power voltage

AC 24 V 50/60Hz

Power consumption

3,5 W (operating position)

Dimensioning

5,5 VA 18 VA (Imax 6.4 A @ 2.5 ms)

Protection class

III (low voltage)

Degree of protection

IP 20

Ambient operation temperature

0 … +50°C

Connection

screw terminals for 2x1.5 mm

2

 conductor

 

Communication and control devices

 indicates operating condition and faults of flue dampers. These conditions can be

signalled  or  transmitted  to  the  higher-level  control  system  via  the  auxiliary  built-in  contacts.
Signals from individual BKNE 230-24 are evaluated separately. All BKNE 230-24 are controlled
simultaneously. A maximum of 6 BKNE 230-24 can be connected to the BKSE 24-6.

 

Damper control is ensured with a simple 2-wire line. The damper's correct function is indicated by
two LEDs. The operating status of the entire control system and any errors are indicated by these
LEDs and the corresponding error LED.

 

Mounting and connection of BKSE 24-6 can be done on a 35mm DIN rail. It's connected using
two 9-pin terminal blocks (plug connectors).

17

~

AC 24 V

18

15

16

13

14

2

1

4

3

6

5

7

9

8

11

12

10

+

-

U

a1...a6

BKNE 230-24

a1...a6

Input 1

SMOKING

AUTO

END OF SMOKING

COM

delay 0 s (fan)

delay 60 s (fan)

OPEN

CLOSED

* Error

* reverse output: fault = contact open

Input 2
(galvanically isolated)

Содержание SEDS-L

Страница 1: ......

Страница 2: ...on designing ordering delivery maintenance and operation 1 Description 3 2 Design 4 3 Dimensions weights 11 4 Placement and Assembly 13 5 Suspension systems 15 6 Pressure drops 16 7 Noise data 16 8 Ma...

Страница 3: ...applications according with EN 1366 9 The field of direct applications based on tests results is acceptable according to EN 1363 1 part A 1 and A 2 EN 1366 2 part 13 and EN 1366 10 part 9 Smoke extra...

Страница 4: ...r blade positions is ensured by two built in fixed potential free end limit switches The actuator for operating the damper blade is mounted in an insulated cover box It is accessible after removing th...

Страница 5: ...I III II Degree of protection IP 54 Adjustment time for 95 30 s Ambient temperature Storage temperature 30 C 55 C 40 C 80 C Connection drive auxiliary switch Cable 1 m 3 x 0 75 mm2 Cable 1 m 6 x 0 75...

Страница 6: ...1 W 3 W 0 3 W 3 5 W 0 4 W Dimensioning 5 VA Imax 8 2 A 5 ms 5 5 VA Imax 8 2 A 5 ms 6 VA Imax 4 A 5 ms Protection class III III II Degree of protection IP 54 Adjustment time for 95 60 s Ambient temper...

Страница 7: ...in the end position 12 W 0 5 W 8 W 0 5 W Dimensioning 18 VA Imax 8 2 A 5 ms 15 VA Imax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Adjustment time for 95 60 s Ambient temperature Sto...

Страница 8: ...30 24 controls the switching position of the actuator its adjustment time and the data exchange with the BKSE 24 6 In addition it controls the actuator current actuator connection and the power supply...

Страница 9: ...work drive terminal blocks cable 1 m without plug 6 pin plug 3 pin plug screw terminals for 2x1 5 mm2 conductor yellow flashing damper rotates to the open position yellow lit up damper is open green f...

Страница 10: ...valuated separately All BKNE 230 24 are controlled simultaneously A maximum of 6 BKNE 230 24 can be connected to the BKSE 24 6 Damper control is ensured with a simple 2 wire line The damper s correct...

Страница 11: ...11 1 Damper body 2 Damper blade 3 Actuating mechanism cover Dimensions mm mm BEN BEE 176 5 315 BE 186 5 380 BEN BEE BKNE 236 5 315 BE BKNE 251 5 380 standard height of the flange...

Страница 12: ...44 5 0 3075 BEE 5 38 5 0 1785 BEE 5 47 0 0 3485 BEE 6 41 6 0 1947 BEE 6 50 9 0 3801 BEE 6 43 6 0 2157 BEE 6 53 4 0 4211 BEE 1 15 9 0 0369 BEN 1 19 2 0 0653 BEN 2 18 3 0 0439 BEN 2 22 2 0 0777 BEN 2 19...

Страница 13: ...53 1 0 4928 BEE 4 63 2 0 6647 BE 4 56 7 0 5788 BE 4 67 4 0 7807 BE 5 62 5 0 6450 BE 5 74 5 0 8700 BE 5 66 0 0 7310 BE 5 78 7 0 9860 BE 6 71 8 0 7972 BE 6 85 8 1 0753 BE 6 75 4 0 8832 BE 6 90 0 1 1913...

Страница 14: ...1 Damper hinge 2 Nut 3 Washer 4 Profile C 5 Washer C 6 Wall construction without fire resistance 7 Atypical protection box with access to actuator from side not as standard from the top Installation...

Страница 15: ...234 M20 245 150 300 Position 1 Threaded rod M8 M20 2 Nut 3 Washer 4 Coupling Nut 5 Anchor 6 Hinge plate min thickness 10 mm 7 Concrete screw tested for fire resistance R30 R90 max Tension up to 0 75...

Страница 16: ...63 68 68 67 65 62 48 57 65 70 70 69 67 64 50 w air velocity in the free cross section AxB i e before blades f frequency of octave band Sound power level corrected with filter A ps static pressure drop...

Страница 17: ...67 65 62 48 w air velocity in the free cross section AxB i e before blades f frequency of octave band 13 21 26 26 25 23 20 6 21 29 34 34 33 31 28 14 28 36 41 41 40 38 35 21 34 42 47 47 46 44 41 27 38...

Страница 18: ...re must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages when transported and manipulated All effective safety standards and directi...

Страница 19: ...ith cables from actuator acc to above mentioned electrical diagram Seal up the space around cable with fire resistant mastic HILTI CFS S ACR PROMASTOP or equivalent Let the mastic harden Drill two hol...

Страница 20: ...o ensure that the damper is put into condition in which it is ready for function and meanwhile he is obliged to provide the fire protection by another appropriate way Results of regular checks imperfe...

Страница 21: ...tuating mechanism BEN BEE BE for 230V 44 with actuating mechanism BEN BEE BE for 24V 54 with actuating mechanism BEN BEE SR for 24V 65 with the communication and supply device BKNE 230 24 and actuatin...

Страница 22: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Отзывы: