SEDM-L - Smoke extraction damper - multi
Page 42
Version 2022-12-20
TPM 157/22
1
Solid wall construction
2
SEDM-L
3
Ablative Coated Batt
4
Fixing element/steel bracket for connecting damper to the wall
(optional accessories MANDIK, a.s. or sheet metal min. thickness 2 mm
and min. width 60 mm). Full drawing of bracket,
5
Anchor to concrete min. M6
6
Installation hols
7
M8 bolt assemply (bolt M8x55 mm, 2 pcs large washer M8, nut M8) *
■
The method of mounting must meet the minimum requirements
for attachment in accordance with national regulations.
Fixing SEDM-L to the solid wall / solid shaft wall construction with Ablative Coated Batt system
Suspension systems
*
RESPECT JOINT POSITION !
Bolts and nuts shall not prevent free rotation on the blades.
A
A
FOR:
A < 500 => 1 anchor
1)
A ≥ 500 => 2 anchor
2)
FOR:
B = 430 and 630 => 1 anchor
3)
B = 830, 1030, 1230 => 2 anchors
4)
B = 1430, 1630, 1830, 2030 => 3 anchors
5)
N => number of blades
View A