18
Nut M8 and anchor
8-fixing part of the pipe (see only
example and recommneded type
on this picture)
Holes for rivets
View A:
Solid ceiling construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Pipe insulation with minimal fire resistance EI60 (e.g. ISOVER Ultimate protect Wired MAT 4.0 ALU1)
Fixing part of the pipe between wall and pipe (mandatory)
Hanging ring (e.g. FISCHER - type LGS)
150
Installation of pipe insulation perform according instructions of the manufacturer (e.g. ISOVER, ROCKWOOL,PAROC ...).
Minimal wool density for pipe insulation must be 66kg/m.
Minimal thickness of the ceiling is for concrete 110mm and fo aerated concrete 125mm.
This fixing part isn't mandatory if the installation opening was fulfill by mortar or gypsum. In other cases of the fire resistant
fill is this fixing part of the pipe mandatory. This fixing part can by mounted on the both sides of the wall.
Fire classification:
Ø D
Connecting surface between wall
and pipe insulation fulfil with fire
resistant sealant before instalation of
the insulation (recommended type of
sealant - see instalation instructions
of the insulation contractor).
Ø D+200