15
Gypsum wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Pipe insulation with minimal fire resistance EI60 (e.g. ISOVER Ultimate protect Wired MAT 4.0 ALU1)
Fixing part of the pipe between wall and pipe (mandatory)
Hanging ring (e.g. FISCHER - type LGS)
≥
100
Fire classification:
Connecting surface between wall and pipe insulation
fulfil with fire resistant sealant before instalation of
the insulation (recommended type of sealant - see
instalation instructions of the insulation contractor).
Installation of pipe insulation perform according instructions of the manufacturer (e.g. ISOVER, ROCKWOOL,PAROC ...).
Minimal wool density for pipe insulation must be 66kg/m.
This fixing part isn't mandatory if the installation opening was fulfill by mortar or gypsum. In other cases of the fire
resistant fill is this fixing part of the pipe mandatory. This fixing part can by mounted on the both sides of the wall.
View A:
Ø
D
Screw M8 and anchor
8-fixing part of the pipe (see only
example and recommneded type
on this picture)
Holes for rivets
Ø
D
+2
00
Содержание FDMS Series
Страница 1: ......
Страница 12: ...11 Fire classification 96 47 47 96 96...
Страница 15: ...14 Fire classification 96 47 47 96 96...
Страница 18: ...17 Fire classification 96 47 47 96 96...
Страница 29: ...28...
Страница 30: ...29...
Страница 31: ...30...