Содержание FDMB

Страница 1: ......

Страница 2: ...eral stone wool min density 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 75...

Страница 3: ...rials example 3 HILTI CFS F FX EIS 60 PROMAFOAM C EIS 45 SOUDAL Soudafoam FR B1 EIS 30 DenBraven Fire protection foam EIS 30 Position 1 Fire damper 2 Solid wall construction 3 Fire protection foam 4 S...

Страница 4: ...n density 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Duct 100 Screws has to be fixed in wall ceiling construction If it is need...

Страница 5: ...5 100 100 Position 1 Fire damper 2 Installation frame 3 Solid wall construction 100...

Страница 6: ...terials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Position 1 Fire damper 2 Solid wall construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Duct D 60 to 800 max 2050 D 60 to...

Страница 7: ...not limited 100 80 80 100 Insulation materials can be replaced by another approved fire sealing system with equivalent properties The maximum distance of the fire damper from the structure is not lim...

Страница 8: ...s Depends on the distance of the flap from the construction when the maximum distance from the construct is not limited and according to EN 15882 2 must use the required number of hinges according to...

Страница 9: ...5 Promastop P K Hilti CFS CT Installation opening has to be reinforced by steel U profile Profile is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm 100 75 Position 1...

Страница 10: ...re protection foam EIS 30 Position 1 Fire damper 2 Gypsum plate 3 Mineral wool type depending on the type of construction 4 Fire protection foam 5 Stucco plaster 6 Duct Installation opening has to be...

Страница 11: ...n density 870 kg m 7 Duct Around the perimeter 300 300 25 25 Screw min 4x50 Screws has to be fixed in wall ceiling construction If it is needed use steel bracket Used materials example 4 Promapyr Rock...

Страница 12: ...ofile is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm Installation opening has to be reinforced by steel U profile Profile is fixed by screws 3 5 mm with corre spon...

Страница 13: ...t board 5 Fire stop coating thickness 1 mm 6 Duct D 60 to 800 max 2050 D 60 to 800 max 1650 Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT 100 Installation opening has to be reinforc...

Страница 14: ...80 mm ALU1 Position 1 Fire damper 2 Gypsum plate 3 Mineral wool type depending on the type of construction 4 Stuffing box mineral stone wool min density 140 kg m 5 Fire protection mastic min thickness...

Страница 15: ...materials can be replaced by another approved fire sealing system for damper installation with equivalent material properties Depends on the distance of the flap from the construction when the maximu...

Страница 16: ...tic min thickness 1 mm 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS C...

Страница 17: ...ol Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 5 Promatect H Position 1 Fire damper 2 Solid ceiling construction 3 Stuffing box mineral stone wool min density 140 kg m 4 Fire pro...

Страница 18: ...18 min 110 Concrete min 125 Aerated concrete Position 1 Fire damper 2 Installation frame 3 Solid ceiling construction...

Страница 19: ...ncrete min 125 Aerated concrete Position 1 Fire damper 2 Solid ceiling construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Duct Used materials example 3 Hilti CFS CT B 1S 140 50 4...

Страница 20: ...nce from the construct is not limited and according to EN 15882 2 must use the required number of hinges according to EN 1366 1 2014 Reinforcement fixing VRM Installation of profile U25x40x25 When usi...

Страница 21: ...21 30 100 75 750 Position 1 Fire damper 2 Solid ceiling construction 3 Concrete B20 4 Rebar 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete 100 100...

Страница 22: ...to be done on each corner of VRM For dampers with A 800 and damper placement outside wall construction is necessary to use reinforcement VRM 35 Screw 4 2x50 max 350 100 1 Cut the groove for profil U25...

Страница 23: ...500x400 X 36 AxB 500x400 123 110 B B 60 A A 60 375 B X B 60 A X A 60 60 X 2 60 X 2 37 5 Position 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical...

Страница 24: ...24 1 Damper 2 Mounting plate 3 Sealing cover 4 Seal plates 5 Mounting plate cover 6 Thermal fuse 7 Mechanics 8 Actuator 9 Temperature sensor 10 Sensor sticker...

Страница 25: ...re the distance between the adjacent dampers must be at least 200 mm The damper blade in its closed position must be inside of the fire separating structure The fire damper may also be installed outsi...

Страница 26: ...from the damper control parts At least one inspection hole must be accessible The damper body must not get deformed during its installation process Once the damper is built installed its blade must n...

Страница 27: ...of dampers c a 16 5 30 16 5 10 2 0 10 20 10 8 5 10 10 8 5 20 X 2 16 5 30 X 2 16 5 10 2 0 X 23 AxB 500x400 X 36 AxB 500x400 140 165 190 5 215 15 220 20 240 30 255 40 265 52 5 290 65 295 80 15 315 90 4...

Страница 28: ...ED 1 2 S3 S1 S2 S5 S4 S6 N L1 5 80 BAT Tf Tf LED AC 230V 5A IP 67 25 C 120 C 1 COM black wire 2 NC gray wire 4 NO blue wire This limit switch is possible to connect in following two versions a if the...

Страница 29: ...pers body with four screws M6 Removing the thermal fuse from the fuse holder of initiation device check its correct functionality The mechanism is identified as M1 to M4 depending on the closing sprin...

Страница 30: ...stos free fire resistant mineral fibre boards The damper control devices are made of galvanized materials alternatively of stainless steel without any additional surface finish The springs are galvani...

Страница 31: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...