the setting mode is made by setting the 

EE

 parameter and confirmation with the S button  

or  automatically  after  17  seconds  of  inactivity.  The  following  figure  illustrates  
the programming procedure:

 

 

 

 
 

7. 

THE REGULATOR’S WORK CYCLE

.

 

When  the  regulator  is  connected  to  the  mains  and  its  operation  is  switched  on  with  
the button 

[1]

, the regulator 

 after the delay set in parameter 

dE

 

 goes to the control 

phase. 
The regulator controls two control circuits: 

a.

 

control circuit for the refrigeration (heating) unit; 

b.

 

control circuit for the stirrer’s (

fan

’s)

 motoreducer. 

The work for the control settings of the refrigeration system will be discussed below. 

 

ATTENTION 

Parameter 

dE

 is the delay of switching on the unit and the stirrer after switching on 

the regulator's work or after the supply voltage decay 

 default value is set to 

5 sec

.

 

 

7.1. Control of the refrigeration unit. 

The temperature control value (within the range specified in parameters 

b1

 and 

b2

) is 

set by pressing the buttons marked with the symbols 

 and 

, while short pressing any 

of  these  buttons  displays  the  currently  set  value,  while  only  the  next  pressing  causes  
the  change  of  this  value.  Transition  on  the  display  from  reading  the  measured 
temperature to the reading of the set control temperature is signaled by the flashing  
of digits / numbers. 

Содержание SMT-01

Страница 1: ...rature measuring range between 40 OC and 120 OC control temperature range between 40 OC and 120 OC decreased by a set hysteresis measuring resolution of the temperature measurer resolution of control...

Страница 2: ...er ventilator 10 A 250 V AC power supply 230 V AC 50 HZ protection class IP 55 safety class CE 3 CONSTRUCTION Regulator SMT is placed in a compact casing including all control and executive elements T...

Страница 3: ...own depending on the type of regulator The regulator SMT 02H v 3 apart from cable entry through glands has a sealing connection of the front part of the casing with its back which ensures splash proof...

Страница 4: ...LATOR In order to connect the regulator to the device with which it is to be controlled the following should be done prepare the hole in the refrigeration device to install the regulator place the reg...

Страница 5: ...d temperature parameter C9 is set to the value 0 3 Light signaling function for switching on the cooling heating operation blue LED is on 4 Control function of the heating system depending on the meas...

Страница 6: ...g visual and audible of exceeding the set temperature range parameters HA and HE This function is connected with the possibility of delaying the time of switching on the alarm system of the regulator...

Страница 7: ...motoreducer The work for the control settings of the refrigeration system will be discussed below ATTENTION Parameter dE is the delay of switching on the unit and the stirrer after switching on the re...

Страница 8: ...e difference at which the switching off occurs and then the unit is switched on For example if the control temperature is set to 4 OC and hysteresis to 2 OC then the unit will be switched off after re...

Страница 9: ...lapses the manual operation of the stirrer is switched off ATTENTION No light signaling of the stirrer operation 7 8 when the regulator is switched off means that the automatic stirrer operation has b...

Страница 10: ...e delay time of enabling this function allows for pre cooling of the milk after the start of cooling and thus not taking into account the maximum temperature when the device is started This time shoul...

Страница 11: ...in the initial cooling phase Exceeding the set temperature range is signaled visually and sound In the event of activation of the alarm the buzzer is triggered cyclically every 1 minute for 5 seconds...

Страница 12: ...to 120 OC every 1 0 OC 10 OC control hysteresis HI the possibility of setting the temperature from 0 2 OC to 10 OC every 0 2 OC for the range from 10 OC to 100 OC and from 1 0 OC to 10 OC every 1 0 OC...

Страница 13: ...1 the possibility of setting the temperature from 40 OC to 120 OC every 1 0 OC 2 OC upper temperature of the alarm A2 the possibility of setting the temperature from 40 OC to 120 OC every 1 0 OC 12 OC...

Отзывы: