8.2. The function of registering the minimum and maximum temperatures. 

The  SMT  regulator  has  the  function  of  recording  in  its  internal  memory  the  values  
of  maximum  and  minimum  temperatures  that  occur  throughout  the  regulator's 
operating cycle. This function makes it possible to check whether the milk is stored under 
the correct temperature conditions.  
When the device is switched on, after the end of the programmed delay (parameter 

AA

 

 see 

9. TABLE OF SETTINGS

), the temperature values are recorded to the regulator's 

memory. The programmable delay time of enabling this function allows for pre-cooling 
of  the  milk  after  the  start  of  cooling  and  thus  not  taking  into  account  the  maximum 
temperature when the device is started. This time should be selected by the user for the 
type of tank and the actual operating conditions of the device. 
At any time, the user can read the maximum 

and minimum temperaturę 

values presently 

available. The following figure illustrates reading:

 

 

 

 

ATTENTION 

1. In the absence of entries of maximum and minimum temperatures in the regulator's 
memory, the symbol --- is displayed. 
2. Power supply loss causes the regulator's memory to be cleared.

 

 
At  any  time,  you  can  manually  delete  the  current  maximum  and  minimum  values.  
The following figure illustrates manual memory erasing:

 

 

Содержание SMT-01

Страница 1: ...rature measuring range between 40 OC and 120 OC control temperature range between 40 OC and 120 OC decreased by a set hysteresis measuring resolution of the temperature measurer resolution of control...

Страница 2: ...er ventilator 10 A 250 V AC power supply 230 V AC 50 HZ protection class IP 55 safety class CE 3 CONSTRUCTION Regulator SMT is placed in a compact casing including all control and executive elements T...

Страница 3: ...own depending on the type of regulator The regulator SMT 02H v 3 apart from cable entry through glands has a sealing connection of the front part of the casing with its back which ensures splash proof...

Страница 4: ...LATOR In order to connect the regulator to the device with which it is to be controlled the following should be done prepare the hole in the refrigeration device to install the regulator place the reg...

Страница 5: ...d temperature parameter C9 is set to the value 0 3 Light signaling function for switching on the cooling heating operation blue LED is on 4 Control function of the heating system depending on the meas...

Страница 6: ...g visual and audible of exceeding the set temperature range parameters HA and HE This function is connected with the possibility of delaying the time of switching on the alarm system of the regulator...

Страница 7: ...motoreducer The work for the control settings of the refrigeration system will be discussed below ATTENTION Parameter dE is the delay of switching on the unit and the stirrer after switching on the re...

Страница 8: ...e difference at which the switching off occurs and then the unit is switched on For example if the control temperature is set to 4 OC and hysteresis to 2 OC then the unit will be switched off after re...

Страница 9: ...lapses the manual operation of the stirrer is switched off ATTENTION No light signaling of the stirrer operation 7 8 when the regulator is switched off means that the automatic stirrer operation has b...

Страница 10: ...e delay time of enabling this function allows for pre cooling of the milk after the start of cooling and thus not taking into account the maximum temperature when the device is started This time shoul...

Страница 11: ...in the initial cooling phase Exceeding the set temperature range is signaled visually and sound In the event of activation of the alarm the buzzer is triggered cyclically every 1 minute for 5 seconds...

Страница 12: ...to 120 OC every 1 0 OC 10 OC control hysteresis HI the possibility of setting the temperature from 0 2 OC to 10 OC every 0 2 OC for the range from 10 OC to 100 OC and from 1 0 OC to 10 OC every 1 0 OC...

Страница 13: ...1 the possibility of setting the temperature from 40 OC to 120 OC every 1 0 OC 2 OC upper temperature of the alarm A2 the possibility of setting the temperature from 40 OC to 120 OC every 1 0 OC 12 OC...

Отзывы: