TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
30
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
3.1.5.2 Cabling and fuse configuration
Full load input and output currents must be reviewed for proper cabling and fuse selection.
UPS
Rating
(KVA)
Rated Currents (A)
Input Currents (3P+N)
Output Currents (3P+N)
380V
400V
415V
380V
400V
415V
160
(PF 1)
355
340
326
242
232
222
160
(PF 0,9)
319
306
293
242
232
222
200
(PF 1)
443
424
407
303
290
278
200
(PF 0,9)
399
382
366
303
290
278
It should be noted that with non-linear loads, neutral current may rise up to 1.5 times the phase
current.
Ground cable must be connected directly to ground line and must be kept as short as possible.
Typical ground cable cross sections are 70 mm
2
for 160 kVA, 95 mm
2
for 200 kVA ratings. The
length of the cable must not be over 5 meters.
3.1.5.3 Cable connections
All electrical connections of the UPS are made from the front side of the device.
3 POLE-CIRCUIT BREAKERS (SWITCH) ARE USED FOR THE INPUT AND
OUTPUT OF UPS, NEUTRAL LINE MUST NOT BE INTERRUPTED.