TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
25
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
3 INSTALLATION
3.1 Single Module Installation
This section contains the warnings and control actions that must be performed before the UPS
start-up. Additionally, you will find here important information about the UPS cabins
transportation, positioning and connections.
3.1.1 Warnings
The UPS must be installed by a certified electrician of Makelsan.
The warranty is valid only for the UPS installed by a certified
electrician of Makelsan.
Battery Hazard
Battery terminal voltage reaches up to 450 Vdc during operation.
Proper safety gear must be used to protect the skin and the eyes from electrical arcs.
Check the batteries for leakage before using them.
ESD-protected rubber gloves should be used.
Batteries with leakage must never be used and must be replaced. Defected batteries must be
uninstalled and transported to the destruction points with safety precautions taken.
Battery ingredients are hazardous. In case of contact with battery ingredients, rinse the skin
with water, and consult a physician if irritation occurs.
Remove any metal accessories (ring, watch, etc.) before working on the device.
UPS needs three phase and four cable (+ground) supply system for input. This supply system
type is confirmed as IEC60364-3 standards. Optionally UPS have transformers which have
ability to convert from 3 cables to 4 cable system. If IT AC power distribution system will be
installed, 4 pole-circuit breaker systems must be used. More detailed explanations can be
found in the IEC60364-3 standards titles.