TRANSFORMER LEVELUPS T3 SERIES 160 - 200 KVA
PRODUCT DESCRIPTION
19
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
2.4.4 Password-protected menus
Some menus such as the control menu are
password protected. Press to set each digit and
press ENTER to confirm.
2.4.5 Control Menu
Within the control menu, you can do one of the following:
➢
Start
Start the UPS
➢
Stop
Stop the UPS
➢
Switch to BYPASS
Switch to static BYPASS mode
➢
Switch to UPS
Switch to online mode
➢
Bat. Quick Test
Start the quick battery test
➢
Bat. Capacity Test
Start the deep battery test
➢
Stop Battery Test
Stop the battery test
Battery status test, drains the 10% of battery
energy
and
reports
batteries
which has more capacity than 10% as
“Good”
, less
capacity than 10% as
“Replace”
according to the test
results.
After UPS is started, it makes quick battery test every
24 hours and when test counter value is zero (0).
Note
: Batteries must be fully charged and kept floating for at least 1 hour before applying the
quick battery tests.
Batteries must be fully charged and kept in floating mode for at least 5 hours before performing
the battery tests.