TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
40
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
3. Turn input circuit breaker (CB1) ON. If there is an external bypass input, put the external
bypass switch (CB5) to position closed circuit (ON)
4. Start the UPS using the front panel.
Main menu> Control > Password > Start
5. Check the UPS has switched to normal operation mode, via mimic diagram LEDs and LCD
panel.