W A R N I N G

This heater shall not be installed in a confined 
space or unusually tight construction unless 
provisions are made for adequate combustion 
and ventilation air.

W A R N I N G

If the area in which the heater may be operated 
is smaller than that defined as an unconfined 
space, or if the building is of unusually tight 
construction, provide adequate combustion and 
ventilation air by one of the methods described 
in the National Fuel Gas Code, ANSI Z223.1/NFPA 
54, 1992 Sections 5.3, or applicable codes.

WARNING:

 Before installing the gas logset in a solid-

fuel burning fireplace, the chimney flue and firebox must 
be cleaned of soot, creosote and loose paint by a quali-
fied chimney cleaner.

vent370-2

Ventilation options 

3/26/99   djt

Option 1 -

Vents to 

Adjoining 

Rooms

Option 2 -

Remove Door to 

Adjoining Rooms

Option 3 -

Vents to 

Adjoining 

Room

Fig. 2

 Ventilaton options for confined spaces.

12”

12”

VO370-2

4.

 Compare the maximum BTU/hour rating the space 

can support with the total BTU/hour used by the appli-
ances. 

Example: 

  76,800 BTU/hour the space can support

 

80,000 BTU/hour used by appliances

In this example, the maximum BTU/hour that the space 
can support is less than the total used by the applianc-
es. The space is considered to be 

Confined Space

.

Additional air must be provided to meet the require-
ments of the vent-free gas log set.
The installation and the provisions for combustion and 
ventilation air must conform with the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54, or the CSA-B149 Installa-
tion Code (Series).
A confined space may be ventilated in two ways:

A.

 Open or provide at least two ventilating grilles to an 

adjoining unconfined space. (Fig. 2)
Each of the two grilles must provide an opening of at 
least 50 square inches, with all opening dimensions be-
ing at least 3”. One grille must be within 12” of the ceil-
ing; the other within 12” of the floor. (If the total exceeds 
100,000 BTU/hour, additional grilles will be needed.)

B.

 Vent the room directly to the outdoors. (Provide one 

square inch of opening for each 4,000 BTU/hour)

For further information on ventilation guidelines and siz-
ing specifications, follow the National Fuel Gas Code/
NFPA 54/ANSI Z223.1, Section 5.3. 
If the total BTU/hour used by the appliances is less than 
the maximum BTU/hr the space can support, the room 
meets the 

Unconfined Space

 criteria and no further 

ventilation is needed.

Содержание VL18

Страница 1: ...rpora tion or company experienced in the installa tion repair and servicing of this type of gas appliance Do not modify alter or tamper with any part of this heater control or logs Do not store or use...

Страница 2: ...a sniffer Never test by using an open ame The area around the gas logset must be free of all combus tible materials especially gasoline or other highly ammable vapor producing liquids Due to high temp...

Страница 3: ...n USA installations must be in accordance with the current ANSI Z223 1 NFPA 54 and or local codes having jurisdiction In Canada please consult provincial and or local authorities having jurisdiction f...

Страница 4: ...cal codes If unvented room heaters are not permit ted the replace vent damper must be locked at the minimum vent area required by local codes or by the National Fuel Gas Code ANSI Z223 1 NFPA 54 lates...

Страница 5: ...openings If your home meets all of the above criteria you must provide additional fresh air for the appliance as detailed on Page 6 If your home does not meet the above criteria follow the procedure b...

Страница 6: ...r used by appliances In this example the maximum BTU hour that the space can support is less than the total used by the applianc es The space is considered to be Con ned Space Additional air must be p...

Страница 7: ...the manufacturer from outside the replace as marked by the manufacturer An ON OFF valve should be placed within easy reach of the appliance After the gas supply is installed reinstall the insulation r...

Страница 8: ...inside the re place locate the damper locking bracket on the left side of combustion dome Fig 4 Align the two slots on either side of the cutout on the damper stop with the two small holes on the ang...

Страница 9: ...e appliance to terminate at the right hand side for connection to the inlet of the appliance Connect the appliance to the gas line using ttings and aluminum tubing provided Close the valve knob on the...

Страница 10: ...stalled there must be noncombustible material from the top front opening of the replace to a height of 6 and the full width of the replace A combustible at mantel shelf and breastplate may be installe...

Страница 11: ...0 Locator Pin Fig 7 VL18 log placement LG102 VL21 logset 3 31 99 modified burner grate 4 3 00 djt Locator Pins Grate LG102 Locator Pin Locator Pin Fig 8 VL21 log placement LG104 VL24 logset 4 1 99 mod...

Страница 12: ...d the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace Do not touch any...

Страница 13: ...ury do not touch hot surfaces when the appliance is operating Touch only the valve control knob Avoid contact with the grate feet or prongs or any other part which may be very hot Always ensure that t...

Страница 14: ...4 1 99 changed valve 4 14 00 djt HI OFF PIL OT LO 7 9 Approx 6 8 Ap prox Fig 13 Typical ame patterns P101 Pilot w flame 3 26 99 djt LOW HIGH PILOT OFF Knob Shown in Pilot Position Flame Piezo Ignitor...

Страница 15: ...allow ing gas to ow D No gas supply to the replace A Defective thermocouple B Thermocouple tting not tight in valve C Weak pilot ame D Defective valve E Not enough oxygen in the room DANGER A Plugged...

Страница 16: ...ree Gas Logs Ref Description VL18 VL21 VL24 1 Complete Log Set 2242104 3141108 2240104 1a Top Side Logs 2 7398129 7398129 7398129 1b Top Center Log 7398128 7398128 2 1c Rear Bottom Log 2242106 3141110...

Страница 17: ...ef Description VL18 VL21 VL24 6b Burner Assembly LP 20002632 20002629 20002575 Copreci Valve 7 Nut 15mm 7511168 7511168 7511168 8 Valve Control Knob Extension 7536237 7536237 7536237 9 Knob 7536250 75...

Страница 18: ...information beyond what your dealer can furnish contact CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Attention Technical Service Accessory Description Required to protect wall a...

Страница 19: ...arranties speci ed in paragraphs A and B below with respect to its Vermont Castings Decorative Gas Appliances the Gas Appliance including CFM Corporation supplied accessories and components referred t...

Страница 20: ...CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: