Majestic VL18 Скачать руководство пользователя страница 10

10

20002538

Check the inlet pressure to the appliance, to ensure that 
it is as shown in the table on page 3. The minimum is 
for the purpose of input adjustment.
The pressure is controlled by the regulator and should 
be checked at the pressure test point located in the 
control valve body. Access to the pressure test point is 
obtained by removing all logs. 
The pressure should be checked with the appliance 
burning and the control set on ‘HIGH’. 
The pressure is preset and locked to avoid tampering. If 
the pressure is not as specified, replace the valve. See 
Replacement Parts, page 17.
After measuring the pressure, replace the test point 
plug, ensure there are no leaks, then place the logs in 
their specified positions.

There is a possibility of odor fade in LP. Never 
install an LP appliance or service line below 
grade without a gas detector.

Clearances

(Refer to Fig. 6, Page 9)
To ensure the safe installation into a masonry or factory 
built fireplace, the following instructions must be care-
fully observed.

1. Sidewall Clearances:

 The clearance from the inside 

of the front opening of the fireplace to any combustible 
wall or mantel should not be less than 4

¹⁄₂

”. (Fig. 6a)

2. Ceiling Clearances:

 The ceiling height should not be 

less than 42” from the top of the fireplace opening. 
(Fig. 6a)

3. Mantel Clearances: 

WITHOUT HOOD

If no hood is installed then there must be noncombusti-
ble material from the top front opening of the fireplace to 
a height of at least 20” and the full width of the fireplace. 
A combustible flat mantel shelf can be no closer than 
38

¹⁄₂

” from the top front of the opening of the fireplace. 

(Fig. 6b)

WITH HOOD

If a hood is installed there must be noncombustible 
material from the top front opening of the fireplace to 
a height of 6

³⁄₄

” and the full width of the fireplace. A 

combustible flat mantel shelf and breastplate may be 
installed. (Fig. 6c)
Failure to use a noncombustible material above the 
opening as specified in these instructions may cause 
damage to the materials used or cause a fire hazard.

4. Grate Clearances:

 The minimum clearance between 

the front legs of the grate and front edge of the fireplace 
is 3

¹⁄₄

”. (Fig. 6b)

NOTE:

 Combustible mantels, surrounds and cabinets 

should be finished with materials that can withstand 
250°F.

Positioning the Logs

The logs must be positioned on the grate and locating 
pins as shown in Figures 7-9.
Gas logs must be properly positioned or the appliance 
will not function properly and may result in soot accu-
mulation on the inside of the firebox and/or gas logs. 
Make sure there is no flame impingement on the logs 
which could result in excessive carbon monoxide emis-
sions.

WARNING: Failure to position the parts in accor-
dance with these diagrams or failure to use only 
parts specifically approved with this heater may 
result in property damage or personal injury.

Carefully position the logs as shown in Figures 7-9. 
Make sure each bottom log engages the locator pins on 
the grate and top logs are properly positioned in notch-
es on top of the bottom logs. 

Make sure there is no flame impingement on the 
cross logs which could result in excessive carbon 
monoxide emissions.
The optional volcanic rock may be applied to the 
hearth around the burner assembly.
Never place any other material on the burner.

Fireplace Screen

The fireplace screen must be in place when the appli-
ance is operating, and unless other provisions for com-
bustion air are made, the screen must have openings 
for the introduction of combustion air.

Содержание VL18

Страница 1: ...rpora tion or company experienced in the installa tion repair and servicing of this type of gas appliance Do not modify alter or tamper with any part of this heater control or logs Do not store or use...

Страница 2: ...a sniffer Never test by using an open ame The area around the gas logset must be free of all combus tible materials especially gasoline or other highly ammable vapor producing liquids Due to high temp...

Страница 3: ...n USA installations must be in accordance with the current ANSI Z223 1 NFPA 54 and or local codes having jurisdiction In Canada please consult provincial and or local authorities having jurisdiction f...

Страница 4: ...cal codes If unvented room heaters are not permit ted the replace vent damper must be locked at the minimum vent area required by local codes or by the National Fuel Gas Code ANSI Z223 1 NFPA 54 lates...

Страница 5: ...openings If your home meets all of the above criteria you must provide additional fresh air for the appliance as detailed on Page 6 If your home does not meet the above criteria follow the procedure b...

Страница 6: ...r used by appliances In this example the maximum BTU hour that the space can support is less than the total used by the applianc es The space is considered to be Con ned Space Additional air must be p...

Страница 7: ...the manufacturer from outside the replace as marked by the manufacturer An ON OFF valve should be placed within easy reach of the appliance After the gas supply is installed reinstall the insulation r...

Страница 8: ...inside the re place locate the damper locking bracket on the left side of combustion dome Fig 4 Align the two slots on either side of the cutout on the damper stop with the two small holes on the ang...

Страница 9: ...e appliance to terminate at the right hand side for connection to the inlet of the appliance Connect the appliance to the gas line using ttings and aluminum tubing provided Close the valve knob on the...

Страница 10: ...stalled there must be noncombustible material from the top front opening of the replace to a height of 6 and the full width of the replace A combustible at mantel shelf and breastplate may be installe...

Страница 11: ...0 Locator Pin Fig 7 VL18 log placement LG102 VL21 logset 3 31 99 modified burner grate 4 3 00 djt Locator Pins Grate LG102 Locator Pin Locator Pin Fig 8 VL21 log placement LG104 VL24 logset 4 1 99 mod...

Страница 12: ...d the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace Do not touch any...

Страница 13: ...ury do not touch hot surfaces when the appliance is operating Touch only the valve control knob Avoid contact with the grate feet or prongs or any other part which may be very hot Always ensure that t...

Страница 14: ...4 1 99 changed valve 4 14 00 djt HI OFF PIL OT LO 7 9 Approx 6 8 Ap prox Fig 13 Typical ame patterns P101 Pilot w flame 3 26 99 djt LOW HIGH PILOT OFF Knob Shown in Pilot Position Flame Piezo Ignitor...

Страница 15: ...allow ing gas to ow D No gas supply to the replace A Defective thermocouple B Thermocouple tting not tight in valve C Weak pilot ame D Defective valve E Not enough oxygen in the room DANGER A Plugged...

Страница 16: ...ree Gas Logs Ref Description VL18 VL21 VL24 1 Complete Log Set 2242104 3141108 2240104 1a Top Side Logs 2 7398129 7398129 7398129 1b Top Center Log 7398128 7398128 2 1c Rear Bottom Log 2242106 3141110...

Страница 17: ...ef Description VL18 VL21 VL24 6b Burner Assembly LP 20002632 20002629 20002575 Copreci Valve 7 Nut 15mm 7511168 7511168 7511168 8 Valve Control Knob Extension 7536237 7536237 7536237 9 Knob 7536250 75...

Страница 18: ...information beyond what your dealer can furnish contact CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Attention Technical Service Accessory Description Required to protect wall a...

Страница 19: ...arranties speci ed in paragraphs A and B below with respect to its Vermont Castings Decorative Gas Appliances the Gas Appliance including CFM Corporation supplied accessories and components referred t...

Страница 20: ...CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: