background image

INSTALLATION OF NON-COMBUSTIBLE FACING MATERIALS TO THE FRONT FACE OF THE FIREPLACE

COMBUSTIBLE FRAMING

MEMBERS FACING MATERIAL

 TO TOP OF SPACERS. 

CAUTION:  DO NOT COVER 

OR RESTRICT SIDE VENT 

AREAS WITH SURROUND 

OR TRIM MATERIALS. 

USE ONLY NON-COMBUSTIBLE

MATERIALS BELOW TOP OF SPACERS.

NON-COMBUSTIBLE

 FACING MATERIAL

FIREPLACE

FACE

STEEL LINTEL

 (OPTIONAL)

WARNING:

THE SPACE BETWEEN THE

FACE OF THE FIREPLACE

AND THE NON-COMBUSTIBLE

FACING MATERIAL MUST

MUST BE SEALED.  FAILURE 

TO PROPERLY SEAL THIS 

CRACK CAN CAUSE A 

POSSIBLE FIRE HAZARD AND

WILL VOID THE WARRANTY.

F

IGURE

 25

25

G

LASS

 D

OOR

 I

NSTALLATION

This fireplace has been tested and listed for use with optional Model WSB60 glass doors.  For installation of 
the Model WSB60 glass doors, see the instructions provided with the doors.

T

RIM

 

AND

 D

OOR

 I

NSTALLATION

F

IGURE

 26

53D9027

Содержание SB6000

Страница 1: ...SB6000 MODEL RESIDENTIAL FIREPLACE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS FIREPLACE IS LISTED BY OMNI TEST LABORATORIES FOR USE WITH L SERIES CHIMNEY SYSTEM COMPONENTS 53D9027 Rev 2 9 08...

Страница 2: ...ure to install operate and maintain this or any other factory built replace properly can result in a house re or other occurrences that could cause deaths injuries and property damages It is very impo...

Страница 3: ...commended for use in such areas INTENDED PRODUCT USAGE The replace is designed to sit directly on a combustible oor The replace must be installed with clearances to combustible building materials spec...

Страница 4: ...lling down to close the damper When the replace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the...

Страница 5: ...OT RESTRICT SIDE AIR INLET VENTS WITH SURROUND OR TRIM MATERIALS GALVANIZED METAL STRIP NAIL TO FRAMING MEMBERS SB6000 FIREPLACE MODEL FLEXIBLE DUCT TYPE FP 4 U COMBUSTION AIR ASSEMBLY NOTE IF MODEL W...

Страница 6: ...3 6 L 3 6 L 3 6 L 4 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36...

Страница 7: ...5 provide dimensional details of the replace required spacing to combustible walls and some suggested replace locations When selecting a location choose one that is away from frequently opened doors...

Страница 8: ...ney cap in a preferred location Refer to the sections of this manual pertaining to chimney offsets for instructions on proper elbow use Poor installation or location of the chimney cap and or componen...

Страница 9: ...FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGHT 2 CLEARANCE TO C...

Страница 10: ...ressive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2074 FIGURE 10 FIGURE 11...

Страница 11: ...ltiplied by 1 2 50 K 43 R The material thickness divided by K Example R 1 2 50 divided by 43 R 1 16 FLOOR PROTECTION With either type hearth extension minor shifting of the supporting oor or expansion...

Страница 12: ...himney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for contempora...

Страница 13: ...eplace and chimney CHIMNEY INSTALLATION In order to assure safe and satisfactory performance of the replace it is very important to properly install the chimney This is an important part of the instal...

Страница 14: ...es of the spacer and use a minimum of four 8 penney nails to secure the spacer 3 To install the L series chimney sections insert the male end of the ue the smallest diameter pipe into the ue outlet of...

Страница 15: ...1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC LEVEL FLUE PIPE FLUE...

Страница 16: ...inimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Dete...

Страница 17: ...TOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE OFFSET MAX 10 DIAGONAL CHIMNEY ENCLOSURE FASTEN ALL SUPPORT S...

Страница 18: ...the ashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the ashing securely in place with eight nails 6 Seal the crack between the top of the...

Страница 19: ...1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 4 3 5 4 3 5 4 6 5 4 6 5 4 6 5 7 6 5 7 6 5 7 6 8 3 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0...

Страница 20: ...s should be at least 24 inches apart to help prevent smoke from a replace in use from being drawn down the chimney of a replace that is not in use Additional spacing between caps or staggering the hei...

Страница 21: ...TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKET AND WILL SEAL AGAINST THE FIREBOX WALL WHEN SECURED AS INDICATED SE...

Страница 22: ...or location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly...

Страница 23: ...ce of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum ef ciency and safety Do not use a combustible duct Always...

Страница 24: ...NSI IAS AGA Z21 11 2 are to be installed in this replace WARNING Do not operate an unvented gas log set in this replace with the chimney removed The installer of the replace and gas appliance must des...

Страница 25: ...rther reduce the possibility of such a crack developing Wall ties should be fastened to the face of the replace with sheet metal screws and placed in the mortar joints of masonry trim Combustible mate...

Страница 26: ...RIAL FIREPLACE FACE STEEL LINTEL OPTIONAL WARNING THE SPACE BETWEEN THE FACE OF THE FIREPLACE AND THE NON COMBUSTIBLE FACING MATERIAL MUST MUST BE SEALED FAILURE TO PROPERLY SEAL THIS CRACK CAN CAUSE...

Страница 27: ...other wood goes a long way Start your re with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well when freshly cut the wood you p...

Страница 28: ...oors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to make a good re Add k...

Страница 29: ...ermine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney re The chimney cap can be removed for inspection maintenance and cleaning by...

Страница 30: ...for the installation of the replace 4 Do insulate the exterior walls surrounding the replace to prevent excessive heat loss from the replace 5 Do trim the face of the replace only with noncombustible...

Страница 31: ...liquids gases or pressurized containers near the replace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the replace 17 Don t fail to instruct all persons esp...

Страница 32: ...IRE BRICK BACK ASSEMBLY HANDLE DAMPER FIRE BRICK RT SIDE ASSEMBLY HEARTH REFRACTORY KEY NO 1 2 3 4 5 6 7 8 9 10 31 PARTS DIAGRAM AND LIST FIGURE 27 All repair part orders should be placed through your...

Страница 33: ...32 NOTES 53D9027...

Страница 34: ...ng code contains restrictions on the use of this replace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the replace...

Страница 35: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE...

Страница 36: ...SEPTEMBER 2008 53D9027 Rev 2 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: