NOTE: 

FLUE OUTLET SHOULD BE TWO FEET ABOVE ALL PORTIONS OF THE BUILDING

WITHIN TEN FEET AS SHOWN IN THE ILLUSTRATION. THE CHIMNEY MUST NOT

EXTEND MORE THAN 90 INCHES ABOVE THE ROOF WITHOUT ADDITIONAL SUPPORT. 

24" MIN.

36"

24" MIN.

36"

10'

10'

C

HIMNEY

 I

NSTALLATION

13

1.  Lay out, cut and frame openings through all ceilings and the roof at the point where the chimney will pass 

through.  Unless the chimney is to be offset, the point where the center line of the chimney will pass through 
the ceiling and roof can be determined with a plumb line as shown by Figure 16.  The fireplace should 
be located in the planned installation position.  After the center line is established and a nail is driven to 
mark the point, the opening can be cut if you are satisfied with the chimney location relative to ceiling and 
roof joists and/or any other obstructions.  The roof  opening center line should be marked by driving a 
nail through the roof from underneath that will penetrate the roof and can be located from the rooftop.  If 
the chimney is to penetrate a pitched roof, the hole in the roof must be rectangular instead of square and 
should be sized according to Table1.

2.  Install the firestop spacer as required from beneath the ceiling unless the space above is attic space.  In an 

attic, the firestop spacer should be installed at the floor level of the attic.  You must have joists or headers 
on all four sides of the spacer and use a minimum of four 8-penney nails to secure the spacer.

3.  To install the “L” series chimney sections, insert the male end of the flue, the smallest diameter pipe, into 

the flue outlet of the fireplace and press down until the snap locks engage.  Continue the process, adding 
the chimney sections on top of each other until the chimney is at least six inches above the roof opening 
on all sided.  As the chimney sections are installed, check each joint to make sure it is properly locked to 
the previous section.  If additional strength of the outer pipe joints is desired, you may use two or three 
sheet metal screws placed through the area where the outer pipes overlap one another.  To install these 
screws, drill a 1/8-inch diameter hole through the chimney sections, taking care not to penetrate the inner 
flue pipe.  Warning:  Be very careful when drilling the holes into the outer pipe.  The drill must not penetrate 
the inner stainless steel pipe.

NOTE:  If you intend to have a total fireplace installation of more that 30 feet you must use chimney support 
model LCS at or below 30 feet to support the weight of additional chimney pipe.

To install the chimney support, place the crimped end of the flue and outlet air duct portions into the last sec-
tion of chimney pipe.  Push down until the outside or inlet air duct of the chimney support overlaps and snap 
locks the chimney support into the chimney section.

Nail the support straps tightly to a building frame member or ceiling joist as shown by Figure 17.  You must 
use at least two 8-penney nails per strap.

F

IGURE

 15

53D9027

Содержание SB6000

Страница 1: ...SB6000 MODEL RESIDENTIAL FIREPLACE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS FIREPLACE IS LISTED BY OMNI TEST LABORATORIES FOR USE WITH L SERIES CHIMNEY SYSTEM COMPONENTS 53D9027 Rev 2 9 08...

Страница 2: ...ure to install operate and maintain this or any other factory built replace properly can result in a house re or other occurrences that could cause deaths injuries and property damages It is very impo...

Страница 3: ...commended for use in such areas INTENDED PRODUCT USAGE The replace is designed to sit directly on a combustible oor The replace must be installed with clearances to combustible building materials spec...

Страница 4: ...lling down to close the damper When the replace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the...

Страница 5: ...OT RESTRICT SIDE AIR INLET VENTS WITH SURROUND OR TRIM MATERIALS GALVANIZED METAL STRIP NAIL TO FRAMING MEMBERS SB6000 FIREPLACE MODEL FLEXIBLE DUCT TYPE FP 4 U COMBUSTION AIR ASSEMBLY NOTE IF MODEL W...

Страница 6: ...3 6 L 3 6 L 3 6 L 4 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36...

Страница 7: ...5 provide dimensional details of the replace required spacing to combustible walls and some suggested replace locations When selecting a location choose one that is away from frequently opened doors...

Страница 8: ...ney cap in a preferred location Refer to the sections of this manual pertaining to chimney offsets for instructions on proper elbow use Poor installation or location of the chimney cap and or componen...

Страница 9: ...FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGHT 2 CLEARANCE TO C...

Страница 10: ...ressive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2074 FIGURE 10 FIGURE 11...

Страница 11: ...ltiplied by 1 2 50 K 43 R The material thickness divided by K Example R 1 2 50 divided by 43 R 1 16 FLOOR PROTECTION With either type hearth extension minor shifting of the supporting oor or expansion...

Страница 12: ...himney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for contempora...

Страница 13: ...eplace and chimney CHIMNEY INSTALLATION In order to assure safe and satisfactory performance of the replace it is very important to properly install the chimney This is an important part of the instal...

Страница 14: ...es of the spacer and use a minimum of four 8 penney nails to secure the spacer 3 To install the L series chimney sections insert the male end of the ue the smallest diameter pipe into the ue outlet of...

Страница 15: ...1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC LEVEL FLUE PIPE FLUE...

Страница 16: ...inimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Dete...

Страница 17: ...TOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE OFFSET MAX 10 DIAGONAL CHIMNEY ENCLOSURE FASTEN ALL SUPPORT S...

Страница 18: ...the ashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the ashing securely in place with eight nails 6 Seal the crack between the top of the...

Страница 19: ...1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 4 3 5 4 3 5 4 6 5 4 6 5 4 6 5 7 6 5 7 6 5 7 6 8 3 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0...

Страница 20: ...s should be at least 24 inches apart to help prevent smoke from a replace in use from being drawn down the chimney of a replace that is not in use Additional spacing between caps or staggering the hei...

Страница 21: ...TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKET AND WILL SEAL AGAINST THE FIREBOX WALL WHEN SECURED AS INDICATED SE...

Страница 22: ...or location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly...

Страница 23: ...ce of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum ef ciency and safety Do not use a combustible duct Always...

Страница 24: ...NSI IAS AGA Z21 11 2 are to be installed in this replace WARNING Do not operate an unvented gas log set in this replace with the chimney removed The installer of the replace and gas appliance must des...

Страница 25: ...rther reduce the possibility of such a crack developing Wall ties should be fastened to the face of the replace with sheet metal screws and placed in the mortar joints of masonry trim Combustible mate...

Страница 26: ...RIAL FIREPLACE FACE STEEL LINTEL OPTIONAL WARNING THE SPACE BETWEEN THE FACE OF THE FIREPLACE AND THE NON COMBUSTIBLE FACING MATERIAL MUST MUST BE SEALED FAILURE TO PROPERLY SEAL THIS CRACK CAN CAUSE...

Страница 27: ...other wood goes a long way Start your re with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well when freshly cut the wood you p...

Страница 28: ...oors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to make a good re Add k...

Страница 29: ...ermine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney re The chimney cap can be removed for inspection maintenance and cleaning by...

Страница 30: ...for the installation of the replace 4 Do insulate the exterior walls surrounding the replace to prevent excessive heat loss from the replace 5 Do trim the face of the replace only with noncombustible...

Страница 31: ...liquids gases or pressurized containers near the replace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the replace 17 Don t fail to instruct all persons esp...

Страница 32: ...IRE BRICK BACK ASSEMBLY HANDLE DAMPER FIRE BRICK RT SIDE ASSEMBLY HEARTH REFRACTORY KEY NO 1 2 3 4 5 6 7 8 9 10 31 PARTS DIAGRAM AND LIST FIGURE 27 All repair part orders should be placed through your...

Страница 33: ...32 NOTES 53D9027...

Страница 34: ...ng code contains restrictions on the use of this replace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the replace...

Страница 35: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE...

Страница 36: ...SEPTEMBER 2008 53D9027 Rev 2 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: