background image

23

G

AS

 A

PPLIANCE

 I

NSTALLATION

 

W

ARNING

:

  Improper installation or operation of a gas appliance in this fireplace can allow unburned gas to leak 

out which will cause a fire or explosion hazard, or the release of poisonous carbon monoxide into the dwelling 
which can cause serious injury or death to its inhabitants.  To reduce these risks to a minimum, the following 
important notices and instructions should be read and followed carefully.

I

MPORTANT

 N

OTICES

:

  

1.  The provision for a gas line is intended for connection to a decorative gas appliance which has an automatic 

shutoff device and complies with the Standard for Decorative Gas Appliances for Installation in Vented 
Fireplaces, ANSIZ21.60.   If a decorative gas appliance is installed, it must be installed in accordance with 
the National Fuel Gas Code, ANSIZ223.1. 

 

C

AUTION

:

 

 “When a decorative gas appliance is installed, the fireplace damper must be fixed in a manner 

which will maintain the minimum permanent vent opening at all times.”  

 

If an unvented gas appliance (blue flame) is installed it must incorporate an automatic shutoff device, and 
must be installed in accordance with with the National Fuel Gas Code Z223.1, Latest edition.  

 

C

AUTION

:

  If an unvented gas appliance is installed in the fireplace, the gas appliance must only be operated 

with the fireplace glass door fully open (if included).  Only unvented gas log set which have been found to 
comply with the standard for unvented room heaters, ANSI/IAS/AGA Z21.11.2, are to be installed in this 
fireplace.  

 

W

ARNING

:

  Do not operate an unvented gas log set in this fireplace with the chimney removed.  The installer 

of the fireplace and gas appliance must describe the operation of the fireplace and appliance to the people 
who will be operating them and leave all instruction manuals with the operator of the appliance.

2.  An approved gas shut off valve must be located outside the fireplace in an area accessible to the users of 

the fireplace.

3.  All gas piping and fitting must be either steel or malleable iron.  Unions must be of the ground joint type.
4.  Some code authorities prohibit or place restrictions on the use of gas appliances in fireplaces.  Check with 

local code authorities before proceeding with the installation.

5.  The gas appliance and all connecting gas piping should only be installed by a licensed gas appliance 

installer.  

The following instructions only apply to passing the gas line through the fireplace wall.  Follow the instructions 
provided by the appliance for the gas line, testing and adjusting it.

1.  Locate the recessed area in the side refractory panel as shown by Figure 24.
2.  Tap out a round hole in the brick liner with a hammer by tapping lightly on the recessed area.
3.  Remove the two screws that hold the cover plates on the jacket wrap and discard the cover plate.
4.  Use a screwdriver or similar tool to push the loose insulation out of the tube between the firebox and the 

outer jacket of the fireplace.

5.  Install the gas pipe through the tube between the firebox and jacket.
6.  Attach the gas appliance to the gas pipe according to the appliance makers instructions.

53D9027

Содержание SB6000

Страница 1: ...SB6000 MODEL RESIDENTIAL FIREPLACE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS FIREPLACE IS LISTED BY OMNI TEST LABORATORIES FOR USE WITH L SERIES CHIMNEY SYSTEM COMPONENTS 53D9027 Rev 2 9 08...

Страница 2: ...ure to install operate and maintain this or any other factory built replace properly can result in a house re or other occurrences that could cause deaths injuries and property damages It is very impo...

Страница 3: ...commended for use in such areas INTENDED PRODUCT USAGE The replace is designed to sit directly on a combustible oor The replace must be installed with clearances to combustible building materials spec...

Страница 4: ...lling down to close the damper When the replace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the...

Страница 5: ...OT RESTRICT SIDE AIR INLET VENTS WITH SURROUND OR TRIM MATERIALS GALVANIZED METAL STRIP NAIL TO FRAMING MEMBERS SB6000 FIREPLACE MODEL FLEXIBLE DUCT TYPE FP 4 U COMBUSTION AIR ASSEMBLY NOTE IF MODEL W...

Страница 6: ...3 6 L 3 6 L 3 6 L 4 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36...

Страница 7: ...5 provide dimensional details of the replace required spacing to combustible walls and some suggested replace locations When selecting a location choose one that is away from frequently opened doors...

Страница 8: ...ney cap in a preferred location Refer to the sections of this manual pertaining to chimney offsets for instructions on proper elbow use Poor installation or location of the chimney cap and or componen...

Страница 9: ...FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGHT 2 CLEARANCE TO C...

Страница 10: ...ressive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2074 FIGURE 10 FIGURE 11...

Страница 11: ...ltiplied by 1 2 50 K 43 R The material thickness divided by K Example R 1 2 50 divided by 43 R 1 16 FLOOR PROTECTION With either type hearth extension minor shifting of the supporting oor or expansion...

Страница 12: ...himney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for contempora...

Страница 13: ...eplace and chimney CHIMNEY INSTALLATION In order to assure safe and satisfactory performance of the replace it is very important to properly install the chimney This is an important part of the instal...

Страница 14: ...es of the spacer and use a minimum of four 8 penney nails to secure the spacer 3 To install the L series chimney sections insert the male end of the ue the smallest diameter pipe into the ue outlet of...

Страница 15: ...1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC LEVEL FLUE PIPE FLUE...

Страница 16: ...inimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Dete...

Страница 17: ...TOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE OFFSET MAX 10 DIAGONAL CHIMNEY ENCLOSURE FASTEN ALL SUPPORT S...

Страница 18: ...the ashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the ashing securely in place with eight nails 6 Seal the crack between the top of the...

Страница 19: ...1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 4 3 5 4 3 5 4 6 5 4 6 5 4 6 5 7 6 5 7 6 5 7 6 8 3 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0...

Страница 20: ...s should be at least 24 inches apart to help prevent smoke from a replace in use from being drawn down the chimney of a replace that is not in use Additional spacing between caps or staggering the hei...

Страница 21: ...TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKET AND WILL SEAL AGAINST THE FIREBOX WALL WHEN SECURED AS INDICATED SE...

Страница 22: ...or location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly...

Страница 23: ...ce of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum ef ciency and safety Do not use a combustible duct Always...

Страница 24: ...NSI IAS AGA Z21 11 2 are to be installed in this replace WARNING Do not operate an unvented gas log set in this replace with the chimney removed The installer of the replace and gas appliance must des...

Страница 25: ...rther reduce the possibility of such a crack developing Wall ties should be fastened to the face of the replace with sheet metal screws and placed in the mortar joints of masonry trim Combustible mate...

Страница 26: ...RIAL FIREPLACE FACE STEEL LINTEL OPTIONAL WARNING THE SPACE BETWEEN THE FACE OF THE FIREPLACE AND THE NON COMBUSTIBLE FACING MATERIAL MUST MUST BE SEALED FAILURE TO PROPERLY SEAL THIS CRACK CAN CAUSE...

Страница 27: ...other wood goes a long way Start your re with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well when freshly cut the wood you p...

Страница 28: ...oors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to make a good re Add k...

Страница 29: ...ermine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney re The chimney cap can be removed for inspection maintenance and cleaning by...

Страница 30: ...for the installation of the replace 4 Do insulate the exterior walls surrounding the replace to prevent excessive heat loss from the replace 5 Do trim the face of the replace only with noncombustible...

Страница 31: ...liquids gases or pressurized containers near the replace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the replace 17 Don t fail to instruct all persons esp...

Страница 32: ...IRE BRICK BACK ASSEMBLY HANDLE DAMPER FIRE BRICK RT SIDE ASSEMBLY HEARTH REFRACTORY KEY NO 1 2 3 4 5 6 7 8 9 10 31 PARTS DIAGRAM AND LIST FIGURE 27 All repair part orders should be placed through your...

Страница 33: ...32 NOTES 53D9027...

Страница 34: ...ng code contains restrictions on the use of this replace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the replace...

Страница 35: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE...

Страница 36: ...SEPTEMBER 2008 53D9027 Rev 2 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: