NVB Series B-Vent Gas Fireplace

7412950

Framing and Finishing

Check appliance to make sure it is levelled 
and properly positioned.

The appliance should only be mounted on the following sur-
faces:

 

•  A flat combustible (burnable) surface.

 

•  A raised wooden platform.

 

•  A concrete block or other solid object  

 

   placed beneath each of the four corners  

 

   of the appliance.

To mount the appliance:
1. Choose unit location.
2. Four (4) nailing flanges are supplied with the fireplace 

(found on the fireplace hearth). To level the box and secure 
it firmly in place, remove the nailing flanges from the hearth 
and install at the sides of the fireplace as shown in Figure 6.

FP549

Fig. 6 

Adjustable drywall strip (nailing flange).

FP549

9/29/97

BR/BC

Nail Top 

Standoffs

Nail Side-

Nailing 

Flanges

Finishing

CAUTION: All joints between the finished 
wall and the appliance surround (top and 
sides) may be sealed only with non-com-
bustible material. Only noncombustible 
material can be applied as facing to the ap-
pliance surround (the black painted face).

When finishing the appliance, never obstruct or modify 
the air inlet/outlet grilles in any manner.
Finish the wall with the material of your choice. Refer to 
Figures 5a and 5b for specific clearances when install-
ing a combustible mantel or other combustible projec-
tion.

Gas Specification

 

 

 

 

Max. 

Min.

 

Model 

Fuel 

Gas Control 

Input  Input

  NVBR36RN  Natural 

Millivolt Hi/Lo 

30,000  21,500

  NVBC36RN  Natural 

Millivolt Hi/Lo 

30,000  21,500

  NVBR36RP  Propane 

Millivolt Hi/Lo 

30,000  22,000

  NVBC36RP  Propane 

Millivolt Hi/Lo 

30,000  22,000

  NVBR36EN  Natural  Electronic Ignition  30,000  21,500
  NVBC36EN  Natural  Electronic Ignition  30,000  21,500
  NVBR36EP  Propane  Electronic Ignition  30,000  22,000
  NVBC36EP  Propane  Electronic Ignition  30,000  22,000
  NVBR42RN  Natural 

Millivolt Hi/Lo 

30,000  21,500

  NVBC42RN  Natural 

Millivolt Hi/Lo 

30,000  21,500

  NVBR42RP  Propane 

MIllivolt Hi/Lo 

30,000  21,500

  NVBC42RP  Propane 

Millivolt Hi/Lo 

30,000  21,500

  NVBR42EN  Natural  Electronic Ignition  30,000  21,500
  NVBC42EN  Natural  Electronic Ignition  30,000  21,500
  NVBR42EP  Propane  Electronic Ignition  30,000  22,000
  NVBC42EP  Propane  Electronic Ignition  30,000  22,000

Gas Inlet & Manifold Pressures

   

Natural 

LP

  Minimum Inlet Pressure 

5.5” w.c. 

11.0” w.c.

  Maximum Inlet Pressure 

14.0” w.c. 

14.0” w.c.

  Manifold Pressure 

3.5”w.c. 

10.0” w.c.

NVBR36 / NVBC36 / NVBC42 / NVBR42

Certified to

ANSI Z21.50b-2002 / CSA 2.22b-2002 

Vented Gas Fireplace

High Elevations

Input ratings are shown in BTU per hour and are 
certified without deration for elevations up to 
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, 
installations must be in accordance with the 
current ANSI Z223.1/NFPA 54 and/or local codes 
having jurisdiction.
In Canada, please consult provincial and/or local 
authorities having jurisdiction for installations at 
elevations above 4,500 feet (1,370m).

Be sure to always maintain the proper one 
(1) inch distance to combustibles around 
B-vent pipe sections.

NOTE:

 Insulating for cold climates is strictly a recom-

mendation and not a requirement. 

Units:

 F34AR0, F34BR0, F34HR0, F34AC0, F34BC0, 

F34HC0, G34AR0, G34BR0, G34HR0, G34AC0, 
G34HC0

Air Shutter

 

Model 

Gap

 

NVBR36RN, NVBC36RN,  

8 mm 

 

  NVBR36EN, NVBC36EN
  NVBR42RN, NVBC42RN, 

10 mm 

 

  NVBR42EN, NVBC42EN
  NVBR36RP, NVBC36RP, 

2 mm 

 

  NVBR36EP, NVBC36EP
  NVBR42RP, NVBC42RP, 

2 mm 

 

  NVBR42EP, NVBC42EP

f i r e - p a r t s . c o m

Содержание NVBR36

Страница 1: ...er Do not store or use gasoline or other amma ble vapors and liquids in the vicinity of this or any other appliance FOR YOUR SAFETY If you smell gas 1 Open windows 2 Do not touch electrical switches 3...

Страница 2: ...ntels 6 Mantel Chart 6 Hearth 6 Insulating for Cold Climates 6 Framing Finishing 7 Final Finishing 7 Gas Speci cations 7 Gas Inlet Manifold Pressures 7 High Elevations 7 Parts Identi cation and Chase...

Страница 3: ...the appliance is installed directly on carpeting vinyl tile or any combustible material other than wood this appliance must be installed on a metal or wood panel extending the full width and depth of...

Страница 4: ...59mm Recessed Nailing Flange 6 DIA Rough Opening Width 41 Rough Opening Depth 3 76mm 1041mm FP562 Fig 2 NVBC36 Series speci cation and framing dimensions NVBC36 Series Gas Appliance Circulating Model...

Страница 5: ...ssed Nailing Flange 6 DIA Rough Opening Width 47 Rough Opening Depth 3 76mm 35 895mm 1194mm FP564 Fig 4 NVBC42 Series speci cation and framing dimensions NVBC42 Series Gas Appliance Circulating Model...

Страница 6: ...ng F 14 356 mm K 14 356 mm G 12 305 mm L 12 305 mm H 10 254 mm M 10 254 mm I 8 203 mm N 8 203 mm J 1 38 mm O 1 38 mm Black Sur round Face CFM164 CFM170 Fig 5b Combustible mantel leg minimum installati...

Страница 7: ...gnition 30 000 21 500 NVBC36EN Natural Electronic Ignition 30 000 21 500 NVBR36EP Propane Electronic Ignition 30 000 22 000 NVBC36EP Propane Electronic Ignition 30 000 22 000 NVBR42RN Natural Millivol...

Страница 8: ...the appliance location has not been accomplished install the required pipe Consult local plumbing code to assure proper pipe size The gas pipeline can be brought in through the right side of the appl...

Страница 9: ...ide a union so that gas line can be easily disconnected for burner or fan servic ing See gas speci cation for pressure details and ratings NOTE If ex connector is used it must be kept inside of the ap...

Страница 10: ...on excess wire completely within the EB1 Attach the cov erplate to the replace Fig 11 Fig 11 Junction box EB 1 hook up FP580 FP580 INSTA VENT FREE EB1 JUNCTION BOX 11 18 97 Outside Electrical Box Insi...

Страница 11: ...ng configuration Unacceptable venting configuration FP567a Fig 14 Venting con gurations when installing 36GSKBB 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 2 4 6 8 10 12 14 16 18 20 A FP567a Ven...

Страница 12: ...mes with a non ammonia household cleaner and warm water we recommend gas replace glass cleaner After that the glass should be cleaned two or three times during each heating season depending on the cir...

Страница 13: ...or units equipped with Hi Lo valves ame adjustment is accomplished by rotating the Hi Lo adjustment knob located near the center of the gas control Flame Characteristics It is important to periodicall...

Страница 14: ...B Series B Vent Gas Fireplace 7412950 LG151 NVB36 log flames 2 2 01 djt Red Glow Embers LG151 Fig 19 NVB36 ame appearance LG150 NVB42 log flames 2 1 01 djt LG150 Fig 20 NVB42 ame appearance fire parts...

Страница 15: ...or turn by hand do not try to repair it call a quali ed service technician Applying force or any attempted repair may result in a re or explo sion D Do not use this replace if any part has been under...

Страница 16: ...h in or turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it call a quali ed service technician Force or attempting repair may result in a re...

Страница 17: ...modisk For Air in the lines Thermopile needs a minimum 325mV Adjust pilot flame height All wiring connections Replace Thermopile Thermocouple needs a minimum of 14mV Defective valve Turn to pilot mete...

Страница 18: ...ld cable and boot from excessive temperatures Check for 24VAC across MV MV PV terminals If no voltage replace module Check electrical connections between module and gas control If okay replace gas con...

Страница 19: ...identical to taking care of the Standing Pilot models Maintenance Burner and Burner Compartment It is important to keep the burner and the burner compartment clean At least once per year the logs and...

Страница 20: ...3 5 Ceramic Tile single 57803 57803 6a Burner Ori ce Natural Manifold Ori ce 20003532 20003547 6b Burner Ori ce LP Manifold Ori ce 20003541 20003552 7 Thermodisk 20001558 20001558 8 Remote Switch Kit...

Страница 21: ...Assy Natural 4 Way 10002387 10002387 29b E Pilot Assy LP 4 Way 10002388 10002388 30 Sensing Electrodes 57885 57885 31 Ignition Device Honeywell 20000005 20000005 32 Transformer 7522409 7522409 33 Air...

Страница 22: ...Connection The EB 1 electrical junction box is available for use with the fan kits The EB 1 is standard on the electronic igni tion models Glass Doors Bi fold and single panel glass doors are availab...

Страница 23: ...damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this warranty...

Страница 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation fire parts com...

Отзывы: