73D4126

DVKST Series Gas Fireplace

SIGnaTure coMManD SySTeM operaTIon InSTrucTIonS

SySTeM conFIGuraTIon/SeTup

System configuration/setup is done on the Command Center.

Intermittent/Standing pilot Setup (Default intermittent)

1.  Holding the ON button on the Command Center while turning on the master switch will toggle 

between standing pilot and intermittent pilot. 

2.  After the above operation, one beep (for standing pilot) or two beeps (for intermittent pilot) will 

be given as confirmation.

Six-hour Safety Shutdown option (Default on)

1.  The system comes preset from the factory with a six (6) hour shutdown from its last command 

of operation. This is done to prevent the fireplace from continuing to operate if unattended. You 
may disable this feature if you wish.

noTe:

 By disabling this feature, your fireplace may continue to operate unattended.

2.  When the master switch is in the ON position (“-”), pressing the ON button and the OFF button 

on the Command Center simultaneously will toggle between enabling and disabling the six-hour 
shutdown option. 

3.  After the above operation, one beep (for enabling the six-hour shutdown option) or two beeps 

(for disabling the six-hour shutdown option) will be given as confirmation.

remote Transmitter learn Function (Default oFF)

1.  The RF receiver button located on the control board must be in the on position before the learn 

function can begin. Use paper clip to depress button. One beep for RF receiver ON or two beeps 
for RF receiver OFF will be given as confirmation.

2.  After the RF receiver is on, holding the OFF button on the Command Center while turning on the 

master switch will activate the learn function for the transmitter. 

3.  After the above operation, two beeps will be given and the green LED on the Command Center 

will flash for 10 seconds. 

4.  During the 10 seconds, press the OFF button on a transmitter to learn. Another two beeps will be 

given to confirm a successful learning. Refer to Transmitter Instructions for remote operation.

Shutting off the Standing pilot

To shut off the standing pilot for service or summer shut down, press and hold the ON button on 
the Command Center for 3 seconds when the master switch is in the ON position (“-”) and the main 
burner is off.

note

: Pilot will resume the next time system is turned on.

Key combinations for System Settings

 

Function 

operation 

Default Setting

 

Intermittent/Standing 

Hold the ON 

 button while turning on the master switch 

Intermittent

  Pilot Setup 

(Beep once for standing pilot, twice for intermittent pilot) 

Pilot

  Standing Pilot Temp. 

Hold the ON 

 button 3 seconds (when the master switch

  Shutoff 

on the main burner is off)

  RF Remote Receiver 

Push the RF receiver On/Off button on the control board 

RF OFF   

  On/Off 

Beep once for ON and beep twice for OFF

  Learn Remote 

Hold the OFF 

 button while turning on the master switch

  Transmitter 

(Beep twice then press any handheld remote button)

  6-hour safety  

Press the ON 

 button and OFF 

 button simultaneously 

ON

  shutdown setup 

(Beep once for ON, twice for OFF)

Содержание 500DVKST

Страница 1: ...y or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use...

Страница 2: ...ation 22 Electrical Wiring 22 Command Center Wall Installation 23 Optional Fan Blower Systems 24 Operating Instructions Signature Command 25 Operating Instructions 26 To Turn Off Gas 26 Signature Comm...

Страница 3: ...ace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified...

Страница 4: ...side of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as fo...

Страница 5: ...s are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installations must be in accordanc...

Страница 6: ...mm 39 6 1007 mm 44 6M 1137 mm 456M 108 mm 4456O 1130 mm 38 6 981 mm 23 584 mm 24 610 mm 4956O 1257 mm 30 762 mm 25 635 mm 1156O 292 mm 734126 DVKST KSTDV DIMS Figure 2 Fireplace and Framing Dimensions...

Страница 7: ...x with insulation or other materials This could cause a fire COLD CLIMATE INSULATION If you live in a cold climate seal all cracks around your appliance and wherever cold air could enter the room with...

Страница 8: ...where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable venting configura tions These units can be installed in a bedroom See...

Страница 9: ...CLEARANCES NOTE The combustible area above the facing must not protrude more than 1 2 from the facing If it does it is considered a mantel and must meet the mantel requirements listed in this manual...

Страница 10: ...nal fan must be done prior to final finishing to avoid costly reconstruction Only noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to co...

Страница 11: ...des and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration Vertical sections of this vent system require a minimum o...

Страница 12: ...xposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance be...

Страница 13: ...tion air inlet to any BTU h 3kW 12 30 cm for 10 000 BTU h 3kW 9 other appliances appliances 10 000 BTU h 3kW and 23 cm for appliances 10 000 100 000 Btuh 30kW 36 91 cm BTU h 3kW and 50 000 BTU h for a...

Страница 14: ...f the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimen sion on the Sidewall Vent Graph below locate the point intersecting w...

Страница 15: ...90 elbows per side wall installation is three 3 Figure 10 Aminimum of 24 is required before a 90 elbow If a 90 elbow is fitted directly after 24 vertical section mounted to the top of the fireplace t...

Страница 16: ...The maximum horizontal run with the 24 vertical pipe is 36 This measurement is taken from the collar of the fireplace or transition elbow to the face of the exterior wall See the Sidewall Venting Gra...

Страница 17: ...he flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration Vertical sections of thi...

Страница 18: ...tion FP1969 offset w wallstrap Figure 19 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firestop FP1669 within the parameters shown in Figures 20 and 21 2 Set fireplac...

Страница 19: ...roofing material overlaps the top edge of the flashing There must be a 1 clearance from the vent pipe to combustible materials 6 Continue to add pipe sections until the height of the vent cap meets th...

Страница 20: ...l codes not provided A CSA design certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA design certified equipment shutoff valve fro...

Страница 21: ...end that you install a sediment trap drip leg in supply line as shown in Figure 24 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and...

Страница 22: ...for gas leaks Figure 25 Signature Command Valve Pilot Adjustment Screw Pressure Outlet WARNING Do not use open flame to check for gas leaks Electrical Wiring This fireplace burner system will work wi...

Страница 23: ...all Do not extend beyond the 15 ft wire cable provided Route the wire from junction box to lower control area at bottom of fireplace Unplug the 12 cable from control box and command center Plug the 15...

Страница 24: ...t side of the outside firebox wall Junction box was installed at the factory 3 The junction box cover has a factory installed romex style strain relief connector After connecting the wires route the w...

Страница 25: ...hone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not fu...

Страница 26: ...f you do not smell gas go to next step 4 Install four 4 AA batteries provided in your Homeowner s Manual bag into the command center box Make sure the batteries orientation match 5 Press the master sw...

Страница 27: ...RFSC Three Flame Height Settings X Low battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes X Thermostatic Control Mode X Three Brightness Settings for Lights X...

Страница 28: ...epress button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation 2 After the RF receiver is on holding the OFF button on the Command Center while turning on the...

Страница 29: ...Flip the master switch to the off O position 2 Press the OFF button to Medium Low then Off 3 Hold the OFF button anytime for three seconds This command of OFF will remember all last settings before t...

Страница 30: ...no key is pressed The transmitter will send an OFF signal after reset 4 After reset the transmitter is operating in manual mode The room temperature is shown Manual Mode Figure 32 1 Press the ON butt...

Страница 31: ...f the fireplace is on the blower speed will take effect right away if the fire place is off the receiver will remember this setting and blower is still off 4 If you continue to press FAN button to the...

Страница 32: ...operation Turn the unit OFF before replacing batter ies F FP2150 low battery display 12 08 FP2150 Figure 39 Low Battery Display Child Proof Protection Figure 40 1 Press and hold the ON and OFF buttons...

Страница 33: ...the transfer of oil from hands will reduce the lifespan of the bulbs It is advisable to handle the light bulbs with a clean cloth 4 The light lenses are included in the Homeowner s Manual packet Remov...

Страница 34: ...nly on the carry over areas between the flames To better enable the gas to permeate the rock wool apply the rock wool in light fluffy pieces WARNING Do not use the entire bag of rock wool to cover the...

Страница 35: ...ith the wide end of the log toward you and the flat edge on the bottom right place the log over the right end of all three burners making sure to align the notches in the log with the first tine from...

Страница 36: ...he log should rest against log 3 Log 4 LG729 5 Move to the other side of the unit to place the remaining logs LG730 KSTDV log 5 Log 5 LG730 6 From the front of the unit with the controls on your right...

Страница 37: ...creating a V shape with log 5 LG731 KSTDV log 6 Log 6 LG731 LG732 Log 8 Log 7 LG732 8 Hold log 7 with the Y pointing away from you and place the log on the notch located on the top of log 3 angling t...

Страница 38: ...the control compartment logs and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year Make sure the burner porting pilot air opening and burner air opening are free...

Страница 39: ...ls may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit...

Страница 40: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check v...

Страница 41: ...scription Qty 500DVKST 1 Bulb 2 73D0020 2 Bulb Socket 2 73D4521 3 Glass Frame Assembly 2 73D0159 4 Junction Box Assembly not shown 1 26D2128 5 Light Lens 2 73D0022 6 Access Doors 4 73D3258 7 Front Cov...

Страница 42: ...42 73D4126 DVKST Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 730024 KHLDV SG parts 12 08 2 22 29 30 17 13 17 12 13 18 16 15 3 1 5 14 11 4 23 24 25 26 26 27 27 28...

Страница 43: ...1 1 73D4528 73D4528 16 Burner Assy Front 2 1 73D4529 73D4529 17 Venturi Front Burner 2 73D4537 73D4537 18 Venturi Middle Burner 1 73D4537 69D1026 19 Wire Valve Control not shown 1 80D0010 80D0010 20...

Страница 44: ...ireplace REPLACEMENT PARTS Item Description Qty 500DVKST 1 Log 1 1 73D4090 2 Log 2 1 73D4091 3 Log 3 1 73D4092 4 Log 4 1 73D4093 5 Log 5 1 73D4094 6 Log 6 1 73D4095 7 Log 7 1 73D4096 8 Log 8 1 73D4097...

Страница 45: ...Front Left Cottage Red 2 73D4135 5 Brick Front Right Cottage Red 2 73D4136 1 Brick Wall Eng Side Tavern Brown 1 73D4149 2 Brick Wall Air Side Tavern Brown 1 73D4150 3 Brick Floor Tavern Brown 2 73D41...

Страница 46: ...46 73D4126 DVKST Series Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT components REPLACEMENT PARTS...

Страница 47: ...Heat Deflector Firestop 90 Elbow and Adjustable Pipe 11 to 14 24 Section of Pipe 2 1 Vertical Termination see below see below 5DT VC 2 1 Extended Vertical Termination 58DVA VCE 1283 2 1 High Wind Ver...

Страница 48: ...48 73D4126 DVKST Series Gas Fireplace...

Страница 49: ...73D4126 49 DVKST Series Gas Fireplace...

Страница 50: ...cordance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of...

Страница 51: ...fetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly d...

Страница 52: ...DVKST Series Gas Fireplace MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com Efficiency Ratings Model EnerGuide Ratings D O E Fireplace Efficiency AFUE 500DVKSTNTSC 77 30 67 40 500DVKSTPTSC 7...

Отзывы: