BDVR Series Direct Vent Gas Fireplace

10003357

WARNING:  BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

electrode at pilot.

pilot and push the red button again.  If pilot will not
light - check gap at electrode and pilot-should be
1/8" to have a strong spark.

B.  Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at
electrode and pilot. If no spark to pilot, and elec
trode wire is properly connected, replace ignitor.

2. Pilot will not stay lit after

A.  Defective pilot generator

Check pilot flame.  Must impinge on thermo-

carefully following lighting

(thermocouple), remote wall

couple/thermopile.  Note: this pilot burner assem

instructions.

switch.

bly utilizes both-a thermocouple and a thermopile.
The thermocouple operates the main valve
operation (On and Off). Clean and or adjust pilot for
maximum flame impingement on thermopile and
thermocouple.

B. Defective automatic valve

Turn valve knob to “Pilot”.  Maintain flow to pilot;
millivolt meter should read greater than 10 mV.  If
the reading is okay and the pilot does not stay on,
replace the gas valve.  Note:  An interrupter block
(not supplied) must be used to conduct this test.

3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connec

main burner

tions. Jumper wire across terminals at wall
switch, if burner comes on, replace defective wall
switch. If okay, jumper wires across wall switch
wires at valve, if burner comes on, wires are faulty
or connections are bad.

B. Thermopile may not be

1. Be sure wire connections from thermopile at

generating sufficient

gas valve terminals are tight and thermopile is fully

millivoltage.

inserted into pilot bracket.

2. One of the wall switch wires may be grounded.

Remove wall switch wires from valve terminals if
pilot now stays lit, trace wall switch wiring for
ground. May be grounded to fireplace or gas
supply.

3. Check thermopile with millivolt meter. Take

reading at thermopile terminals of gas valve.
Should read 250-300 millivolts (minimum 150)
while holding valve knob depressed in pilot
position and wall switch “Off”.  Replace faulty
thermopile if reading is below specified minimum.

C. Plugged burner orifice.

Check burner orifices for debris and remove.

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

operator.

millivolt meter should read greater than 100 mV.  If
the reading is okay and the burner does not come on,
replace the gas valve.

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

pilot safety to drop out.

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

terminal.

flue gases)

Troubleshooting the Gas Control System

NOTE:  Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

SIT NOVA 820 MILLIVOLT VALVE

Содержание 33BDVR

Страница 1: ...r from your neighbor s phone Follow the gas suppliers instructions If you cannot reach your gas supplier call the fire department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FI...

Страница 2: ...Location 7 EB 1 Electrical Box 8 Electronic Gas Control Valve 8 General Venting Information General Venting Information Termination Location 10 General Information Assembling Vent Pipes 11 How to Use...

Страница 3: ...installed on a metal or wood panel extending the full width and depth of the fireplace 12 This fireplace requires adequate ventilation and combustion air to operate properly 13 This fireplace must no...

Страница 4: ...5 140mm K 7 191mm 10 254mm 8 213mm 8 210mm L 8 216mm 13 343mm 12 318mm 12 318mm M 1 18mm 1 18mm 1 18mm 1 18mm Framing Dimensions N 29 737mm 35 889mm 35 889mm 37 959mm O 33 851mm 36 927mm 39 1003mm 43...

Страница 5: ...and the following Mantel Charts The fitting of a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart Noncombustible mantels and legs may be ins...

Страница 6: ...he floor are located just behind the access door grille on the left and right side of the unit 3 Frame in the fireplace with a header across the top It is important to allow for the finished wall face...

Страница 7: ...to the 120 volt power supply Alternate Switch Location The remote switch can be installed on the front side of the access door Simply mount the switch to the bracket provided and screw the bracket to...

Страница 8: ...ect the ground wire of the supply line to the green screw of the socket assembly 8 Refit the socket assembly back into the electrical box and replace the cover plate Secure the cable with the clamp on...

Страница 9: ...gs within 24 610mm from the front of the termination hood General Venting Do not locate termination hood where excessive snow or ice build up may occur Be sure to check vent termination area after sno...

Страница 10: ...assembly 5m above the meter regulator assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances t...

Страница 11: ...bustible 2 50mm B Combustible 6 152mm Noncombustible 2 50mm A Balcony with no side wall G Combustible Noncombustible 12 305mm G Balcony with perpendicular side wall H 24 610mm J 20 508mm H J B Recesse...

Страница 12: ...vented directly to a termination located on the rear wall behind the appliance Only CFM Corporation venting components are approved to be used in these applications Refer to Venting Components listed...

Страница 13: ...ing for Combustible Wall 9 240mm 10 264mm Fireplace Hearth Framing Detail Opening for Noncombustible Wall 7 190mm VO584 100 Fig 14 Locate vent opening on wall Max Length 12 305mm 8 Screws 2 8 Screws 2...

Страница 14: ...efers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall Horizontal plane means no vertical rise exists on this portion of the vent assembly The maxim...

Страница 15: ...ming off the transition elbow Canadian USA Installations The venting system must conform with local codes or in the absence of local codes with National Fuel Gas Code ANSI Z223 1 NFPA 54 latest editio...

Страница 16: ...lace with three 3 screws Fig 24 Follow with the installation of the inner and outer elbow Again secure joints with three 3 sheet metal screws Wipe off any excess high temperature sealant STEP 4 Measur...

Страница 17: ...e wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide into the vent pipe and secure to the wall 7 Level the soil to maintain a 4 102mm clearance below sn...

Страница 18: ...maximum of three 90 elbows Vertical Through the Roof Applications If the foundation is recessed use recess brackets not supplied for securing lower portion of the snorkel Fasten brackets to wall first...

Страница 19: ...tion always face downward Fig 33 11 11 Joist Joist Firestop Spacer Nails 4 Upper Floor Attic Insulation Shield Ceiling Installation CFM100 Fig 32 Place firestop spacer s and secure 40 12m Storm Collar...

Страница 20: ...TDVSNORK for Below Grade Installation 45 Elbow 7TDV45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90 Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical...

Страница 21: ...e Also initial paint curing may deposit a slight film on the glass It is therefore recommended the glass be cleaned two or three times with a non ammonia based household cleaner and warm water We reco...

Страница 22: ...the front end of this log will also set against the back wall of the deflector 6 Scatter the ember material over the front area of the burner housing assembly Fig 38 Do not pack this material tightly...

Страница 23: ...firebox base Do not place any of the lava rock mate rial on the burner housing assembly 39BDVR Refer to Figure 40 1 Remove the top louvre assembly 2 Remove the window frame assembly 3 Fit the rear lef...

Страница 24: ...Flame Characteristics Flame Temperature Adjustment L O HI Turn counterclockwise to decrease flame height Turn clockwise to increase flame height Fig 42 Flame adjustment knob for Honeywell valve Honey...

Страница 25: ...ally When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and wi...

Страница 26: ...n by hand do not try to repair it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediat...

Страница 27: ...All Wiring Connections Replace Piezo Ignitor Supply Line Hooked Up Shutoff Valve Open Pilot Stays Lit For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connection...

Страница 28: ...er wire across terminals at wall switch if burner comes on replace defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wires are faulty or connections are b...

Страница 29: ...ES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY...

Страница 30: ...B and diaphram C b Ensure the rubber gasket D is properly posi tioned and install the new HI LO pressure regula tor to the valve using the new screws E supplied with the kit Tighten screws securely Re...

Страница 31: ...rmopile millivolt gas valve Most of these components may require only an occasional checkup and cleaning and some may require adjustment If repair is necessary it should be performed by a qualified te...

Страница 32: ...b 16 11 20 24 15 8 7 5 3a b 4a b 19 21 22 23 6 10 25 9 26 1f 1h 1b 33BDVR 1c 1a 1b 36BDVR 1f 1a 1e 1g 39BDVR CFM Specialty Home Products reserves the right to make changes in design materials specifi...

Страница 33: ...T Top Convertible NG 10002268 10002268 10002268 10002268 Pilot orifice SIT Top Convertible Prop 10002269 10002269 10002269 10002269 6 Pilot hood SIT Top Convertible 10002385 10002385 10002385 10002385...

Страница 34: ...481 55686 57437 57438 Gasket window glass 57317 57317 57317 57317 20 Clamp window frame assembly 54174 54174 54174 54174 21 Window trim polished brass w magnets 55005 57480 57483 57485 22 Top louvre a...

Страница 35: ...the unit to a conveniently located wall socket Method B Using EB 1 Receptacle Box The EB 1 receptacle box Pt ZA1200 may be hard wired into the house supply The fan lead is then plugged into the EB 1...

Страница 36: ...al rewiring of this fan must be done by a licensed electrician Wiring Instructions Black White Ground Speed Control Temperature Sensor Fan FP1025 Fig 52 FK24 fan wiring Take care when handling the ref...

Страница 37: ...instructions supplied with the kit 5 Place the 2 pieces of ceramic refractory along the base of the bay window 6 Hang the Bay Window Assembly over the existing window frame assembly 7 Reinstall the up...

Страница 38: ...upon inspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisi...

Страница 39: ...39 BDVR Series Direct Vent Gas Fireplace 10003357...

Страница 40: ...9 76 79 58 36BDVRRP 48 9 77 80 58 36BDVREN 48 9 76 79 58 36BDVREP 48 9 77 80 58 39BDVRRN 56 5 77 79 63 39BDVRRP 56 5 78 80 63 39BDVREN 56 5 77 79 63 39BDVREP 56 5 78 79 63 43BDVRRN 52 9 76 77 63 43BD...

Отзывы: