-4-
2. Grounded, cord-connected tools intended for use on a supply circuit having a nominal rating
less than 150 volts:
This tool is intended for use on a circuit that has an outlet that looks like the one illustrated in
Sketch A in Figure 1. The tool has a grounding plug that looks like the plug illustrated in Sketch
A in Figure 1. A temporary adapter, which looks like the adapter illustrated in Sketches B and
C, may be used to connect this plug to a 2-pole receptacle as shown in Sketch B if a properly
grounded outlet is not available. The temporary adapter should be used only until a properly
grounded outlet can be installed by a qualified electrician. The green-colored rigid ear, lug,
and the like, extending from the adapter must be connected to a permanent ground such as a
properly grounded outlet box.
3. Grounded, cord-connected tools intended for use on a supply circuit having a nominal rating
between 150-250 volts, inclusive:
This tool is intended for use on a circuit that has an outlet that looks like the one illustrated in
Sketch D in Figure 1. The tool has a grounding plug that looks like the plug illustrated in Sketch
D in Figure 1. Make sure the tool is connected to an outlet having the same configuration as the
plug. No adapter is available or should be used with this tool. If the tool must be reconnected for
use on a different type of electric circuit, the reconnection should be made by qualified service
personnel; and after reconnection, the tool should comply with all local codes and ordinances.
Note : In Canada, the use of a temporary adaptor is not
permitted by the Canadian Electrical Code.
GROUNDING
PIN
COVER OF GROUNDED
OUTLET BOX
METAL SCREW
(A)
(B)
FIGURE 1
Grounding methods
Note : In Canada, the use of a temporary adaptor is not permitted by the
Canadian Electrical Code.
Содержание MI-92300
Страница 1: ...MODEL NO MI 92300 OPERATING MANUAL START STOP ON OFF...
Страница 15: ...14...
Страница 17: ......
Страница 20: ...FAULT DISPLAY...